background image

© 2009  Trane            All Rights Reserved

18-CD29D1-3

Installer’s Guide

SAFETY SECTION

The following safety practices and precautions must be
followed during the installation, servicing, and operation
of this furnace.

1. Use only with the type of gas approved for this fur-

nace.  Refer to the furnace rating plate.

2. Install this furnace only in a location and position as

specified in “Location and Clearances” (page 4), of
these instructions.

3. Provide adequate combustion and ventilation air to

the furnace space as specified in “Air for Combus-
tion and Ventilation” (pages 8-9), of these instruc-
tions.

4. Combustion products must be discharged outdoors.

Connect this furnace to an approved vent system
only, as specified in the “Venting” section (starting
on page 15), of these instructions.

5. Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions, as specified in “Gas Piping” (pages 31-32), of
these instructions.

6. Always install the furnace to operate within the

furnace’s intended temperature-rise range with a
duct system which has an external static pressure
within the allowable range, as specified on the unit
rating plate.  Airflow with temperature rise for cfm
versus static is shown in the Service Facts accompa-
nying this furnace.

7. When a furnace is installed so that supply ducts

carry air circulated by the furnace to areas outside
the space containing the furnace, the return air
shall also be handled by a duct(s) sealed to the fur-
nace casing and terminating outside the space con-
taining the furnace.

8. A gas-fired furnace for installation in a residential

garage must be installed as specified in “Location
and Clearances” section (page 4), of these instruc-
tions.

WARNING

!

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each ap-
pliance connected to the venting system being placed
into operation could result in carbon monoxide poi-
soning or death.
The following steps shall be followed for each appli-
ance connected to the venting system being placed
into operation, while all other appliances connected to
the venting system are not in operation:

1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and

horizontal pitch, as required in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 or the CAN/CGA
B149 Installation Codes and these instructions.
Determine that there is no blockage or restriction,
leakage, corrosion and other deficiencies which
could cause an unsafe condition.

3. As far as practical, close all building doors and

windows and all doors between the space in which
the appliance(s) connected to the venting system
are located and other deficiencies which could
cause an unsafe condition.

4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not con-

nected to the venting system.  Turn on any exhaust
fans, such as range hoods and bathroom exhausts,
so they are operating at maximum speed.  Do not
operate a summer exhaust fan.

6. Follow the lighting instructions.  Place the appli-

ance being inspected into operation.  Adjust the
thermostat so appliance is operating continuously.

7. If improper venting is observed during any of the

above tests, the venting system must be corrected
in accordance with the National Fuel Gas Code,
ANSI Z221.1/NFPA 54 and/or CAN/CGA B149.1 In-
stallation Codes.

8. After it has been determined that each appliance

connected to the venting system properly vents
where tested as outlined above, return doors, win-
dows, exhaust fans, fireplace dampers and any
other gas-fired burning appliance to their previous
conditions of use.

9. The furnace may be used for temporary heating of

buildings or structures under construction only
when the  following  conditions have been  met:
a.

The furnace venting system must be complete
and installed per manufacturers instructions.

b.

The furnace is controlled only by a room ther-
mostat (no field jumpers).

c.

The furnace return air duct must be complete
and sealed to the furnace and  clean air filters
are in place.

d.

The furnace input rate and temperature rise
must be verified to be within nameplate mark-
ing.

e.

100% of the furnace combustion air require-
ment must come from outside the structure.

Safety signal words are used to designate a degree or
level of seriousness associated with a particular hazard.
The signal words for safety markings are 

WARNING

 and

CAUTION

.

a.

WARNING

 indicates a potentially hazardous situa-

tion which, if not avoided, could result in death or
serious injury.

b.

CAUTION

 indicates a potentially hazardous situation

which, if not avoided, may result in minor or moder-
ate injury.  It is also used to alert against unsafe
practices and hazards involving only property dam-
age.

