Trane BAYLOAM105AA Installer'S Manual Download Page 14

14

Installer’s Guide

minutes after Y is applied.

The liquid temperature set point will not change

during system start-up.

The dip switches should be set prior to initial

application of the Y signal to the Control Module.

The dip switches should be set for each specific

HVAC system based upon the following
instructions:

8c.  Determine liquid temperature set point

Reference appropriate high side charging chart
for liquid pressure for cooling units and head
pressure for heat pump units.

Locate the high side pressure for 70 deg F
outdoor temperature at the expected indoor wet
bulb temperature in Table 2. Correct the high
side pressure according to the specific unit being
used.  For Heat pumps subtract 7 psi, for cooling
only units subtract 0

 

(zero) psi. Using the

refrigerant properties chart, find the saturation
temperature for the calculated liquid pressure.
Subtract the anticipated sub-cooling temperature
(typically 12 degrees) from the saturation
temperature to obtain an estimate of the liquid
temperature. Set S2 dip switch 1, 2 and 3 settings
to the nearest liquid temperature set point in the
table below.

S2 Dip Switch

 

4:

Off - Automatic Mode
(recommended setting)

On - Manual Mode

8b.  Dip Switches (S2)

The Control Module will control a liquid

temperature set point as determined by the dip
switch settings. The dip switch is used:

1.  To select either Automatic mode or Manual
Mode operation (S2 dip switch 4 setting).
2.  To select the liquid temperature set point (S2
dip switch 1, 2 and 3 settings).

Automatic Mode (S2 dip switch 4 in “Off”

position)  - The Control Module determines the

approach temperature

 based upon the liquid and

ambient temperature readings. The 

approach

temperature

 = liquid temperature – ambient

temperature. The approach temperature is
calculated only when the ambient temperature is
in the range of 65 to 75 deg F and the outdoor fan
is on continuously. If the Control Module has not
yet acquired an approach temperature, S2 dip
switch 1, 2 and 3 settings are used for
determining the liquid temperature set point the
same as in Manual Mode. If the Control Module
has acquired an 

approach temperature

, then the

liquid temperature set point is determined as
follows:

Liquid Temperature Set Point = 

Approach

Temperature

 + 70 deg F

Manual Mode (S2 dip switch 4 in “On” position) -

The S2 dip switch 1,2,3 settings are read by the
Control Module and used to determine the liquid
temperature set point when:

1) Y is first applied,

2) After initial startup mode completion, during

the system control mode and no sooner than six

8.  System Setup

The Control Module contains a momentary test

switch (S1) and a 4-position installer selectable
dip switch (S2). Both components are located in
the lower right hand corner of the Control
Module. See Figure 11 on page 10.

8a.  Test Switch (S1)

The test switch provides a means of verifying that
the fan motor is under the control of the Low
Ambient Control Module. A "Y" signal must be
present in order to test the control. Depressing the
test switch causes the fan to alternately cycle on

(for 3 seconds) and off (for 3 seconds) for a total
time of 12 seconds. The on / off fan operation may
be observed by watching the fan once the test
function has been invoked or by monitoring the
head pressure using a gauge set. The LED on the
solid state relay should light when voltage is being
applied to the fan motor. Once the 12-second test
period is complete the control resumes normal
control operation.

LIQUID TEMP

SET POINT°F

DIP

SWITCH 1

DIP

SWITCH 2

DIP

SWITCH 3

70 °F

OFF

OFF

OFF

76 °F

OFF

OFF

ON

82 °F

OFF

ON

OFF

88 °F

OFF

ON

ON

94 °F

ON

OFF

OFF

100 °F

ON

OFF

ON

106 °F

ON

ON

OFF

112 °F

ON

ON

ON

Table 2. Liquid Temperature Set Point

8d.  LEDs

The Control Module contains two LEDs, one

green and one red surface mount. See Figure 11
on page 10. The green LED is a status indicator
labeled Lite Port on the Control Module and
flashes at a ½  second on (plus fast blink at the
end for lite port data) and ½   second off rate in
the cooling mode. In the heating mode the green

Summary of Contents for BAYLOAM105AA

Page 1: ...ontrol Module is to be mounted to the universal bracket included in the kit or the Compressor Startkit bracket depending upon your unit s configuration Continue with the following section that applies...

Page 2: ...LOAM Kit Components Note Unit vents not shown Universal Bracket Liquid Sensor Clamp Bushing Wire Nuts 5 Cable Ties 5 Liquid Sensor Assembly Thermal Compound Outdoor Air Sensor Retainer Dart Informatio...

Page 3: ...ressor Start Kit bracket using the two 2 machine screws See Figure 3 3 Continue with step 4 Mounting the Liquid Line Sensor page 7 Figure 3 230 Volt 2 4WC with Compressor Start Kit 460 Volt 2 4WC 3060...

Page 4: ...s 230 460 Volt Three Phase 2 4WC units except for 2 4WC 3060A4 460 Volt 4WCZ6 units Mount Universal Bracket to back wall of Control Box with two 2 Sheetmetal Screws horizontally Control Box Mount Univ...

Page 5: ...5 230 Volt 2 4YC and 4DC units with Compressor Start Kit 460 volt 2 4YC 3060A4 460 volt 4YCZ6 units 3 Mount the Control module to the Start Kit bracket with the two 2 machine metal screws you removed...

Page 6: ...to the bottom of the control box with two 2 sheetmetal screws One is inserted horizontally from inside the control box into the universal bracket and one is inserted vertically See Figure 6 Figure 6 2...

Page 7: ...utside of the outdoor coil See Figure 9 page 8 1 On the outdoor fan grill remove eight 8 plastic screw caps covering the fan screws Then remove the eight 8 screws that secure the outdoor fan grill to...

Page 8: ...e Sensor OUTDOOR TEMPERATURE SENSOR DART OUTDOOR TEMPERATURE SENSOR WIRES LIQUID LINE SENSOR WIRES LOUVERED PANEL REMOVE 3 SCREWS LIFT PANEL UP TO UNHOOK FROM SLOT REMOVE 8 FAN GRILL SCREWS TO ROUTE O...

Page 9: ...lead with a wire nut supplied Connect the other black wire from the solid state relay SSR to the contactor terminal L2 from where the fan motor lead was disconnected Connect Low voltage wires BYO 1 Co...

Page 10: ...over the header pins 2 Connect the yellow lead wire of the harness to a male tab on the right hand side of the main contactor low voltage contactor coil terminal See Figure 12 3 Connect the blue lead...

Page 11: ...he insertion of the connector housing on to the J5 header place the connector on the tips of the three header pins Angle the connector upward to ward the header latch while pushing connector over the...

Page 12: ...ector over the header pins 2 Connect the yellow lead wire of the harness to a male tab on the right hand side of the main contactor low voltage contactor coil terminal See Figure 15 3 Connect the blue...

Page 13: ...f the three header pins Angle the connector upward toward the header latch while pushing connector over the header pins 2 Connect the yellow lead wire of the harness to a male tab on the right hand si...

Page 14: ...has not yet acquired an approach temperature S2 dip switch 1 2 and 3 settings are used for determining the liquid temperature set point the same as in Manual Mode If the Control Module has acquired an...

Page 15: ...c e S g n i h s a l F f f O d n o c e S t l u a F r o s n e S t n e i b m A y l s u o u n i t n o c N O d r a o b t l u a F M O R P E E C 2 I e l b a r i a p e r d l e i f t o N e r u l i a f working...

Page 16: ...ler s Guide Trane 6200 Troup Highway Tyler TX 75707 9010 The manufacturer has a policy of continuous product and product data improvement It reserves the right to change design and specification witho...

Reviews: