14
SS-SVX07B-E4
Installation
Power and control wiring
Table 7 - Control interconnection
Outdoor unit
Number of wires x section area (mm²)
Including ground wire
TTK 512
3 x 2.5
TTK 518
2 x 1.5
TTK 524
2 x 1.5
TTK 530
2 x 1.5
TTK 536
2 x 1.5
TTK 048
2 x 1.5
TTK 060
2 x 1.5
TWK 512
5 x 1.5
TWK 518
5 x 1.5
TWK 524
5 x 1.5
TWK 530
6 x 1.5
TWK 536
6 x 1.5
TWK 048
6 x 1.5
TWK 060
6 x 1.5
Table 8 - Power supply outdoor unit (1)
Number of wires x section area (mm²)
Including ground wire
TTK/TWK 512
-
TTK/TWK 518
3 x 2.5
TTK/TWK 524
3 x 2.5
TTK/TWK 530
4 x 2.5
TTK/TWK 536
4 x 2.5
TTK/TWK 048
4 x 2.5
TTK/TWK 060
4 x 2.5
(1) Indoor and outdoor units are powered separately
(2) Number of wires and section area are given for a
maximum wire length of 50m. If the wire is longer
than 50m, these must be recalculated.
Table 9 - Power supply indoor unit (1)
Without electric heater
With electric heater
Number of wires x section area (mm²)
Number of wires x section area (mm²)
MCD/MWD 512
3 x 1.5
3 x 2.5 / 3 x 4
MCD/MWD 518
3 x 1.5
3 x 4
MCD/MWD 524
3 x 1.5
3 x 4
MCD/MWD 530
3 x 1.5
4 x 4
MCD/MWD 536
3 x 1.5
4 x 4
MCD/MWD 048
3 x 1.5
4 x 4
MCD/MWD 060
3 x 1.5
4 x 4
(1) Indoor and outdoor units are powered separately
(2) Number of wires and section area are given for a
maximum wire length of 50m. If the wire is longer
than 50m, these must be recalculated.