Table 2 - CGCL Fan performance
Size
Airflow
Total Fan Static Pressure (Pa)
(m
3
/h)
300
400
500
CGCL 200
15300
Fan Motor Nominal Power Low Speed*
(kW)
0.75
1.1
1.1
Fan Motor Nominal Power High Speed
(KW)
4.0
5.5
5.5
Nominal Amps Low speed *
(A)
3.2
3.7
3.7
Nominal Amps High speed
(A)
8.9
11
11
Starting Amps *
(A)
14
12
12
CGCL 250
17800
Fan Motor Nominal Power Low Speed*
(kW)
0.75
1.1
1.5
Fan Motor Nominal Power High Speed
(KW)
4.0
5.5
7.5
Nominal Amps Low speed *
(A)
3.2
3.7
5.0
Nominal Amps High speed
(A)
8.9
11
15.3
Starting Amps *
(A)
14
12
17
CGCL 300
23800
Fan Motor Nominal Power Low Speed*
(kW)
1.5
1.5
2.8
Fan Motor Nominal Power High Speed
(KW)
7.5
7.5
11.0
Nominal Amps Low speed *
(A)
5.0
5.0
7.7
Nominal Amps High speed
(A)
15.3
15.3
21.5
Starting Amps *
(A)
17
17
33
CGCL 350
26800
Fan Motor Nominal Power Low Speed*
(kW)
1.5
2.8
2.8
Fan Motor Nominal Power High Speed
(KW)
7.5
11.0
11.0
Nominal Amps Low speed *
(A)
5.0
7.7
7.7
Nominal Amps High speed
(A)
15.3
21.5
21.5
Starting Amps *
(A)
17
33
33
CGCL 400
30600
Fan Motor Nominal Power Low Speed*
(kW)
2.8
2.8
3.8
Fan Motor Nominal Power High Speed
(KW)
11
11
15
Nominal Amps Low speed *
(A)
7.7
7.7
10.1
Nominal Amps High speed
(A)
21.5
21.5
28.6
Starting Amps *
(A)
33
33
43
CGCL 450
34500
Fan Motor Nominal Power Low Speed*
(kW)
3.8
3.8
4.8
Fan Motor Nominal Power High Speed
(KW)
15.0
15.0
18.5
Nominal Amps Low speed *
(A)
10.1
10.1
12.1
Nominal Amps High speed
(A)
28.6
28.6
34.6
Starting Amps *
(A)
43
43
45
CGCL 500
39100
Fan Motor Nominal Power Low Speed*
(kW)
2.8
3.8
3.8
Fan Motor Nominal Power High Speed
(KW)
11.0
15.0
15.0
Nominal Amps Low speed *
(A)
7.7
10.1
10.1
Nominal Amps High speed
(A)
21.5
28.6
28.6
Starting Amps *
(A)
33
43
43
CGCL 600
47600
Fan Motor Nominal Power Low Speed*
(kW)
4.8
4.8
5.3
Fan Motor Nominal Power High Speed
(KW)
18.5
18.5
22.0
Nominal Amps Low speed *
(A)
12.1
12.1
13.2
Nominal Amps High speed
(A)
34.9
34.9
40.9
Starting Amps *
(A)
45
45
48
*: Fan motor always starts in Low speed
Unit nominal amps = nominal fan amps (according to static pressure) + compressor nominal amps
Unit starting amps = nominal fan amps (according to static pressure) + compressor starting amps
Table 3 - Pressure drop through condenser coil and air filter
Unit
Airflow
Chiller internal pressure drop (Pa)
m
3
/h
Cds coil
AR300 filter
A150 Filter
M8 Filter
CGCL 200
15300
96
100
66
28
CGCL 250
17800
77
85
56
22
CGCL 300
23800
124
122
84
40
CGCL 350
26800
77
85
56
22
CGCL 400
30600
96
100
68
28
CGCL 450
34500
117
117
80
36
CGCL 500
39100
124
95
64
26
CGCL 600
47600
163
122
84
40
For minimum clearance, consult the certified submittals, which are available on request from your local Trane sales office.
Available static pressure = Total fan static pressure (from table 2) - Chiller internal pressure drop (from table 3)
IMPORTANT:
The setting of the external static pressure supplied by the CGCL chiller must correspond to the actual ductwork (inlet and outlet) pressure drop +/- 50Pa.
Failure to comply to this condition could lead to operational problems such as excessive sound levels, vibrations, or early wear of motor, fan or bearings. Adjustment of the
airflow through the unit must be performed at chiller commissioning or warranty will not apply.
CGCL-SVX01B-E4