18-HE46D1-3B-EN  

3

Installer’s Guide

MOUNTING OUTDOOR TEMPERATURE SENSOR

  7. Using pliers, bend the corner of the control box 

base downward, to create an opening for the sensor 

leads. See Figure 4.

  8. Route the sensor, from the control board, down 

through the opening created in the control box base. 

With wire tie provided, secure the sensor to the 

low voltage wiring or conduit below the control box 

base. Place the wire tie on the sensor wires (not on 

the sensor) and dress so that the temperature sens-

ing area is not in direct contact with any surrounding 

surfaces and is not in direct sunlight.

WIRING CONTROL MODULE

9A) Cooling Only Air Conditioner Models:

 See Figure 

5 Disconnect the black fan motor lead from the 

contactor (This wire is attached to contactor termi-

nal “T2”, with a quick connect terminal). Reconnect 

this fan motor lead to the black wire from the solid 

state relay on the control module. This wire has a 

sleeved, 1/4" male tab for attaching to the fan motor 

wire terminal.

    Connect the other black wire from the solid state 

relay to the contactor terminal “T2” (from where the 

fan motor lead was disconnected).

    Low voltage wires:

    Connect the 3-pin wire assembly to J5 on the con-

trol board (3-pin male connector).

NOTE: 

To ease the insertion of the connector housing 

onto the J5 header, place the connector on the 

tips of the three header pins.  Angle the connec-

OUTDOOR TEMPERATURE SENSOR

SENSOR WIRE ROUTING

BEND CONTROL

BOX CORNER

AIR CONDITIONING /  COOLING ONLY

tor upward toward the header latch while push-

ing connector over the header pins.

    Connect the yellow lead wire to a 1/4" male tab on 

the right hand side of the main contactor (low volt-

age contactor coil terminal).

    Connect the blue lead wire to the wire nut junction 

of the blue wire.

    Connect the orange wire to the wire nut junction of 

the yellow wire.

    (New wire nuts are provided)

Summary of Contents for BAYLOAM103

Page 1: ...nce and replaced with autho rized parts only INSTALLATION NOTE As the head pressure control is applied to units op erating in low ambient conditions it is required that the units have compressor crank...

Page 2: ...he insulation tape b If installing on a heat pump unit attach the liquid line sensor to the liquid line running vertically directly behind the control box Apply thermal grease supplied to the liquid l...

Page 3: ...motor lead to the black wire from the solid state relay on the control module This wire has a sleeved 1 4 male tab for attaching to the fan motor wire terminal Connect the other black wire from the so...

Page 4: ...the N C terminal on the defrost board relay from where the fan motor was disconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease t...

Page 5: ...sconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease the insertion of the connector housing onto the J5 header place the connector...

Page 6: ...termin ing the liquid temperature set point the same as in Manual Mode If the controller has acquired an ap proach temperature then the liquid temperature set point is determined as follows Liquid Tem...

Page 7: ...off accordingly SYSTEM CHECK OUT COOLING UNITS ONLY Verify that the control module is installed and wired per the instructions contained within this installer s guide J5 Blue connected to B J5 Yellow...

Page 8: ...Switch S1 may be used to verify the Control Module has con trol over the fan Momentarily depress the TEST Switch S1 on the Control board The fan should then cycle 3 seconds on then 3 seconds off for...

Reviews: