background image

 

 

13.5

 

START UP PROCEDURE 

1)

 

With the switch closed, open the electrical panel and exclude compressor (refer to the wiring diagram on the 

unit). Close the panel, set switch to “ON” (to give power to the unit). 
2)

 

Wait for the start of the microprocessor and control. Make sure that the temperature of the oil is hot enough. 

The oil temperature must be at least 5°C higher than the saturation temperature of the refrigerant inside the 

compressor. 
3)

 

Place the unit in the “ON” and wait until the unit is indicated on the display-On. 

4)

 

Turn on the pumps (at max speed if with inverter). 

5)

 

Verify that the loss of load of the evaporator is equal to that of the project and correct if necessary. The 

pressure drop on the evaporator must be read on the service valves installed on the evaporator piping as a 

standard. Do not measure the load losses in points where any valves and / or filters are interposed. 
6)

 

Check for air in cleaning filters, and then drain the system. 

7)

 

Return the pump to the factory setting. 

8)

 

Turn off the power (into standby mode) and make sure the pumps stop after about 2 minutes. 

Verify that the local temperature subcooling is set to the required value by pressing the Set button. 
9)

 

Turn the main switch to “OFF”. Open the cabinet. Reactivate the compressors. Close the cabinet. Turn the main 

switch to “ON” (to give power to the unit). 

10)

 

Wait for the start of the microprocessor and control.  

11)

 

When the compressor is started, wait about 1 minute for the system begins to stabilize. 

12)

 

Check the pressure of evaporation and condensation of refrigerant. 

13)

 

Verify that, after a period of time necessary for the stabilization of the refrigerant circuit, the liquid indicator 

placed on the inlet pipe to the expansion valve is completely filled (no bubbles), and that the moisture indicator 

signs ‘Dry’. The passage of bubbles within the liquid indicator may indicate a low amount of refrigerant, or an 

excessive pressure drop through the filter drier, or an expansion valve blocked at the maximum opening position 
14)

 

In addition to checking the sight glass, check the operating parameters of the circuit controlling: 

a) - Overheating compressor 

b) - Overheating compressor discharge 

c) – Sub cooling of the liquid exiting the condenser coil 

d) - Evaporation pressure 

c) - Condensing pressure 
15)

 

Measure the values of pressure and temperature by means of the suitable instrumentation and make comparison 

by reading the corresponding values directly on the display of the microprocessor on board 
16)

 

To temporarily turn off the unit put on standby the unit key or open the remote contact (terminals shown in the 

wiring diagram provided with the unit) of the terminal X (by means of a remote switch installed by the customer) 

or set time zones. The microprocessor will activate the shutdown procedure that will take a few seconds. The unit 

water pump will be running on for two minutes after the unit has been switched off. Do not remove the main 

power to not turn off the electrical resistances of the compressor and the evaporator. 

 
 

14

 

MAINTENANCE 

 

Maintenance operations are fundamental in order to keep the units running properly, from a purely functional and an 
energetic and environmental points of view

Every unit comes with a logbook, in which the user to machine maintenance can keep all the required notes, in order to 

keep a historical log of the unit. 

A lack of notes in the logbook could be considered proof of careless maintenance. 

 

14.1

 

GENERAL 

 

IMPORTANT! 

Beyond the cadences of checks recommended in the following, in order to keep the unit at optimum levels of 

performance and efficiency and prevent incipient failures, we recommend periodic visits of inspection and control of 

the unit by qualified personnel. 

In particular, we recommend: 

4 annual visits to units that operate about 365 days / year (quarterly) 

2 visits per year for units with seasonal operation about 180 days / year (one at the start of the season and another one 

at mid-season) 

1 annual visit for units with seasonal operation of about 90 days / year (starting seasonal) 

It’s important that during the initial start-up and periodically during operation routine checks are carried out. Among 

them we must also check the suction and condensation as well as the sight glass located on the liquid line. 

Check through the microprocessor installed on the unit if the unit is working within normal parameters of superheating 

Summary of Contents for Flex II

Page 1: ...CG SVX048A GB Original instructions Installation Operation Maintenance Flex II Air to water heat pumps with fixed speed scroll compressors...

Page 2: ...6 ELECTRICAL POWER SUPPLY 12 7 WATER CONNECTIONS 13 8 ELECTRICAL PANEL 24 9 OPERATOR RESPONSABILITIES 27 10 START UP PRELIMINARY PROCEDURES 27 12 CHECK LIST MANDATORY OPERATION CONTROL BEFORE START UP...

Page 3: ...made to the carrier for damage or for not delivery and the Receiving Card to be found inside the unit electrical panel must be filled in Photographic evidence must be provided for macroscopic damage T...

Page 4: ...means of the external knife switch check that the unit has been earthen correctly before starting it up control all the electrical connections and the connection cables paying particular attention to...

Page 5: ...only after having placed a sign which says do not use maintenance in progress if modifications must be carried out to the cooling hydraulic or electrical circuit of the unit or to its command logic c...

Page 6: ...ING LIMITS Unit operation is permitted within the limits indicated in the diagram provided in 3 3 CAUTION The operation outside the limits specified may cause the activation of the protections and dis...

Page 7: ...OAT Outdoor Air Temperature C LWT Leaving Water Temperature C Low ambient kit down to 15 C Heater in control box HEAT PUMP MODE kit 15 C...

Page 8: ...06 1 09 1 118 1 149 1 182 1 211 1 243 In order to calculate performance with glycoled solutions multiply main sizes by respective coefficients GLYCOL PERCENTAGE DEPENDING ON FREEZINGTEMPERATURE glycol...

Page 9: ...supporting structures fit shock absorbers in every fastening point Rubber shock absorbers are recommended for units installed on the ground spring shock absorbers for units installed on roofs Open sp...

Page 10: ...osition fix the antivibration bolts 4 3 PRECAUTIONS FOR DOMINANT WINDS Avoid obstacles on suction and discharge sides of the units Respect the safety distances as shown on the units dimensional drawin...

Page 11: ...ocal code 6 1 POWER CONNECTIONS Protect the unit electric box power supply circuit with protection devices not included in the supplied equipment Connect the line terminals with a three core cable of...

Page 12: ...g units with temperature around 0 C please evacuate the exchanger with compressed air in order to avoid breakings due to ice If the unit is installed in order to replace another the entire hydraulic s...

Page 13: ...eat exchanger Q max maximum water flow to the heat exchanger Tmax chiller 8 C Tmax heat pump 8 C dpw K Q 1000 Q 0 86 P T IMPORTANT If pumps driven by inverters either unit onboard pump or external pum...

Page 14: ...from weather conditions The problem of water pipes freezing could appear in two different situations 1 Stand by with mode on but electrically connected in this case the unit has frost resistances whic...

Page 15: ...the customer pump if present must always be electrically supplied alike and functioning properly 2 Addition of an appropriate amount of glycol inside the water circuit 3 Additional heat insulation an...

Page 16: ...tank Modular version with single pump Modular version with double pump and stand by pump Units can be installed in modular configuration up to a maximum of 6 units by means of a dedicated hydraulic c...

Page 17: ...6 bar Shut Off Valve Pump Water Charge Water DIscharge Check Valve Water Tank Antivibration System Flow Switch FIlter 2 Way Valve With ON OFF Servo Control Water Differential Pressure Switch Temperatu...

Page 18: ...6 bar Shut Off Valve Pump Water Charge Water DIscharge Check Valve Water Tank Antivibration System Flow Switch FIlter 2 Way Valve With ON OFF Servo Control Water Differential Pressure Switch Temperatu...

Page 19: ...Valve Pump Water Charge Water DIscharge Check Valve Water Tank Antivibration System Flow Switch FIlter 2 Way Valve With ON OFF Servo Control Flow Switch FIlter 2 Way Valve With ON OFF Servo Control 6...

Page 20: ...he flow switch and the water strainer in the customer plant are obligatory in order to keep the warranty Primary Pump Secondary Pump Temperature Probe Flow Switch Drainage Vent Valve Expansion Vessel...

Page 21: ...NT the flow switch and the water strainer in the customer plant are obligatory in order to keep the warranty Primary Pump Secondary Pump Temperature Probe Flow Switch Drainage Vent Valve Expansion Ves...

Page 22: ...y Pump Temperature Probe Flow Switch AIR CONDITIONING WATER PUMP WATER TANK FANCOIL AIR CONDITIONING WATER PUMP WATER TANK FANCOIL Drainage Vent Valve Expansion Vessel Filling Group Steel Mesh Straine...

Page 23: ...calibrate the device to compensate for the weight of the headstock If the unit is mounted to the bottom WARNINGS on deposits that can form must be made The appliance must be installed in a straight p...

Page 24: ...PARTIAL RECOVERY PB LP PRESSURE SWITCH Rliq LIQUID RECEIVER RC CARTER HEATER VA SAFETY VALVE AA LIQUID SEPARATOR FE FILTER DRIER PS SERVICE VALVE KA HP TRANSDUCER V FAN KB LP TRANSDUCER VS SIGHT GLASS...

Page 25: ...uit 230 24V It requires no additional power cable for the control equipment The unit has an antifreeze heater installed directly into the evaporator The circuit also has an electric resistance install...

Page 26: ...p of the evaporator with the calibration valve shut and then slowly open it Discharge the air from the high points of the water circuit and check the direction of the water flow Carry out a setting of...

Page 27: ...ALLED BETWEEN THE UNIT AND THE FLOOR 7 THE UNIT DISPLAYS DEFECTS OR DAMAGES RESULTING FROM MODIFICATIONS OR CHANGES UNIT TAMPERING UNAUTHORIZED MODIFICATIONS TO THE REFRIGERANT CIRCUIT OR THE HYDRAULI...

Page 28: ...ANY ADDITIONAL CONTROLLER HAS BEEN INSTALLED 18 THE CONNECTION WIRES ARE SHIELDED 19 REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN CONFORMITY WITH TRANE WIRING DIAGRAMS...

Page 29: ...RT UP 33 HYDRAULIC CONNECTIONS TO THE UNIT ARE COMPLIANT WITH THE UNIT NAME PLATE AND DIMENSIONAL DRAWINGS HOT WATER INLET HOT WATER OUTLET COLD WATER INLET COLD WATER OUTLET ETC 34 RUBBER JOINTS ARE...

Page 30: ...CUMENTATION 44 ALL WATER PIPES ARE GROUND CONNECTED IN ORDER TO AVOID ABNORMAL VOLTAGES THAT CAN CAUSE DANGEROUS CORROSIONS 45 THE EVAPORATOR WATER FLOW IS COMPLIANT TO THE TECHNICAL DOCUMENTATION PRO...

Page 31: ...may mean an excess of charge After intervention on the charge it is appropriate to check that the unit runs within the declared values with unit steadily running on a full charge measure the temperatu...

Page 32: ...e at the end IMPORTANT If the unit has not been provided with integrated pump on board do not turn off the external pump before 3 minutes have elapsed after turning off the last compressor The early s...

Page 33: ...es at full load and check the oil level The units use POE oil In case of burns for the electrical motor or fault of the compressor it is necessary to make a test to check the acidity of the lubricant...

Page 34: ...circuit controlling a Overheating compressor b Overheating compressor discharge c Sub cooling of the liquid exiting the condenser coil d Evaporation pressure c Condensing pressure 15 Measure the valu...

Page 35: ...he oil in the remaining compressor and also replace the liquid line filter drier After an electrical failure of a compressor it will also be necessary to change the oil in the remaining compressor rep...

Page 36: ...or use and maintenance manual for a complete description of applications setting and adjustments All sensors are preassembled and connected to the microprocessor The descriptions of each sensor are li...

Page 37: ...te 5 X Carry out the analysis of the vibrations of the compressor X Carry out the analysis of the acidity of the oil of the compressor 7 X Check pressure safety accessories PED Condensing section Clea...

Page 38: ...ype fans and engines 1 per type 2 YEAR COMPONENTS QUANTITY fuses all filter dryers all solenoid valves all electronic expansion valves all pressure switches all gas gauges all contactors and relays al...

Page 39: ...he circuit Make sure that working conditions are within the limits of operation Loss of coolant see section G C The compressor starts up and stops repeatedly x s Intervention of the minimum See point...

Page 40: ...ck the voltage across the coil of the contactor and the continuity of the coil x s Lack of output voltage from the control fan speed Check the contacts replace if necessary x s Thermal protection insi...

Page 41: ...Water circulation pump blocked Unlock the pump x s Water circulation pump defective Check the pump and replace if necessary x s Low refrigerant charge See point G x s The liquid filter is clogged Repl...

Page 42: ...rane optimizes the performance of homes and buildings around the world A business of Ingersoll Rand the leader in creating and sustaining safe comfortable and energy efficient environments Trane offer...

Reviews: