CVHH-SVX001G-EN
123
Appendix D: CVHH CenTraVac
™
™
Chiller Annual
Inspection List
Follow the annual maintenance instructions provided
in the text of this manual, including but not limited to:
1. C
Co
om
mp
prre
esssso
orr//M
Mo
otto
orr
Motor continuity.
Motor meg test.
Check motor terminals.
Inspect motor terminal board.
Check inlet guide vanes (IGV) for abnormalities.
2. S
Stta
arrtte
err o
orr A
Ad
da
ap
pttiiv
ve
e F
Frre
eq
qu
ue
en
nccy
y
™
™
D
Drriiv
ve
e
Inspect starter contacts.
Check all connections per manufacturer
specifications.
Follow all manufacturer recommendations for
starter or Adaptive Frequency
™
Drive (AFD)
maintenance.
Inspect/clean/service the AFD cooling system
(water- or air-cooled AFD).
Record all applicable starter or starter
component settings.
3. O
Oiill S
Sy
ysstte
em
m
Annual oil analysis (follow recommendations).
Clean and lubricate oil system as required.
Electrical inspection.
Pump motor continuity check.
Run oil pump and check differential oil pressure.
4. C
Co
on
nd
de
en
nsse
err
Inspect for fouling and scaling in tubes.
Check operation of condenser water flow
sensing device.
Factory recommendation to eddy current test
tubes every three years.
5. E
Ev
va
ap
po
orra
atto
orr
Inspect for fouling and scaling in tubes.
Check operation of evaporator water flow
sensing device.
Factory recommendation to eddy current test
tubes every three years.
6. C
Co
on
nttrro
oll C
Ciirrccu
uiittss
Verify control parameters.
Test appropriate sensors for accuracy.
Ensure sensors are properly seated in wells with
thermopaste installed.
Check evaporator leaving water temperature
low temperature cutout setpoint.
Condenser high pressure switch check-out.
Check adjustment and operation of the inlet
guide vane actuator.
7. L
Le
ea
akk T
Te
esstt C
Ch
hiilllle
err
Check purge times and unit performance logs. If
warranted, pressure leak test.
Review oil analysis. If required, submit
refrigerant sample for analysis.
Inspect unit for any signs of refrigerant or oil
leakage.
Check unit for any loose screws on flange,
volutes, or casing.
8. P
Pu
urrg
ge
e U
Un
niitt
Review the purge the purge sections of this
manual and follow maintenance and/or
inspection items identified.
Review purge pump-out data.
Review overall operation of purge and service
as necessary.
9. E
Ex
xtte
erriio
orr
Inlet guide vane linkage.
Clean and touch-up painted surfaces as needed.
Repair deteriorated, torn, or missing insulation.
10. O
Op
pttiio
on
na
all A
Acccce
esssso
orriie
ess
If applicable, lubricate factory-installed gantries.
After the first month of operation, inspect
Heresite
®
or Belzona
®
coated waterboxes;
thereafter, inspect as needed.
Inspect anodes.
Inspect and lubricate hinged waterboxes.
With water flow sensing option, bleed tubing
from waterboxes to transformers.
Summary of Contents for CVHH CenTraVac
Page 126: ...126 CVHH SVX001G EN N No ot te es s ...