27
PKG-PRC007-EN
Performance
Data
Air Cooled
60 Hz
Table PD-11 — Gross Cooling Capacities SRVE-050
Metric
Ambient Temperature (°C)
29.5
35.0
Entering Wet Bulb Temperature (°C)
Ent.
16.0
19.5
23.0
16.0
19.5
23.0
DB
m3/h
(ºC)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
24
22.5
18.6
25.2
14.3
28.1
10.0
21.7
18.2
24.3
14.0
27.1
9.6
4590
27
22.6
21.9
25.2
17.8
28.0
13.5
21.9
21.5
24.3
17.5
27.1
13.1
29
23.4
23.4
25.1
20.7
28.0
16.3
22.8
22.8
24.3
20.3
27.1
16.0
32
24.6
24.6
25.2
23.5
28.0
19.2
23.9
23.9
24.4
23.1
27.1
18.9
24
22.7
19.2
25.5
14.7
28.4
10.1
22.0
18.9
24.6
14.3
27.4
9.7
4970
27
23.0
22.6
25.4
18.4
28.4
13.8
22.3
22.1
24.6
18.0
27.4
13.4
29
24.0
24.0
25.4
21.5
28.3
16.8
23.3
23.3
24.6
21.1
27.3
16.5
32
25.1
25.1
25.6
24.3
28.3
19.9
24.5
24.5
24.8
23.9
27.3
19.5
24
23.0
19.8
25.7
15.0
28.6
10.2
22.2
19.4
24.8
14.7
27.6
9.8
5355
27
23.3
23.2
25.7
18.9
28.6
14.1
22.6
22.6
24.8
18.6
27.6
13.7
29
24.5
24.5
25.7
22.2
28.6
17.3
23.8
23.8
24.8
21.8
27.6
16.9
32
25.7
25.7
25.9
25.1
28.6
20.5
24.9
24.9
25.1
24.6
27.6
20.2
24
23.2
20.4
25.9
15.3
28.9
10.2
22.4
20.0
25.0
15.0
27.9
9.9
5740
27
23.7
23.7
25.9
19.5
28.9
14.3
23.0
23.0
25.0
19.1
27.8
14.0
29
24.9
24.9
25.9
22.9
28.8
17.7
24.2
24.2
25.0
22.5
27.8
17.4
32
26.1
26.1
26.2
25.8
28.8
21.1
25.4
25.4
25.4
25.3
27.8
20.8
Table PD-11 — Gross Cooling Capacities SRVE-050 (Cont.)
Metric
Ambient Temperature (°C)
40.5
46
Entering Wet Bulb Temperature (°C)
Ent.
16.0
19.5
23.0
16.0
19.5
23.0
DB
m3/h
(ºC)
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
TGC
SHC
24
20.9
17.9
23.4
13.6
26.1
9.3
20.1
17.5
22.5
13.2
25.1
8.9
4590
27
21.2
21.0
23.4
17.1
26.1
12.8
20.5
20.4
22.5
16.7
25.1
12.4
29
22.2
22.2
23.4
20.0
26.1
15.6
21.5
21.5
22.5
19.6
25.0
15.2
32
23.3
23.3
23.6
22.7
26.1
18.5
22.5
22.5
22.7
22.2
25.0
18.1
24
21.2
18.5
23.7
14.0
26.4
9.4
20.3
18.1
22.7
13.6
25.3
9.0
4970
27
21.6
21.6
23.7
17.7
26.3
13.0
20.9
20.9
22.7
17.3
25.3
12.7
29
22.6
22.6
23.7
20.7
26.3
16.1
21.9
21.9
22.7
20.3
25.3
15.7
32
23.8
23.8
23.9
23.4
26.3
19.2
23.0
23.0
23.0
22.9
25.3
18.8
24
21.4
19.1
23.9
14.3
26.6
9.4
20.5
18.7
23.0
13.9
25.5
9.1
5355
27
22.0
22.0
23.9
18.2
26.6
13.4
21.2
21.2
22.9
17.8
25.5
13.0
29
23.1
23.1
23.9
21.4
26.6
16.6
22.3
22.3
23.0
21.0
25.5
16.2
32
24.2
24.2
24.3
24.1
26.5
19.8
23.4
23.4
23.4
23.4
25.5
19.4
24
21.6
19.6
24.1
14.6
26.8
9.5
20.7
19.2
23.1
14.2
25.7
9.2
5740
27
22.3
22.3
24.1
18.7
26.8
13.6
21.6
21.6
23.1
18.3
25.7
13.3
29
23.5
23.5
24.1
22.1
26.8
17.0
22.7
22.7
23.2
21.6
25.7
16.6
32
24.6
24.6
24.6
24.6
26.7
20.4
23.8
23.8
23.8
23.8
25.7
20.0
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)