CG-PRC026C-GB
27
General Data
Table 7 - CXAX High Effi ciency and Standard Noise (continued)
Eurovent Performances (1)
CXAX
039
HE-SN
CXAX
045
HE-SN
CXAX
035
HE-SN
CXAX
040
HE-SN
CXAX
046
HE-SN
CXAX
052
HE-SN
CXAX
060
HE-SN
Net Cooling Capacity
(kW)
108
118
94
114
127
146
162
Total Power input in cooling
(kW)
36
41
34
37
43
49
55
EER
3.00
2.88
2.81
3.06
2.96
2.95
2.93
ESEER
4.20
4.02
3.98
4.10
4.00
4.03
3.95
Eurovent Ef
fi
ciency class Cooling
B
C
C
B
B
B
B
Sound power level
(dBA)
87
88
87
89
88
88
89
Heating application data (2)
Net Heating Capacity
(kW)
110
120
101
114
127
139
162
Total Power input in heating
(kW)
35
39
32
37
42
46
52
COP
3.14
3.12
3.16
3.08
3.02
3.00
3.11
Eurovent Ef
fi
ciency class Heating
B
B
B
B
B
B
B
η
s
(%)
133
132
131
124
124
128
129
SCOP
3.39
3.37
3.35
3.16
3.16
3.28
3.30
Unit amps (4) (5)
Unit rated amps
(A)
86
98
78
93
104
114
131
Unit rated amps - HESP Option (100Pa)
(A)
86
98
78
93
104
114
131
Unit start up amps
(A)
218
224
200
215
236
247
256
Unit start up amps - HESP Option (100Pa)
(A)
218
224
200
215
236
247
256
Short Circuit Unit Capacity (9)
(kA)
15
15
15
15
15
15
15
Compressor
Compressor Number per Circuit
#
3
3
2
2
2
2
2
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Model Circuit1 / Circuit 2
13+13+13
15+15+15
7.5+10 / 7.5+10 10+10 / 10+10 10+13 /10+13 13+13 / 13+13 15+15 / 15+15
Motor RPM
(rpm)
2900
Evaporator
Quantity
#
1
1
1
1
1
1
1
Type
Stainless steel Copper Brazed plate Heat exchanger
Evaporator model
P120Tx110
P120Tx110
DP300x82
DP300x82
DP300x82
DP300x114
DP300x114
Evaporator Water Content volume
(l)
13.3
13.3
8.5
8.5
8.5
11.8
11.8
Nominal water connection size (Grooved coupling) - Without HYM (in) - (mm)
2” - 60.3
2” - 60.3
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
Nominal water connection size (Grooved coupling) - With HYM
(in) - (mm)
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
3” OD - 76.1
Hydraulic Module Components
Expansion Tank Volume
(l)
35
35
35
35
35
35
35
Max User water loop Volume for factory mounted expansion tank (1)
(l)
2000
2000
2000
2000
2000
2000
2000
Optionnal water Buffer tank volume
(l)
444
444
444
444
444
444
444
Max. Water-side Operating Pressure without pump package
(kPa)
1000
Max. Water-side Operating Pressure with pump package
(kPa)
400
Condenser
Type
Aluminum
fi
ns & copper tubes heat exchanger
Quantity of coil
#
2
2
2
2
2
2
2
Face area per circuit
(m²)
5.93
5.93
2.96
2.96
2.96
2.96
3.46
Condenser Fan
Quantity
#
3
3
2
4
4
4
4
Diameter
(mm)
800
Fan / motor Type
Propeller fan : Variable speed - EC motor / HESP MAX SPEED
Air
fl
ow per Fan
(m
3
/h)
13823
13828
14960
14964
12725
12725
13351
Power per Motor
(kW)
1.95 / 1.95
Rated Amps per Motor
(A)
3 / 3
Motor RPM
(rpm)
150 - 686 RPM
Partial Heat recovery (PHR) option
Heat-Exchanger Type
Stainless steel Copper Brazed plate Heat exchanger
Heat-Exchanger Model
B3-027-20-4.5L
B3-027-20-4.5L 2x B3-014-14-4.5M 2x B3-014-14-4.5M 2x B3-014-14-4.5M 2x B3-027-14-4.5L 2x B3-027-14-4.5L
Water connection size (Thread connection)
(in) - (mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
G 1”1/4
(31.75 mm)
Water content volume
(l)
0.5
0.5
2x0.14
2x0.14
2x0.14
2x0.35
2x0.35
Dimensions
Unit Length
(mm)
2327
2327
2327
2327
2327
2327
2327
Unit Width
(mm)
2250
2250
2250
2250
2250
2250
2250
Unit Height
(mm)
1524
1524
1524
1524
1524
1524
1724
Option Additional height
Water Buffer tank option
(mm)
+330
+330
+330
+330
+330
+330
+330
Weights
Shipping Weight (5)
(kg)
954
972
1000
1098
1098
1120
1190
Operating Weight (5)
(kg)
925
942
974
1072
1072
1093
1163
Option Additional shipping weight
Single pump - Standard head pressure
(kg)
47
47
45
47
47
47
47
Single pump - High head pressure
(kg)
49
49
49
49
49
49
49
Twin pump - Standard head pressure
(kg)
75
75
75
75
75
75
75
Twin pump - High head pressure
(kg)
86
86
84
84
84
84
84
Partial heat recovery option
(kg)
4.6
4.6
2x1.48
2x1.48
2x1.48
2x3.82
2x3.82
Water Buffer tank option
(kg)
425
425
425
425
425
425
425
System data
Nb of refrigerant circuit
#
1
1
2
2
2
2
2
Minimum cooling load % (6)
%
33
33
22
25
22
25
25
Standard unit
R410A refrigerant charge Circuit1 / Circuit 2
(kg)
26.0
26.0
13.0 / 13.0
13.5 / 13.5
13.0 / 13.0
13.5 / 13.5
14.5 / 14.5
Oil charge Circuit1 / Circuit 2
(l)
10.5
11.5
6.3 / 6.3
6.6 / 6.6
6.6 / 6.6
6.6 / 6.6
7.2 / 7.2
Unit with partial heat receovery option
R410a refrigerant charge Circuit1 / Circuit 2
(kg)
26.0
26.0
13.0 / 13.0
13.5 / 13.5
13.0 / 13.0
13.5 / 13.5
14.5 / 14.5
Oil charge Circuit1 / Circuit 2
(l)
10.5
11.5
6.3 / 6.3
6.6 / 6.6
6.6 / 6.6
6.6 / 6.6
7.2 / 7.2
POE Oil type
OIL058E / OIL057E
(1) At Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C according to EN14511:2013
(2) At Evaporator water temperature : 40°C / 45°C - Condenser air. DB/WB 7°C / 6°C according to EN14511:2013
(4) under 400V/3/50Hz
(5) Rated Condition without Pump Package
(6) Minimum ambient in heating operation is for unit at 40°C / 45°C
(7) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(8) Maximum ambient operation is for unit at 12°C / 7°C
(9) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
Electrical & system data are subject to change without notice. Please refer to unit nameplate data.