Trane BAYECON300 Series Installation Instructions Manual Download Page 11

Installation

ACC-SVN155D-EN

11

Minimum Position Setting

To adjust the minimum position setting and check out the
economizer, the power must be connected.

Close the unit disconnect and place the zone sensor fan
selector in the fan "ON" position and the heat/cool selector
in the "OFF" position. This will place the damper in the
minimum ventilation position.

To adjust the minimum position setting for the required
ventilation air, turn the potentiometer (on the ECA)
clockwise to "open" (to increase the amount of ventilation)
or counterclockwise to "close" (to decrease the amount of
ventilation). The damper will open to this setting each time
the blower circuit is energized.

When adjusting minimum position, the damper may move
to the new setting in several small steps. Once the damper
has remained in position for 10 - 15 seconds without
movement, it can be assumed it is at the new position.

Replace the filter access panel.

The damper will close when the blower circuit is de-
energized.

Dry Bulb Settings

Standard economizer dry bulb changeover is field
selectable to 5 outdoor temperatures. See

Table 1

for

potentiometer settings.The selection is made on the ECA.

Reference Enthalpy Settings

Economizer enthalpy changeover is field selectable to 5
points. See

Table 1

for potentiometer settings. The

selection is made on the ECA.

Table 1.

Potentiometer settings

Potentiometer 

Setting

Dry Bulb

Enthalpy

A

73ºF (22.8ºC)

27 Btu/lb (63 kJ/kg)

B

70ºF (21.1ºC)

25 Btu/lb (58 kJ/kg)

C

(a)

(a) Factory Setting

67ºF (19.4ºC)

23 Btu/lb (53 kJ/kg)

D

63ºF (17.2ºC)

22 Btu/lb (51 kJ/kg)

E

55ºF (12.8ºC)

19 Btu/lb (44 KJ/Kg)

Table 2.

Economizer control options

Control Option

Enable 

Conditions

(a)

(a) Economizing is enabled when these conditions are met.

Dry Bulb (standard)

See 

Table  1

Outdoor Air Temp 

(OAT) 

Reference Enthalpy 

(ReliaTel Only)

See 

Table  1

Outdoor Humidity 

(BAYENTH300*)

Comparative Enthalpy 

(ReliaTel Only)

Outdoor Air Enthalpy 

3.0 BTU/lb. less than 

Return Air Enthalpy

Outdoor Humidity 

Return Humidity 

Return Temperature 

(BAYENTH301*)

Wiring Connections

Locate unit wiring harness plug PPM2A. The plug is
located in the upper left section of the return air section.
Remove the cap covering the plug, and connect to the
economizer wiring harness.

Figure 24.

Electromechanical wiring

Optional Sensors 

Required

(b)

(b) Conditions level will be self configured when optional sensors are con-

nected.

Summary of Contents for BAYECON300 Series

Page 1: ...tall and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the ap...

Page 3: ...ations Introduction ACC SVN155D EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permission Trane...

Page 4: ...ail Request an immediate joint inspection of the damage by the carrier and the consignee Note Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative P...

Page 5: ...onnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with a CAT III or IV voltmete...

Page 6: ...in Figure 6 Figure 6 Install return air damper assembly Carrier 3 a Attach block off 5 to unit using four screws as illustrated in Figure 7 The block off is designed to close the opening created betw...

Page 7: ...Figure 9 e Secure economizer using 4 screws on left side and 4 screws on right side as illustrated in Figure 9 f Attach connecting rod bracket to outdoor damper blade using two screws on each side as...

Page 8: ...er assembly outward into the operating position See Figure 13 5 Remove approximately 3 of gasket material from the bottom of each corner post to expose the holes used to attach the economizer assembly...

Page 9: ...ver 2 Remove block off 8 from return air opening Figure 17 Remove block off 3 Remove Trane connecting rods 4 from the unit Figure 18 Remove connecting rods 4 Switch return air damper assembly 3 from T...

Page 10: ...inlet Figure 22 Attach block off plate 8 Attach Filter and Rear access panels Mist Eliminator Servicing 1 Remove screws from end panel that secure it to the unit and economizer 2 Set end panel aside 3...

Page 11: ...atures See Table 1 for potentiometer settings The selection is made on the ECA Reference Enthalpy Settings Economizer enthalpy changeover is field selectable to 5 points See Table 1 for potentiometer...

Page 12: ...ations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residen...

Reviews: