PKG-PRC007-EN
44
Table ED-8 — Genius – Electrical Features - SAVE100
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Consumption
Current
Fan
Voltage
KW
CNO
KW
CNO
KW
CNO
KW
A
220V
14.10
14.10
4.14
32.34
STD
380V
4.17
8.16
4.17
8.16
1.22
2.39
9.56
18.71
440V
7.05
7.05
2.07
16.17
220V
14.10
14.10
5.53
33.73
Option 1
380V
4.17
8.16
4.17
8.16
1.64
3.19
9.98
19.51
440V
7.05
7.05
2.76
16.86
220V
14.10
14.10
7.32
35.52
Option 2
380V
4.17
8.16
4.17
8.16
2.23
4.23
10.57
20.55
440V
7.05
7.05
3.66
17.76
Plenum Box
220V
14.10
14.10
1.80
30.00
Option
380V
4.17
8.16
4.17
8.16
0.45
1.04
8.79
17.36
440V
7.05
7.05
0.90
15.00
Maximum operation values
Compressor 1
Compressor 2
Fan Motor
Current
Fan
Voltage
CMO
CMO
CMO
A
220V
19.80
19.80
5.18
44.78
STD
380V
11.46
11.46
2.99
25.91
440V
9.90
9.90
2.59
22.39
220V
19.80
19.80
6.91
46.51
Option 1
380V
11.46
11.46
3.99
26.91
440V
9.90
9.90
3.46
23.26
220V
19.80
19.80
9.15
48.75
Option 2
380V
11.46
11.46
5.28
28.20
440V
9.90
9.90
4.58
24.38
Plenum Box
220V
19.80
19.80
2.25
41.85
Option
380V
11.46
11.46
1.30
24.22
440V
9.90
9.90
1.13
20.93
Start-up values
Compressor 1
Compressor 2
Fan Motor
Fan
Voltage
LRA
LRA
LRA
220V
128.00
128.00
30.92
STD
380V
74.11
74.11
17.85
440V
64.00
64.00
15.46
220V
128.00
128.00
48.36
Option 1
380V
74.11
74.11
27.92
440V
64.00
64.00
24.18
220V
128.00
128.00
60.45
Option 2
380V
74.11
74.11
34.90
440V
64.00
64.00
30.23
Plenum Box
220V
128.00
128.00
11.25
Option
380V
74.11
74.11
6.50
440V
64.00
64.00
5.63
Electrical
Data
•
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
CMO = Maximum operation current.
•
LRA = Locked rotor amps.
•
STD Option - evaporator fan motor -1.5 CV.
•
Option 1 - evaporator fan motor -2 CV.
•
Option 2 - evaporator fan motor -3 CV.
•
Plenum box option - evaporator fan motor -0.5 CV.
•
Size the electrical wiring using the maximum operation currents.