10
RF-SVX003A-GB
Minimum space requirements
In any case, the microprocessor will allow the unit to adapt to the new condition producing the maximum available
capacity (which would, however, lower than the nominal capacity of the unit) even with a lateral distance less than
the recommended. When two or more units are positioned side by side, it is recommended that a minimum distance
of 3600 mm of distance between the condenser coils.
Condensate
The unit in order to easily discharge the condensate caused by the heat pump operation, especially during the
defrosting cycle. Avoid the condensate drain in location where people pass.
◄
►
◄
►
◄
►
◄
►
3000
500
18
0
0
18
0
0
1500
1500
3600
1500