Table 4-6 (Continued)
50 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt; "On")
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
180
200
220
240
260
280
300
320
340
360
380
50
55
60
65
70
75
80
85
90
95
100
SUCTION PRESSURE, PSIG
DISCHARG
E PRESSURE, PSIG
105 F OD Ambient
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.
4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.
55 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt, "On")
50
55
60
65
70
75
80
85
90
95
100
180
200
220
240
260
280
300
320
340
360
55 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt, "On")
Full Load
(Based on Indoor Airfow of 400 CFM / Ton)
Cooling Cycle Pressure Curve
65 F OD Ambient
75 F OD Ambient
85 F OD Ambient
95 F OD Ambient
105 F OD Ambient
D
is
c
har
ge
P
res
s
u
re
, P
S
IG
Suction Pressure, PSIG
Summary of Contents for INTELLIPAK RT-SVX10C-EN
Page 16: ...15 Figure 3 1 Minimum Operation and Service Clearances for Single Multiple Unit Installation...
Page 17: ...16 Figure 3 2A SAHF Cooling Only Units 20 thru 75 Ton...
Page 19: ...18 Figure 3 2B SEHF SFHF SLHF SSHF SXHF Units 20 thru 75 Ton...
Page 21: ...20 Figure 3 2C S_HG Cooling Heating Units 90 through 130 Ton...
Page 25: ...24 Figure 3 4 Typical Unit Rigging Figure 3 5 Unit Base Roof Curb Section...
Page 52: ...51 Field Connection Diagram Notes for 20 through 130 Ton CV or VAV Applications...
Page 86: ...84 Figure 4 6 Compressor Locations...
Page 117: ...115...
Page 118: ...116...