![Trane GECA Installation Operation & Maintenance Download Page 30](http://html1.mh-extra.com/html/trane/geca/geca_installation-operation-and-maintenance_1150167030.webp)
WSHP-PRC004-EN
30
GECA 009 –
Heating – I-P
Performance
Data
Tabulated performance data is tabulated for heating at 68 F [20 C] DB entering air at ARI-ISO 13256-1 rated CFM.
Multipliers must be used to correct performance at conditions other than those tabulated. Data shown in
BOLD
type is performance and
multipliers at ARI-ISO 13256-1 WLHP and GLHP conditions.
RATED GPM: 2.3
MINIMUM CFM: 240
RATED CFM: 300
MAXIMUM CFM: 300
Table PD-5 – 009 Heating Performance
Htg Cap
Absorb
Power
Ft.
ISO Cap
ISO Pwr
ISO
EWT
GPM
Mbtuh
Mbtuh
kW
COP
LWT
Hd
CFM
Mbtuh
kW
COP
1.5
6.8
4.9
0.78
2.5
15.6
3.0
333
6.8
0.79
2.5
1.8
7.1
5.2
0.79
2.6
17.5
4.1
333
7.1
0.80
2.6
2.1
7.3
5.4
0.80
2.7
18.7
5.0
333
7.3
0.81
2.6
25
2.3
7.5
5.5
0.81
2.7
19.7
6.0
333
7.5
0.82
2.7
2.4
7.5
5.6
0.81
2.7
19.9
6.3
333
7.5
0.82
2.7
2.6
7.6
5.7
0.81
2.8
20.4
7.1
333
7.6
0.82
2.7
2.7
7.8
5.8
0.82
2.8
20.8
7.8
333
7.8
0.83
2.7
2.9
7.8
5.9
0.82
2.8
21.1
8.6
333
7.8
0.83
2.8
1.5
7.9
6.0
0.82
2.8
24.8
3.0
333
7.9
0.82
2.8
1.8
8.2
6.3
0.83
2.9
26.7
4.1
333
8.2
0.84
2.9
2.1
8.4
6.4
0.84
2.9
27.9
5.0
333
8.4
0.84
2.9
35
2.3
8.6
6.6
0.84
3.0
28.9
6.0
333
8.6
0.85
3.0
2.4
8.7
6.7
0.85
3.0
29.1
6.3
333
8.7
0.86
3.0
2.6
8.8
6.8
0.85
3.0
29.6
7.1
333
8.8
0.86
3.0
2.7
8.9
6.9
0.85
3.1
30.0
7.8
333
8.9
0.87
3.0
2.9
9.0
7.0
0.86
3.1
30.3
8.6
333
9.0
0.87
3.0
1.5
9.1
7.1
0.86
3.1
34.0
3.0
333
9.1
0.86
3.1
1.8
9.4
7.4
0.87
3.2
35.9
4.1
333
9.4
0.88
3.1
2.1
9.6
7.6
0.88
3.2
37.1
5.0
333
9.6
0.88
3.2
45
2.3
9.8
7.8
0.88
3.2
38.0
6.0
333
9.8
0.89
3.2
2.4
9.9
7.8
0.89
3.3
38.3
6.3
333
9.9
0.90
3.2
2.6
10.0
7.9
0.89
3.3
38.8
7.1
333
10.0
0.90
3.2
2.7
10.1
8.0
0.89
3.3
39.2
7.8
333
10.1
0.91
3.3
2.9
10.2
8.1
0.90
3.3
39.5
8.6
333
10.2
0.91
3.3
1.5
10.5
8.4
0.91
3.4
43.8
2.9
333
10.5
0.91
3.4
1.8
10.7
8.6
0.91
3.4
45.6
4.1
333
10.7
0.92
3.4
2.1
10.9
8.8
0.92
3.5
46.6
5.0
333
10.9
0.93
3.4
55
2.3
11.0
9.0
0.93
3.5
47.3
6.0
333
11.0
0.93
3.5
2.4
11.1
9.0
0.93
3.5
47.5
6.3
333
11.1
0.94
3.5
2.6
11.2
9.1
0.93
3.5
48.0
7.1
333
11.2
0.94
3.5
2.7
11.3
9.2
0.93
3.5
48.4
7.8
333
11.3
0.95
3.5
2.9
11.4
9.3
0.94
3.6
48.7
8.6
333
11.4
0.95
3.5
1.5
11.9
9.8
0.95
3.7
54.9
2.9
333
11.9
0.96
3.6
1.8
12.2
10.1
0.96
3.7
57.0
4.1
333
12.2
0.97
3.7
2.1
12.4
10.3
0.97
3.7
58.1
5.0
333
12.4
0.98
3.7
68
2.3
12.6
10.5
0.98
3.8
59.0
6.0
333
12.6
0.99
3.7
2.4
12.7
10.5
0.98
3.8
59.3
6.3
333
12.7
0.99
3.7
2.6
12.8
10.6
0.98
3.8
59.8
7.0
333
12.8
1.00
3.8
2.7
12.9
10.7
0.99
3.8
60.2
7.8
333
12.9
1.00
3.8
2.9
13.0
10.8
0.99
3.8
60.6
8.6
333
13.0
1.01
3.8
1.5
12.9
10.8
0.99
3.8
62.6
2.9
333
12.9
0.99
3.8
1.8
13.3
11.1
1.00
3.9
64.8
4.0
333
13.3
1.00
3.9
2.1
13.5
11.3
1.01
3.9
66.1
5.0
333
13.5
1.01
3.9
77
2.3
13.7
11.5
1.01
4.0
67.1
6.0
333
13.7
1.02
3.9
2.4
13.8
11.6
1.02
4.0
67.4
6.3
333
13.8
1.03
3.9
2.6
13.9
11.7
1.02
4.0
67.9
7.0
333
13.9
1.03
3.9
2.7
14.0
11.8
1.03
4.0
68.4
7.8
333
14.0
1.04
4.0
2.9
14.1
11.9
1.03
4.0
68.8
8.5
333
14.1
1.05
4.0
1.5
13.9
11.7
1.02
4.0
70.2
2.9
333
13.9
1.03
4.0
1.8
14.3
12.1
1.04
4.1
72.7
4.0
333
14.3
1.04
4.0
2.1
14.6
12.4
1.04
4.1
74.0
5.0
333
14.6
1.05
4.1
86
2.3
14.8
12.6
1.05
4.1
75.1
6.0
333
14.8
1.06
4.1
2.4
14.9
12.7
1.06
4.1
75.4
6.3
333
14.9
1.06
4.1
2.6
15.0
12.8
1.06
4.2
76.0
7.0
333
15.0
1.07
4.1
2.7
15.2
12.9
1.06
4.2
76.5
7.8
333
15.2
1.08
4.1
2.9
15.3
13.1
1.07
4.2
77.0
8.5
333
15.3
1.08
4.1
Table 6 – Fan Correction Factors – Model GECA 009
Entering
Cooling
Sensible
Cooling Input
Heating
Heating Input
CFM
Capacity
Capacity
Watts
Capacity
Watts
267
0.963
0.937
0.998
0.978
1.068
333
1.000
1.000
1.000
1.000
1.000