Summary of Contents for *DH1B040A9241A

Page 1: ...erty and is to remain with this unit Please return to service information pack upon completion of work Installer s Guide __First letter may be A or T 1 8 CD2 9 D1 3 UPFLOW UH1 UPFLOW HORIZONTAL A34162...

Page 2: ...horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the CAN CGA B149 Installation Codes and these instructions Determine that there is no blockage or restriction leakage...

Page 3: ...quipment to approximate location If damage to contents is found report the damage immediately to the de livering agency Codes and local utility requirements governing the installation of gas fired equ...

Page 4: ...46 cm above the floor and the furnace must be located or protected to avoid physical damage from ve hicles IMPORTANT The furnace must be installed level The only allowable variation would be slightly...

Page 5: ...NTAL ALL DIMENSIONS ARE IN INCHES 1 UH1D120A9601 REQUIRES 3 DIAMETER VENT PIPE UH1C100A9481 UH1D100A9601 REQUIRES 2 1 2 OR 3 DIAMETER VENT PIPE 2 DIAMETER OF VENT PIPE MAY BE LIMITED TO 2 1 2 OR 3 ON...

Page 6: ...From Dwg C341885 Rev 7 DH1 OUTLINE DRAWING DOWNFLOW HORIZONTAL ALL DIMENSIONS ARE IN INCHES 12345 3617898 3618 8 36178 8 3617838 1234567689 74 123456 897 4 4 4 4 7 4 4 7 4 1234 6 897 4 4 4 49 7 49 4...

Page 7: ...e or other combustible material other than wood flooring For vertical downflow application subbase BAYBASE 205 must be used between the furnace and combus tible flooring When the downflow furnace is i...

Page 8: ...or craft rooms Furnaces installed near chemical storage areas Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus tion Permanent wave solutions...

Page 9: ...commencing within 12 inches of the top and one commencing within 12 inches of the bot tom of the enclosure The openings shall communi cate directly or by ducts with the outdoors or spaces crawl or at...

Page 10: ...the bottom All return air duct systems should provide for installa tion of return air filters 1 Determine the appropriate position to set the furnace in order to connect to the existing supply and ret...

Page 11: ...the cloths before you start the furnace RETURN AIR FILTERS Filter and filter rack are not supplied with unit TYPICAL UPFLOW RETURN AIR FILTER INSTALLA TIONS These furnaces require high velocity type...

Page 12: ...ace cabinet side See Figures 13 14 15 NOTE Remove the bottom front channel to install the filter rack in the 14 1 2 width cabinet furnaces Filter Rack Furnace Cabinet Side Filter Rack Retaining Screw...

Page 13: ...ide of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 13 14 16...

Page 14: ...ter clip with the leaf spring mounts in the rear of the cabinet See Figure 21 a UNIT SIZE RETURN AIR BOTTOM SIDE 14 1 2 CUT ON LINE DO NOT CUT 17 1 2 DO NOT CUT DO NOT CUT 21 DO NOT CUT CUT ON LINE 24...

Page 15: ...d lateral of the existing venting system as well as quantity and type of bends c Use the appropriate tables in the latest edition of the National Fuel Gas Code ANSI Z223 1 CAN CGA B149 1 Installation...

Page 16: ...LE TEMPERATURE MARKING D2846 CPVC 41 212 ASTM D2846 F441 SCH 40 80 212 ASTM F441 F442 SDR SERIES 212 ASTM F442 ABS ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING D2661 SCH 40 DWV 180 ASTM D2661...

Page 17: ...MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET Except adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the ma...

Page 18: ...pt adapters at the top of the furnace If different inlet and vent pipe sizes are used the vent pipe must adhere to the maximum length limit shown in the table above See Note 7 below for exception The...

Page 19: ...y is fully open on a minimum of two sides beneath the floor Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer s Installation Instructi...

Page 20: ...he condition of a heated space HORIZONTAL VENTING THROUGH WALL These furnaces may be installed as direct vent as shipped or as nondirect vent Installation must conform to national state and local code...

