Installation - FIAECON102*

8

 ACC-SVN264B-EN

Important:

Verify holes in copper tube are facing down. 
Unit will not sense smoke if holes are not facing 
down.

Figure 8.

Smoke detector

Smoke Detector

Economizer Wiring

Once economizer has been installed, plug actuator harness 
into J11 on fresh air module. Refer to 

Figure 9

 for fresh air 

module access.

Figure 9.

Return enclosure access

Fresh Air Module 
Access Door

Minimum Position Setting for One 
Speed Indoor Fan

1. Apply power to the unit.
2. Place the zone sensor fan selector in the fan 

ON

 position 

and the heat/cool selector in the 

OFF

 position to place the 

damper in the minimum ventilation position.

3. The Min Position (on the rooftop economizer) can be 

adjusted using the Symbio™ 700 or Mobile App. In the 
Settings -> Fresh/Return Air Menu the Minimum Position 
can be adjusted between 0-50%.

4. Wait at least 30 seconds for the damper to settle at the new 

position.

5. Replace the filter access panel. The damper will close 

when the blower circuit is no longer energized.

Minimum Position Setting

1. Apply power to the unit.
2. Using Service Test mode, through the Symbio™ 700 or 

mobile app, set the unit to Service Test step 

Ventilation 

Low Fan Speed

.

3. Navigate to the Settings –> Fresh/Return Air menu. Set the 

Design Minimum OA Damper Position at Min Fan Capacity 
to the desired value.

4. Wait at least 30 seconds for the damper to settle at the new 

position. Range of damper for this setting is 0-100%.

5. Using Service Test mode, through the Symbio™ 700 or 

mobile app, set the unit to Service Test step 

Ventilation 

Low Fan Speed

.

6. Navigate to the Settings –> Fresh/Return Air menu. Set the 

Design Minimum OA Damper Position at Mid Fan Capacity 
to the desired value.

7. Wait at least 30 seconds for the damper to settle at the new 

position. Range of damper for this setting is 0-100%.

8. Using Service Test mode, through the Symbio™ 700 or 

mobile app, set the unit to Service Test step 

Ventilation 

Low Fan Speed

9. Navigate to the Settings –> Fresh/Return Air menu. Set the 

Design Minimum OA Damper Position at Full Fan Capacity 
to the desired value.

10. Wait at least 30 seconds for the damper to settle at the new 

position. Range of damper for this setting is 0-100%.

11. Replace the filter access panel. The damper will close 

when the blower circuit is de-energized.

Dry Bulb Settings

Standard economizer dry bulb changeover is field selectable 
and has a range of 50-140

º

F.

Control Option

Optional Sensors Required

Dry Bulb (standard)

OAT

Discharge Air Temperature Sensor

Summary of Contents for FIAECON102 Series

Page 1: ...WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires...

Page 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Page 3: ...lways follow local regulations Introduction ACC SVN264B EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without w...

Page 4: ...7 Economizer Wiring 8 Minimum Position Setting for One Speed Indoor Fan 8 Minimum Position Setting 8 Dry Bulb Settings 8 General Information FIAECON103 9 Inspection 9 Parts List 9 Installation FIAECO...

Page 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Page 6: ...filler panel 3 Between top of filler panel and unit only if filler panel is required 4 Top of hood triangle seal between hood and hood flange 5 Around barometric relief hood seal between barometric re...

Page 7: ...emove the slack in wire harness 7 Attach powered exhaust with self drilling screws See Figure 6 8 Verify wire harness is clear of gears doors and any sharp edges of metal 9 Hook up electrical as descr...

Page 8: ...to Service Test step Ventilation Low Fan Speed 3 Navigate to the Settings Fresh ReturnAir menu Set the Design Minimum OADamper Position at Min Fan Capacity to the desired value 4 Wait at least 30 seco...

Page 9: ...unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur afte...

Page 10: ...ter 1 9 Hardware bag 52 Type AB sheet metal screws with sealing washer 10 16 x 5 8 in Identification label Installation instructions 1 Field only parts Carton B a a These parts are already installed i...

Page 11: ...rear fresh air access panels from the unit and set them aside Figure 11 Panel removal Unit Access Panel Front Do Not Remove If Hinged Unit Access Panel Rear Unit End Panel 2 For a factory installed lo...

Page 12: ...he left side of the outdoor air damper assembly as shown in Figure 17 Figure 17 Outside air block off panel installation Outside Air Block off Outdoor Air Damper Assembly 8 Secure outdoor air damper a...

Page 13: ...brackets should be installed on the flat side of the hood panel with the flanges facing away from the panel 13 Attach the triangle hood panels on the left and right side of the damper assembly Use fiv...

Page 14: ...anels on the front and back of the unit Figure 24 Back panel and barometric relief parts Horizontal Return Block off Panel Barometric Relief Assembly Note The back panel will be replaced with the baro...

Page 15: ...e carrier and the consignee Note Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative Parts List NOTICE Corrosion Damage Failure to use recommended...

Page 16: ...ontaining ship with parts from the outdoor air damper assembly Refer to Figure 27 for the following assembly process 3 Installthehorizontalductconversionkitpertheinstructions included with that kit 4...

Page 17: ...facing away from the panel 10 Attach the triangle hood panels on the left and right side of the damper assembly Use five screws for each hood panel The hood panels have pre installed gasket between t...

Page 18: ...nd panel reinstallation Unit End Panel Diverter Panel Identification Label 16 Install the access panel on the front of the unit 17 Using field supplied silicone sealant seal all seams cracks and gaps...

Page 19: ...s and route the controls harness from the sensor to the fresh air options module located in the return enclosure using the factory installed wire ties Connect the harness J9 connector to the fresh air...

Page 20: ...ations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residen...

Reviews: