background image

©2022

 ACC-SVN264B-EN

Introduction

Read this manual thoroughly before operating or servicing this 
unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. 
Your personal safety and the proper operation of this machine 
depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

Indicates a potentially hazardous 

situation which, if not avoided, could 

result in death or serious injury.

CAUTION

s

Indicates a potentially hazardous 

situation which, if not avoided, could 

result in minor or moderate injury. It could 

also be used to alert against unsafe 

practices.

NOTICE

Indicates a situation that could result in 

equipment or property-damage only 

accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made 
chemicals can affect the earth’s naturally occurring 
stratospheric ozone layer when released to the atmosphere. In 
particular, several of the identified chemicals that may affect 
the ozone layer are refrigerants that contain Chlorine, Fluorine 
and Carbon (CFCs) and those containing Hydrogen, Chlorine, 
Fluorine and Carbon (HCFCs). Not all refrigerants containing 
these compounds have the same potential impact to the 
environment. Trane advocates the responsible handling of all 
refrigerants-including industry replacements for CFCs and 
HCFCs such as saturated or unsaturated HFCs and HCFCs.

Important Responsible Refrigerant 

Practices

Trane believes that responsible refrigerant practices are 
important to the environment, our customers, and the air 
conditioning industry. All technicians who handle refrigerants 
must be certified according to local rules. For the USA, the 
Federal Clean Air Act (Section 608) sets forth the requirements 
for handling, reclaiming, recovering and recycling of certain 
refrigerants and the equipment that is used in these service 
procedures. In addition, some states or municipalities may 
have additional requirements that must also be adhered to for 
responsible management of refrigerants. Know the applicable 
laws and follow them.

WARNING

Proper Field Wiring and Grounding 

Required!

Failure to follow code could result in death or serious 

injury. All field wiring MUST be performed by qualified 

personnel. Improperly installed and grounded field 

wiring poses FIRE and ELECTROCUTION hazards. To 

avoid these hazards, you MUST follow requirements for 

field wiring installation and grounding as described in 

NEC and your local/state/national electrical codes. 

WARNING

Personal Protective Equipment (PPE) 

Required!

Failure to wear proper PPE for the job being undertaken 

could result in death or serious injury. Technicians, in 

order to protect themselves from potential electrical, 

mechanical, and chemical hazards, MUST follow 

precautions in this manual and on the tags, stickers, 

and labels, as well as the instructions below:

Before installing/servicing this unit, technicians 
MUST put on all PPE required for the work being 
undertaken (Examples; cut resistant gloves/sleeves, 
butyl gloves, safety glasses, hard hat/bump cap, fall 
protection, electrical PPE and arc flash clothing). 
ALWAYS refer to appropriate Safety Data Sheets 
(SDS) and OSHA guidelines for proper PPE.

When working with or around hazardous chemicals, 
ALWAYS refer to the appropriate SDS and OSHA/GHS 
(Global Harmonized System of Classification and 
Labeling of Chemicals) guidelines for information on 
allowable personal exposure levels, proper 
respiratory protection and handling instructions.

If there is a risk of energized electrical contact, arc, or 
flash, technicians MUST put on all PPE in accordance 
with OSHA, NFPA 70E, or other country-specific 
requirements for arc flash protection, PRIOR to 
servicing the unit. NEVER PERFORM ANY 
SWITCHING, DISCONNECTING, OR VOLTAGE 
TESTING WITHOUT PROPER ELECTRICAL PPE AND 
ARC FLASH CLOTHING. ENSURE ELECTRICAL 
METERS AND EQUIPMENT ARE PROPERLY RATED 
FOR INTENDED VOLTAGE.

Summary of Contents for FIAECON102 Series

Page 1: ...WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires...

Page 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Page 3: ...lways follow local regulations Introduction ACC SVN264B EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without w...

Page 4: ...7 Economizer Wiring 8 Minimum Position Setting for One Speed Indoor Fan 8 Minimum Position Setting 8 Dry Bulb Settings 8 General Information FIAECON103 9 Inspection 9 Parts List 9 Installation FIAECO...

Page 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Page 6: ...filler panel 3 Between top of filler panel and unit only if filler panel is required 4 Top of hood triangle seal between hood and hood flange 5 Around barometric relief hood seal between barometric re...

Page 7: ...emove the slack in wire harness 7 Attach powered exhaust with self drilling screws See Figure 6 8 Verify wire harness is clear of gears doors and any sharp edges of metal 9 Hook up electrical as descr...

Page 8: ...to Service Test step Ventilation Low Fan Speed 3 Navigate to the Settings Fresh ReturnAir menu Set the Design Minimum OADamper Position at Min Fan Capacity to the desired value 4 Wait at least 30 seco...

Page 9: ...unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur afte...

Page 10: ...ter 1 9 Hardware bag 52 Type AB sheet metal screws with sealing washer 10 16 x 5 8 in Identification label Installation instructions 1 Field only parts Carton B a a These parts are already installed i...

Page 11: ...rear fresh air access panels from the unit and set them aside Figure 11 Panel removal Unit Access Panel Front Do Not Remove If Hinged Unit Access Panel Rear Unit End Panel 2 For a factory installed lo...

Page 12: ...he left side of the outdoor air damper assembly as shown in Figure 17 Figure 17 Outside air block off panel installation Outside Air Block off Outdoor Air Damper Assembly 8 Secure outdoor air damper a...

Page 13: ...brackets should be installed on the flat side of the hood panel with the flanges facing away from the panel 13 Attach the triangle hood panels on the left and right side of the damper assembly Use fiv...

Page 14: ...anels on the front and back of the unit Figure 24 Back panel and barometric relief parts Horizontal Return Block off Panel Barometric Relief Assembly Note The back panel will be replaced with the baro...

Page 15: ...e carrier and the consignee Note Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative Parts List NOTICE Corrosion Damage Failure to use recommended...

Page 16: ...ontaining ship with parts from the outdoor air damper assembly Refer to Figure 27 for the following assembly process 3 Installthehorizontalductconversionkitpertheinstructions included with that kit 4...

Page 17: ...facing away from the panel 10 Attach the triangle hood panels on the left and right side of the damper assembly Use five screws for each hood panel The hood panels have pre installed gasket between t...

Page 18: ...nd panel reinstallation Unit End Panel Diverter Panel Identification Label 16 Install the access panel on the front of the unit 17 Using field supplied silicone sealant seal all seams cracks and gaps...

Page 19: ...s and route the controls harness from the sensor to the fresh air options module located in the return enclosure using the factory installed wire ties Connect the harness J9 connector to the fresh air...

Page 20: ...ations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residen...

Reviews: