30
T-Series Climate Changer Air Handler IOM •
CLCH-SVX06A-EN
Installation-Mechanical
Control Wiring Assembly at Section Splits
1.
Sections must be together. See
Figure 13
.
2. Remove outer and inner access covers on both sections adjacent to shipping split.
3. Remove top foam blocks in raceway.
4. Route wire harness(es) under inner roof through raceway and make connection to
corresponding wire harness.
5. Replace foam blocks.
Note: For proper unit operation, the foam blocks must be installed in the raceway. Failure
to install the foam blocks can result in condensate management problems.
6. Remove backing from inner access cover tape and replace inner access cover for all
roof inner access plates.
7.
Remove backing from outer access cover tape and replace outer access cover for all
roof outer access plates.
Figure 13. Control wiring assembly at section splits (all unit sizes)
Outer access cover
Tape
Wire harness
Inner access
cover
Foam
block