4
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
AH-SVX03C-GB
General information
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by
the user, of Trane CLCF Air Handling Units. They do not contain full service procedures necessary for the continued
successful operation of this equipment. The services of a qualified technician should be employed through the
medium of a maintenance contract with a reputable service company.
Read this manual thoroughly before unit start-up.
Warnings and cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper
operation of this machine require that you follow them carefully. The constructor assumes no liability for installations
or servicing performed by unqualified personnel.
WARNING! :
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION! :
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
The following pictograms can be found on the unit. Take necessary precautions to avoid damage and injury.
Warning pictograms
13
11
14
12
1 = Risk that unit is powered up
2 = Risk hazard due to fan rotation
3 = Risk hazard of burns on compressors or refrigeration piping
4 = Unit contains refrigerant gas. See specific warnings.
5 = Risk of residual voltage when speed drive or softstarter options are present
6 = Unit under pressure
7 = Risk to cut, particularly on heat exchanger fins
8 = Read instructions before installation
9 = Disconnect all electric power before servicing
10 = Read technical instructions
11 = Ensure that unit is properly grounded
12 = Water inlet
13 = Water outlet
14 = Inflammable dust-clogged filters
Important recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during
equipment operation:
1. The units are suitable for ambient air temperature between -20°C and +50°C and for air flow temperature
between -20°C and +40°C. Different conditions need written confirmation from the manufacturer.
2. The usual measure against frost in coils and protection against temperatures have to be secured by the user.
3. Components - Some OEM products have specific manufacturer's service instruction documents. These are
delivered with the Air Handling Unit. In this case, the indications in the OEM manual are valid and the service
handbook in hand has only general or complementary character for the relating components.
4. Liquid and gas storage -Maximum working pressure for all coils is 15bar. In case of coil connections to higher
working pressures, any warranty relating to coil tightness and personnel safety is excluded.