background image

RT-SVN044A-EN

13

Table 4. Controller menu structure (continued)

Menu

Parameter

Parameter
Default Value

Parameter
Range and
Increment

(a)

Parameter
Recommended
Value

(b)

Notes

FAN SPEED

(c)

1 speed

1 speed/ 2 speed

See unit

nameplate:

Digit 15 = 0 or 1 -

1 speed;

Digit 15 = 7 or 9 -

2 speed

Sets economizer controller for
operation of 1 speed or 2 speed supply
fan. The controller does not control the
fan but positions the OA and RA
dampers to the heating or cooling
mode. See page 23 for modes and
position.

Note:

2-speed fan option also needs

Heat (W1) programmed in AUX
2 In.

FAN CFM

(c)

5000cfm

100 to 15000 cfm;

increment by 100

5000 cfm

This is the capacity of the RTU. The
value is found in the Unit Catalog. The
cfm of the fan is only used with DCV
CAL ENABLE AUO.

SYSTEM

SETUP

AUX1 OUT

NONE

NONE

ERV

EXH2

SYS

NONE

AUX1 OUT is a programmable output
used for System Alarm output.

OCC

(c)

INPUT

INPUT or ALWAYS

ALWAYS

When using a setback thermostat with
occupancy out (24 Vac), the 24 Vac is
input “INPUT” to the OCC terminal. If
no occupancy output from the
thermostat then change program to
“ALWAYS” OR add a jumper from
terminal R to OCC terminal.

FACTORY DEFAULT

(c)

NO

NO or YES

NO

Resets all set points to factory defaults
when set to YES. LCD will briefly flash
YES and change to NO but all
parameters will change to factory
default values.

MA LO SET

(c)

45ºF

35 to 55°F;

increment by 1°F

45ºF

Temp to activate Freeze Protection
(close damper or modulate to MIN POS
if temp falls below set value).

FREEZE POS

(c)

CLO

CLO
MIN

CLO

Damper position when freeze
protection is active (closed or MIN
POS).

CO

2

ZERO

(c)

0ppm

0 to 500 ppm;

increment by 10

0ppm

CO

2

ppm level to match CO

2

sensor

start level. 0-10 Vdc CO

2

sensors

require CO

2

ZERO to be 400.

ADVANCED

SETUP

CO

2

SPAN

(c)

2000ppm

1000 to 3000

ppm; increment

by 50

2000 ppm

CO

2

ppm span to match CO

2

sensor;

e.g.; 500-1500 sensor output would
be 500 CO

2

zero and 1000 CO

2

span.

0-10 Vdc CO

2

sensors require CO

2

SPAN to be 1600.

STG3 DLY

2.0h

0 min, 5 min, 15

min, then 15 min

intervals. Up to 4h

or OFF

2.0h

Delay after stage 2 for cool has been
active. Turns on 2nd stage of
mechanical cooling when economizer
is 1st stage call and mechanical
cooling is 2nd stage call. Allows three
stages of cooling, 1 economizer and 2
mechanical. OFF = no Stage 3 cooling.

SD DMPR POS

CLO

CLO

OPN

CLO

Indicates shutdown signal from space
thermostat or unitary controller. When
controller receives 24 Vac input on the
SD terminal in conventional mode, the
OA damper will open if programmed
for OPN and OA damper will close if
programmed for CLO. All other
controls, e.g., Y1-O, EXH1, etc. will
shut off.

E

Ecco

on

no

om

miizze

err C

Co

on

nttrro

olllle

err

Summary of Contents for BAYECON355 Series

Page 1: ...d or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that...

Page 2: ...r p pr ro op pe er r P PP PE E f fo or r t th he e j jo ob b b be ei in ng g u un nd de er rt ta ak ke en n c co ou ul ld d r re es su ul lt t i in n d de ea at th h o or r s se er ri io ou us s i in...

Page 3: ...ri ig ge er ra an nt t h ha an nd dl li in ng g e et tc c W Wh he er re e l lo oc ca al l r re eg gu ul la at ti io on ns s a ar re e m mo or re e s st tr ri in ng ge en nt t t th ha an n t th he es...

Page 4: ...he Keypad When Working with Menus 9 Time out and Screensaver 9 Controller Menu Structure 9 Sequence of Operation 15 Initiation of Operating Modes 16 Economizer Setup and Configuration Field and Factor...

Page 5: ...nspection for Concealed Damage Visually inspect the components for concealed damage as soon as possible after delivery and before it is stored If concealed damage is discovered Notify the carrier s te...

Page 6: ...installation Economizer Side Post Side Post 5 Connect the unit harness to the economizer harness See the figure that follows Additionally connect the green purple white and orange loose wires with mal...

Page 7: ...orange wire is provided for a fault alarm relay or light When the controller s AUX1 OUT is set to SYS this wire will provide 24V when a fault is detected See Figure 7 p 7 Figure 7 Low voltage control...

Page 8: ...emperature sensor is a system critical sensor if it is removed during the set up mode the controller will alarm After 60 minutes the controller will change to Operation mode and all components removed...

Page 9: ...the currently displayed item Press the button to increase change the displayed parameter value Press the button to decrease change the displayed parameter value N No ot te e When values are displayed...

Page 10: ...e OA TEMP c _ _ _ F 40 to 140 F N A Displays measured value of outdoor air temperature Displays F if sensor sends invalid value if not connected short or out of range OA HUM c _ _ 0 to 100 N A Display...

Page 11: ...80 F increment by 1 32 F Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on Commonly referred to as the Compressor lockout At or below the setpoint the Y1 O will n...

Page 12: ...by CFM With 2 speed fan units VENTMIN L low speed fan and VENTMIN H high speed fan settings are required Default for VENTMIN L is 2 5V and VENTMIN H is 2 25V ERV OAT SP 32 F 0 to 50 F increment by 1...

Page 13: ...l briefly flash YES and change to NO but all parameters will change to factory default values MA LO SET c 45 F 35 to 55 F increment by 1 F 45 F Temp to activate Freeze Protection close damper or modul...

Page 14: ...increments 5 Minutes When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled DAMPER...

Page 15: ...are active The menu title ALARMS _ includes the number of active alarms in parenthesis Sequence of Operation Table 5 Dry bulb operation no DCV CO2 sensor 1 speed fan DCV OA Good to economize Y1 I FAN...

Page 16: ...cool when the damper is at 100 open The Economizer mode is controlled by the MAT getting above the MAT SET setting while the OAT is below the DRYBLB SET setting While the fans are not controlled by t...

Page 17: ...ot te e When using the enthalpy Sylk Bus sensors there will be a slight delay while the controller and the sensor communicate Analog sensors do not communicate on the Sylk Bus and output a 20k ohm sig...

Page 18: ...t all wiring connections at the Economizer module s terminals and verify compliance with the installation wiring diagrams For checkout review the status of each configured parameter and perform the ch...

Page 19: ...sh hu ut td do ow wn n b be et tw we ee en n c ch he ec ck ko ou ut t t te es st ts s c co ou ul ld d r re es su ul lt t i in n c co om mp pr re es ss so or r d da am ma ag ge e D Do o n no ot t s sh...

Page 20: ...20 RT SVN044A EN Figure 11 Ultra low leak economizer wiring diagram E Ec co on no om mi iz ze er r C Co on nt tr ro ol ll le er r...

Page 21: ...RT SVN044A EN 21 N No ot te es s...

Page 22: ...22 RT SVN044A EN N No ot te es s...

Page 23: ...RT SVN044A EN 23 N No ot te es s...

Page 24: ...formation please visit trane com or americanstandardair com Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and spec...

Reviews: