Page 51
Symptom
Cooling
Heating
Who can take
corrective action U
= User
S = specialised
personnel
Probable cause
Possible remedy
E
The compressor
does not start
because the
minimum
pressure switch
has tripped
x
x
s
Pressure switch out of order
Check and replace.
x
x
s
Machine completely void of
refrigerant
See point G.
x
u
Water circulation pump blocked
Unlock the pump
x
s
Water circulation pump blocked and
defective
Check the pump and replace if necessary
x
s
Presence of frost on the evaporator
coil
See point N.
x
x
s
Refrigerant filter clogged
Check and replace.
x
x
s
Expansion device that is not working
properly
Check and replace if necessary.
x
x
s
Presence of moisture in the
refrigerant circuit
Replace the filter, dry and recharge
G
Lack of gas
x
x
s
Loss in the refrigerant circuit
Check the cooling circuit using a leak
detector after pressurising the circuit to
approximately 4 bars.
Repair, evacuate and refill.
H
Frost in the
liquid line
downstream from
a filter
x
x
s
The filter is clogged
Replace the filter
I
The unit works
continuously
without ever
stopping
x
x
s
Lack of refrigerant gas
See item G.
x
x
u
Incorrect tuning of the operating
thermostat
Check and set.
x
x
s
Excessive thermal load
Reduce the thermal load
x
x
s
Compressor does not give the
thermal output
Check, change or revise
x
x
s
The liquid filter is clogged
Replace.
L
The unit works
regularly but with
an insufficient
capacity
x
x
s
Low refrigerant charge
See point G.
x
x
s
4-way reversing valve defective
Check the power supply and the coil of the
valve and replace the valve
Symptom
Cooling
Heating
Who can take
corrective action U
= User
S = specialised
personnel
Probable cause
Possible remedy
M
Frost in the
compressor intake
pipe
x
x
s
Expansion device that is not working
properly
Verify and replace.
x
x
s
Water circulation pump blocked
Unlock the pump.