Table 4. Controller menu structure
Menu
Parameter
Parameter
Default Value
Parameter
Range and
Increment
(a)
Parameter
Recommended
Value
(b)
Notes
ECON AVAIL
(c)
NO
YES/NO
N/A
YES = economizing available; the
system can use Outdoor Air for free
cooling when required.
ECONOMIZING
NO
YES/NO
N/A
YES = Outdoor Air being used for 1st
stage cooling.
OCCUPIED
NO
YES/NO
N/A
YES = OCC signal received from space
thermostat or unitary controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP
N/A
COOL
HEAT
N/A
HEAT PUMP is not available.
COOL Y1-IN
OFF
ON/OFF
N/A
Y1-I signal from space thermostat or
unitary controller for cooling stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
COOL Y1-OUT
OFF
ON/OFF
N/A
Cool Stage 1 Relay Output to
mechanical cooling (Y1-OUT terminal).
COOL Y2-IN
OFF
N/A
N/A
COOL Y2-IN is not available.
COOL Y2-OUT
OFF
N/A
N/A
COOL Y2-OUT is not available.
MA TEMP
_ _._ ºF
-40 to 140°F
N/A
Displays value of measured mixed air
from MAT sensor. Displays –.- if not
connected, short, or out- of-range.
STATUS
DA TEMP
_ _._ ºF
-40 to 140°F
N/A
DA TEMP is not available.
OA TEMP
_ _._ ºF
-40 to 140°F
N/A
Displays measured value of outdoor
air temperature. Displays –°F if sensor
sends invalid value, if not connected,
short or out-of-range.
OA HUM
_ _ %
0 to 100%
N/A
Displays measured value of outdoor
humidity from OA Sylk Bus sensor.
Displays –% if not connected, short, or
out- of-range.
RA TEMP
_ _._ ºF
0 to 140°F
N/A
Displays measured value of return air
temperature from RA Sylk Bus sensor.
Displays –°F if sensor sends invalid
value, if not connected, short or out-
of-range.
RA HUM
_ _ %
0 to 100%
N/A
Displays measured value of return air
humidity from RA Sylk Bus sensor.
Displays –% if sensor sends invalid
value, if not connected, short or out-
of-range.
IN CO
2
_ _ _ ppm
0 to 2000 ppm
N/A
Displays value of measured CO
2
from
CO
2
sensor. Invalid if not connected,
short or out-of-range. May be adjusted
in Advanced menu by Zero offset and
Span. 0-10 Vdc CO
2
sensors require
CO
2
ZERO to be 400 and CO
2
SPAN to
be 1600 in Advanced Setup menu.
DCV STATUS
N/A
ON/OFF
N/A
Displays ON if above setpoint and OFF
if below setpoint, and ONLY if a CO
2
sensor is connected.
DAMPER OUT
2.0V
2.0 to 10.0 V
N/A
Displays output voltage or position to
the damper actuator.
(d)
ACT POS
N/A
0 to 100%
N/A
Displays actual position of actuator.