Page 21: ...large enough to maintain pitch of vent and properly seal Use cement mortar seal on inside and outside of wall See Figure 31 VENTING THROUGH THE ROOF When penetrating roof with a 2 PVC vent pipe a 2 el...

Page 22: ...SUPPLIED COMBUSTION AIR VENT ELBOW FIELD SUPPLIED VENT 1 1 2 BAYAIR30AVENTA 3 PIPING 2 2 1 2 or 3 PIPING REDUCING COUPLING FIELD SUPPLIED IF NEEDED SEAL ALL WALL CAVITIES BAYVENT200B c CAUTION The ve...

Page 23: ...TICIPATED SNOW LEVEL MAXIMUM OF 24 IN ABOVE ROOF SUPPORT FIELD SUPPLIED VENT m 6 Min 40 Inch Upflow or Downflow Furnace Slope 1 4 per ft Slope 1 4 per ft All horizontal pipes must be supported at a ma...

Page 24: ...wall flue pipe and masonry chimney is to be used for another gas appliance venting area must be sufficient to vent that appliance and that appliance must be con nected to chimney with separate entry...

Page 25: ...detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installat...

Page 26: ...low models all 120 000 BTU upflow models UH1C080A9601A and all downflow models LABEL SAYS TOP STRAIGHT SIDE MUST BE ON BOTTOM FOR PROPER CONDENSATE DRAINAGE WHEN THE FACTORY SUPPLIED OFF SET 2X3 REDUC...

Page 27: ...ced blower and reposi tion into the other drain tap of the inducer which is lo cated 90 clockwise around the inducer Move the cap from that drain tap to the unused drain tap On upflow units plug the h...

Page 28: ...NG A 1 STAGE HEATING THERMOSTAT NO COOLING Primary drain vent stack must terminate below secondary heat exchanger condensate drain outlet To drain opening If upflow furnace is installed over a finishe...

Page 29: ...xternal electrical source is utilized OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 From drawing B340388 Rv 2 SEE NOTE 8 FURNACE B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 EAC SE...

Page 30: ...E 4 ISOLATION RELAY SEE NOTE 4 B C B C B C From Dwg 21B341422 Rev 3 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEAT 1 STAGE COO...

Page 31: ...P LEG AUTOMATIC GAS VALVE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG GAS PIPING The upflow horizontal furnace is shipped standard for left side installation of gas pipin...

Page 32: ...necessary For 1 Cu Ft Dial Gas Flow CFH Chart Flow Reading 2 For 1 2 Cu Ft Dial Gas Flow CFH Chart Flow Reading 4 For 5 Cu Ft Dial Gas Flow CFH 10X Chart Flow Reading 4 6 Multiply the final figure by...

Page 33: ...481A 3 5 W C 11 0 W C DH1D110A9601A 4 5 W C 11 0 W C 5 Adjust gas heat by removing the adjustment regulator cover screw a To increase outlet pressure turn the regulator adjust screw clockwise b To dec...

Page 34: ...Code ANSI Z223 1 NFPA 54 or National Standard of Canada Natural Gas and Propane Installation Code CSA 149 1 Installation of this furnace at altitudes above 2 000 ft 610m shall be made in accordance w...

Page 35: ...e sensor hot surface igniter or main burner orifices have required removal of the cover TABLE 20 Orifice Twist Drill Size If Installed At Sea Level ALTITUDE ABOVE SEA LEVEL and Orifice Required At Oth...

Page 36: ...ition See Figure 57 58 Disconnect the electrical supply to the unit CAUTION If this is done during the cold weather months provi sions must be taken to prevent freeze up of all water pipes and water r...

Page 37: ...ndensate drain is blocked either by debris improper draining or by freezing condensate the pressure switch will receive a signal warning of the accumulation of condensate in the heat exchanger assembl...

Page 38: ...38 18 CD29D1 3 Installer s Guide...

Page 39: ...s or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure seitch problem c Inducer problem 4 Flashes Open High Limit Device 5 Flashes Flame sensed when no fl...

Page 40: ...mprovement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Literature Order...

Reviews: