14
RT-SVN044A-EN
Table 4. Controller menu structure (continued)
Menu
Parameter
Parameter
Default Value
Parameter
Range and
Increment
(a)
Parameter
Recommended
Value
(b)
Notes
DCVCAL ENA
MAN
MAN (manual)
AUTO
MAN
Turns on the DCV automatic control of
the dampers. Resets ventilation based
on the RA, OA and MA sensor
conditions. Requires all sensors (RA,
OA, MA and CO
2
). This operation is not
operable with a 2-speed fan unit.
MAT T CAL
0.0 F°
(+/-2.5°F)
0.0 F°
Allows for the operator to adjust for an
out of calibration temperature sensor.
OA T CAL
0.0 F°
(+/-2.5°F)
0.0 F°
Allows for the operator to adjust for an
out of calibration temperature sensor.
ADVANCED
SETUP
OA H CAL
0% RH
(+/-10% RH)
0% RH
Allows for the operator to adjust for an
out of calibration humidity sensor.
RA T CAL
0.0 F°
(+/-2.5°F)
0.0 F°
Allows for the operator to adjust for an
out of calibration temperature sensor.
RA H CAL
0% RH
(+/-10% RH)
0% RH
Allows for the operator to adjust for an
out of calibration humidity sensor.
DA T CAL
0.0 F°
(+/-2.5°F)
0.0 F°
DA T CAL is not available.
2SP FAN DELAY
5 Minutes
0 to 20 minutes in
1 minute
increments.
5 Minutes
When in economizing mode this is the
delay for the high speed fan to try to
satisfy the call for second stage cooling
before the first stage mechanical
cooling is enabled.
DAMPER VMIN-HS
N/A
N/A
N/A
Positions damper to VMIN position.
DAMPER VMAX-HS
N/A
N/A
N/A
Positions damper to VMAX position.
With 2-speed fan units the damper will
position to VMAX low speed fan.
DAMPER OPEN
N/A
N/A
N/A
Positions damper to the full open
position. Exhaust fan contacts enable
during the DAMPER OPEN test. Make
sure you pause in this mode to allow
for exhaust contacts to energize due to
the delay in the system.
DAMPER CLOSE
N/A
N/A
N/A
Positions damper to the fully closed
position.
CHECKOUT
CONNECT Y1-O
N/A
N/A
N/A
Closes the Y1-O relay (Y1-O). See
CONNECT Y2-O
N/A
N/A
N/A
N/A
CONNECT AUX1-O
N/A
N/A
N/A
CONNECT AUX1 O energizes the
AUX1-O output. If AUX1-O setting is:
•
NONE — No action taken
•
ERV — 24 Vac out. Turns on or
signals an ERV that the conditions
are not good for economizing but
are good for ERV operation.
•
SYS — 24 Vax out. Issues a
system alarm.
CONNECT EXH1
N/A
N/A
N/A
Closes the power exhaust fan 1 relay
(EXH1).
ALARMS(_)
(e)
MAT SENS ERR
N/A
N/A
N/A
CO
2
SENS ERR
N/A
N/A
N/A