background image

 18-HE46D1-3B-EN

Installer’s Guide

200 / 230 VOLT HEAT PUMP

9B) 200/230 Volt Heat Pump: 

See Figure 6

    Disconnect the black fan motor lead from the defrost 

board relay (The black wire is attached to the “N.C.” 

terminal of the relay). 

CAUTION

!

FIRMLY HOLD RELAY WHEN REMOVING 

WIRE.

    Reconnect this fan motor lead to the black wire from 

the solid state relay on the control module (This wire 

has a sleeved, 1/4" male tab for attaching to the fan 

motor lead wire terminal).

    Connect the other black wire from the solid state re-

lay to the “N.C.” terminal on the defrost board relay 

(from where the fan motor was disconnected).

    Low voltage wires:

    Connect the 3-pin wire assembly to J5 on the con-

trol board (3-pin male connector).

NOTE: 

To ease the insertion of the connector housing 

on to the J5 header, place the connector on the 

tips of the three header pins. Angle the connec-

tor upward toward the header latch while push-

ing connector over the header pins.

    Connect the yellow lead wire to a 1/4" male tab on 

the right hand side of the main contactor (low volt-

age contactor coil terminal).

    Connect the blue lead wire to the wire nut junction 

of the blue wire.

    Connect the orange lead wire to the wire nut junc-

tion of the orange wire.

    (New wire nuts are provided.)

Summary of Contents for BAYLOAM103

Page 1: ...nce and replaced with autho rized parts only INSTALLATION NOTE As the head pressure control is applied to units op erating in low ambient conditions it is required that the units have compressor crank...

Page 2: ...he insulation tape b If installing on a heat pump unit attach the liquid line sensor to the liquid line running vertically directly behind the control box Apply thermal grease supplied to the liquid l...

Page 3: ...motor lead to the black wire from the solid state relay on the control module This wire has a sleeved 1 4 male tab for attaching to the fan motor wire terminal Connect the other black wire from the so...

Page 4: ...the N C terminal on the defrost board relay from where the fan motor was disconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease t...

Page 5: ...sconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease the insertion of the connector housing onto the J5 header place the connector...

Page 6: ...termin ing the liquid temperature set point the same as in Manual Mode If the controller has acquired an ap proach temperature then the liquid temperature set point is determined as follows Liquid Tem...

Page 7: ...off accordingly SYSTEM CHECK OUT COOLING UNITS ONLY Verify that the control module is installed and wired per the instructions contained within this installer s guide J5 Blue connected to B J5 Yellow...

Page 8: ...Switch S1 may be used to verify the Control Module has con trol over the fan Momentarily depress the TEST Switch S1 on the Control board The fan should then cycle 3 seconds on then 3 seconds off for...

Reviews: