Evaporator Pump 1 Starts/Hours
Modified
Evaporator Pump 1 Starts/Hours
Modified
Evap Pmp Starts/Hrs Modified
Chiller
Warning
NonLatch
All
A counter for evaporator pump 1 starts
or hours has been modified by
TechView. This diagnostic is
immediately and automatically cleared
and thus can only be seen in the
historic diagnostic list.
NA
Evaporator Pump 2 Starts/Hours
Modified
Evaporator Pump 2 Starts/Hours
Modified
Evap Pmp Starts/Hrs Modified
Chiller
Warning
NonLatch
All
A counter for evaporator pump 2 starts
or hours has been modified by
TechView. This diagnostic is
immediately and automatically cleared
and thus can only be seen in the
historic diagnostic list.
NA
Evaporator Water Flow Lost
Evaporator Water Flow Lost
Evap Water Flow Lost
Chiller
Immediate
and Special
Action
NonLatch
All
After the pump request was activated,
water flow was established and then
lost. Special action is to keep the evap
pump request active in a diagnostic
override mode. See
“Chilled Water
Pump Control,” p. 81
for more details.
Remote
Evaporator Water Flow Lost Lockout
Evaporator Water Flow Lost Lockout
Evap Water Flow Lost Lockout
Chiller
Immediate
Latch
All
Four (4) water flow loss events
occurred ina moving 4 day time
window. Corrective action is needed to
identify and eliminate the cause. See
“Chilled Water Pump Control,” p. 81
for
more details.
Local
Evaporator Water Flow Overdue
Evaporator Water Flow Overdue
Evap Water Flow Overdue
Chiller
Immediate
and Special
Action
NonLatch
All
After the pump request was activated,
the evaporator water flow overdue wait
time elapsed before water flow was
established. Special action is to keep
the evap pump request active in a
diagnostic override mode. See
“Chilled
Water Pump Control,” p. 81
for more
details.
Remote
Evaporator Water Flow Lost – Pump 1
Evaporator Water Flow Lost – Pump 1
Evap Water Flow Lost
Chiller
Warning and
Special Action
NonLatch
All
For dual evaporator pump
configurations only. Evaporator Water
Flow Lost diagnostic occurred while
Pump 1 was the selected pump. See
“Chilled Water Pump Control - Field
Supplied Dual Pumps,” p. 82
for more
details.
Remote
Evaporator Water Flow Lost – Pump 2
Evaporator Water Flow Lost – Pump 2
Evap Water Flow Lost
Chiller
Warning and
Special Action
NonLatch
All
For dual evaporator pump
configurations only. Evaporator Water
Flow Lost diagnostic occurred while
Pump 2 was the selected pump. See
“Chilled Water Pump Control - Field
Supplied Dual Pumps,” p. 82
for more
details.
Remote
Evaporator Water Flow Overdue –
Pump 1
Evaporator Water Flow Overdue –
Pump 1
Evap Water Flow Overdue
Chiller
Warning and
Special Action
NonLatch
All
For dual evaporator pump
configurations only. Evaporator Water
Flow Overdue diagnostic occurred
while Pump 1 was the selected pump.
See
“Chilled Water Pump Control -
Field Supplied Dual Pumps,” p. 82
for
more details.
Remote
Evaporator Water Flow Overdue –
Pump 2
Evaporator Water Flow Overdue –
Pump 2
Evap Water Flow Overdue
Chiller
Warning and
Special Action
NonLatch
All
For dual evaporator pump
configurations only. Evaporator Water
Flow Overdue diagnostic occurred
while Pump 2 was the selected
pump.See
“Chilled Water Pump Control
- Field Supplied Dual Pumps,” p. 82
for
more details.
Remote
Fault Detected: Evaporator Water
Pump 1
Fault Detected: Evaporator Water
Pump 1
Fault: Evap Water Pump
Chiller
Normal or
Warning and
Special Action
NonLatch
All
For systems with no evaporator pump
or a single evaporator pump, a normal
shutdown shall be performed. For
multiple pump systems, detection of a
pump fault will generally cause pump
control to switch to the redundant
pump. See
“Chilled Water Pump
Control - Field Supplied Dual Pumps,”
p. 82
for more details.
Remote
Summary of Contents for CGAM
Page 44: ...44 CG SVX17D EN Installation Mechanical Figure 39 CGAM W 80 120 Ton Rigging X Z Y ...
Page 104: ...104 CG SVX17D EN CGAM Operating Principles Figure 79 10 15 Ton Compressor Internal Components ...
Page 105: ...CG SVX17D EN 105 CGAM Operating Principles Figure 80 15 30 Ton Compressor Internal Components ...
Page 135: ...CG SVX17D EN 135 Controls Interface Figure 87 Diagnostic View ...
Page 149: ...CG SVX17D EN 149 Unit Start Up Procedures Figure 95 Power Up to Starting ...
Page 185: ...CG SVX17D EN 185 Unit Wiring S2075 1 20 35 Ton Slant Frame Table of Contents ...
Page 186: ...186 CG SVX17D EN Unit Wiring S2075 2 20 35 Ton Slant Frame Legend ...
Page 187: ...CG SVX17D EN 187 Unit Wiring 20 35 Ton Slant Frame Legend ...
Page 188: ...188 CG SVX17D EN Unit Wiring S2075 3 20 35 Ton Slant Frame Notes ...
Page 189: ...CG SVX17D EN 189 Unit Wiring 20 35 Ton Slant Frame Notes ...
Page 190: ...190 CG SVX17D EN Unit Wiring S2075 4 20 35 Ton Slant Frame Compressor Power Circuit 1 ...
Page 191: ...CG SVX17D EN 191 Unit Wiring 20 35 Ton Slant Frame Compressor Power Circuit 1 ...
Page 192: ...192 CG SVX17D EN Unit Wiring S2075 6 20 35 Ton Slant Frame Fan Power Circuit 1 ...
Page 193: ...CG SVX17D EN 193 Unit Wiring 20 35 Ton Slant Frame Fan Power Circuit 1 ...
Page 194: ...194 CG SVX17D EN Unit Wiring S2075 8 20 35 Ton Slant Frame Pump Power Control ...
Page 195: ...CG SVX17D EN 195 Unit Wiring 20 35 Ton Slant Frame Pump Power Control ...
Page 196: ...196 CG SVX17D EN Unit Wiring S2075 9 20 35 Ton Slant Frame Compressor Control ...
Page 197: ...CG SVX17D EN 197 Unit Wiring 20 35 Ton Slant Frame Compressor Control ...
Page 198: ...198 CG SVX17D EN Unit Wiring S2075 10 20 35 Ton Slant Frame Fan Control 2 3 Fan Units ...
Page 199: ...CG SVX17D EN 199 Unit Wiring 20 35 Ton Slant Frame Fan Control 2 3 Fan Units ...
Page 200: ...200 CG SVX17D EN Unit Wiring S2075 12 20 35 Ton Slant Frame Common Control ...
Page 201: ...CG SVX17D EN 201 Unit Wiring 20 35 Ton Slant Frame Common Control ...
Page 202: ...202 CG SVX17D EN Unit Wiring S2075 13 20 35 Ton Slant Frame Common Control ...
Page 203: ...CG SVX17D EN 203 Unit Wiring 20 35 Ton Slant Frame Common Control ...
Page 204: ...204 CG SVX17D EN Unit Wiring S2075 14 20 35 Ton Slant Frame Freeze Protection ...
Page 205: ...CG SVX17D EN 205 Unit Wiring 20 35 Ton Slant Frame Freeze Protection ...
Page 206: ...206 CG SVX17D EN Unit Wiring V2075 1 40 70 Ton V Frame Table of Contents ...
Page 207: ...CG SVX17D EN 207 Unit Wiring 40 70 Ton V Frame Table of Contents ...
Page 208: ...208 CG SVX17D EN Unit Wiring V2075 2 40 70 Ton V Frame Legend ...
Page 209: ...CG SVX17D EN 209 Unit Wiring 40 70 Ton V Frame Legend ...
Page 210: ...210 CG SVX17D EN Unit Wiring V2075 3 40 70 Ton V Frame Notes ...
Page 211: ...CG SVX17D EN 211 Unit Wiring 40 70 Ton V Frame Notes ...
Page 212: ...212 CG SVX17D EN Unit Wiring V2075 4 40 70 Ton V Frame Compressor Power Circuit 1 ...
Page 213: ...CG SVX17D EN 213 Unit Wiring 40 70 Ton V Frame Compressor Power Circuit 1 ...
Page 214: ...214 CG SVX17D EN Unit Wiring V2075 5 40 70 Ton V Frame Compressor Power Circuit 2 ...
Page 215: ...CG SVX17D EN 215 Unit Wiring 40 70 Ton V Frame Compressor Power Circuit 2 ...
Page 216: ...216 CG SVX17D EN Unit Wiring V2075 6 40 70 Ton V Frame Fan Power Circuit 1 ...
Page 217: ...CG SVX17D EN 217 Unit Wiring 40 70 Ton V Frame Fan Power Circuit 1 ...
Page 218: ...218 CG SVX17D EN Unit Wiring V2075 7 40 70 Ton V Frame Fan Power Circuit 2 ...
Page 219: ...CG SVX17D EN 219 Unit Wiring 40 70 Ton V Frame Fan Power Circuit 2 ...
Page 220: ...220 CG SVX17D EN Unit Wiring V2075 8 40 70 Ton V Frame Pump Power Control ...
Page 221: ...CG SVX17D EN 221 Unit Wiring 40 70 Ton V Frame Pump Power Control ...
Page 222: ...222 CG SVX17D EN Unit Wiring V2075 9 40 70 Ton V Frame Compressor Control ...
Page 223: ...CG SVX17D EN 223 Unit Wiring 40 70 Ton V Frame Compressor Control ...
Page 224: ...224 CG SVX17D EN Unit Wiring V2075 10 40 70 Ton V Frame Fan Control 2 3 Fan Units ...
Page 225: ...CG SVX17D EN 225 Unit Wiring 40 70 Ton V Frame Fan Control 2 3 Fan Units ...
Page 226: ...226 CG SVX17D EN Unit Wiring V2075 12 40 70 Ton V Frame Common Control ...
Page 227: ...CG SVX17D EN 227 Unit Wiring 40 70 Ton V Frame Common Control ...
Page 228: ...228 CG SVX17D EN Unit Wiring V2075 13 40 70 Ton V Frame Common Control ...
Page 229: ...CG SVX17D EN 229 Unit Wiring 40 70 Ton V Frame Common Control ...
Page 230: ...230 CG SVX17D EN Unit Wiring V2075 14 40 70 Ton V Frame Freeze Protection ...
Page 231: ...CG SVX17D EN 231 Unit Wiring 40 70 Ton V Frame Freeze Protection ...
Page 232: ...232 CG SVX17D EN Unit Wiring W2075 1 80 130 Ton W Frame Table of Contents ...
Page 233: ...CG SVX17D EN 233 Unit Wiring 80 130 Ton W Frame Table of Contents ...
Page 234: ...234 CG SVX17D EN Unit Wiring W2075 2 80 130 Ton W Frame Legend ...
Page 235: ...CG SVX17D EN 235 Unit Wiring 80 130 Ton W Frame Legend ...
Page 236: ...236 CG SVX17D EN Unit Wiring W2075 3 80 130 Ton W Frame Notes ...
Page 237: ...CG SVX17D EN 237 Unit Wiring 80 130 Ton W Frame Notes ...
Page 238: ...238 CG SVX17D EN Unit Wiring W2075 4 80 130 Ton W Frame Compressor Power Circuit 1 ...
Page 239: ...CG SVX17D EN 239 Unit Wiring 80 130 Ton W Frame Compressor Power Circuit 1 ...
Page 240: ...240 CG SVX17D EN Unit Wiring W2075 5 80 130 Ton W Frame Compressor Power Circuit 2 ...
Page 241: ...CG SVX17D EN 241 Unit Wiring 80 130 Ton W Frame Compressor Power Circuit 2 ...
Page 242: ...242 CG SVX17D EN Unit Wiring W2075 6 80 130 Ton W Frame Fan Power Circuit 1 ...
Page 243: ...CG SVX17D EN 243 Unit Wiring 80 130 Ton W Frame Fan Power Circuit 1 ...
Page 244: ...244 CG SVX17D EN Unit Wiring W2075 7 80 130 Ton W Frame Fan Power Circuit 2 ...
Page 245: ...CG SVX17D EN 245 Unit Wiring 80 130 Ton W Frame Fan Power Circuit 2 ...
Page 246: ...246 CG SVX17D EN Unit Wiring W2075 8 80 130 Ton W Frame Pump Power Control ...
Page 247: ...CG SVX17D EN 247 Unit Wiring 80 130 Ton W Frame Pump Power Control ...
Page 248: ...248 CG SVX17D EN Unit Wiring W2075 9 80 130 Ton W Frame Compressor Control ...
Page 249: ...CG SVX17D EN 249 Unit Wiring 80 130 Ton W Frame Compressor Control ...
Page 250: ...250 CG SVX17D EN Unit Wiring W2075 10 80 130 Ton W Frame Fan Control 2 3 Fan Units ...
Page 251: ...CG SVX17D EN 251 Unit Wiring 80 130 Ton W Frame Fan Control 2 3 Fan Units ...
Page 252: ...252 CG SVX17D EN Unit Wiring W2075 11 80 130 Ton W Frame Fan Control 4 5 Fan Units ...
Page 253: ...CG SVX17D EN 253 Unit Wiring 80 130 Ton W Frame Fan Control 4 5 Fan Units ...
Page 254: ...254 CG SVX17D EN Unit Wiring W2075 12 80 130 Ton W Frame Common Control ...
Page 255: ...CG SVX17D EN 255 Unit Wiring 80 130 Ton W Frame Common Control ...
Page 256: ...256 CG SVX17D EN Unit Wiring W2075 13 80 130 Ton W Frame Common Control ...
Page 257: ...CG SVX17D EN 257 Unit Wiring 80 130 Ton W Frame Freeze Protection ...
Page 258: ...258 CG SVX17D EN Unit Wiring W2075 14 80 130 Ton W Frame Freeze Protection ...
Page 259: ...CG SVX17D EN 259 Unit Wiring 80 130 Ton W Frame Common Control ...
Page 260: ...260 CG SVX17D EN Unit Wiring 2076 1 Field Wiring Diagram ...
Page 261: ...CG SVX17D EN 261 Unit Wiring C TRANE Field Wiring Diagram ...
Page 262: ...262 CG SVX17D EN Unit Wiring 2076 2 FUSE Field Wiring Diagram Notes ...