Model: 

BAYECON203AA/AB/AC

BAYECON204AA/AB/AC

BAYRLAY006A

Horizontal Economizer & Rain Hood

Used with:

*WCZ, YCZ, DCZ - 024, 036

*WCZ, YCZ, DCZ - 048, 060

(Required with *WCZ & *DCZ models)

General

The economizer is a multi-damper design. It inserts into the 

return air stream and is connected to the unit low voltage 

supply through wire leads. The economizer is fully accessible 

through an access panel.

Use care when inserting the economizer in the return 

air compartment, to prevent damaging the foil faced 

insulation.

18-HE84D1-1D-EN

Installer’s Guide

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

WARNING:

 

HAZARDOUS VOLTAGE - DISCONNECT POWER BEFORE SERVICING

IMPORTANT: 

After the Economizer installation you must 

install an air filter rack ordered separately. Use:

      

BAYFLTR101B for *WCZ, YCZ, DCZ - 024, 036

BAYFLTR201B for *WCZ, YCZ, DCZ - 048, 060
When the economizer is installed in *WCZ & *DCZ models, 

relay accessory kit BAYRLAY006A is required. Refer to 

Figure 7 on page 7 to make your relay wiring connections 

in the Control Box.

Inspect Contents

Y

ou must report damage and make claims to the transpor

-

tation company immediately. Report missing parts to your 

supplier immediately and replace with authorized parts 

only.

Identify Economizer Kit Contents

Refer to Figure 2 on page 3 to identify the kit contents.

ELECTRIC SHOCK HAZARD

Open and lock out all unit disconnects prior to ac-

cessory installation or unit maintenance, to prevent 

injury or death from electrical shock or contact with 

moving parts.

SAFETY HAZARD

Do not remove end covers from Economizer actua-

tor; the  spring-return assembly may release and 

cause personal injury.

CAUTION

IMPORTANT — 

This Document is 

customer property

 and 

is to remain with this unit.  Please return to service informa-

tion pack upon completion of work.

Install Economizer Kit

1.

  

Remove Power

     

D

isconnect and verify that power is off.

2.  

Remove Access Panels

     

Remove these three (3) access panels    

     (see Figure 1, page 3):

     • Control/Heat access panel

     • Blower access panel

     • Coil access panel

3.  

BAYRLAY006A Installation (Required for 

*WCZ & *DCZ units only, for *YCZ units 

skip to step 4)

1.  Remove wire harness that came attached to the 

BAYECON Logic Module being installed.

  IMPORTANT: 

Do NOT remove the resistors from the 

Logic Module. Also, Do NOT remove the YL & YL/BK 

wires connected to SO and + on the Logic Module

2.

  

 Locate the ICMC Board in the upper left hand corner 

of the unit control box and the DFC board in the upper 

center of the unit control box. See Figure 5, page 5.

3.

  

 

Using the existing holes in the back of the unit control 

box, mount the relay bracket assembly using the 2 

screws supplied with the BAYRLAY006A Kit. See 

Figure 5, page 5.

4.

  

Route the BAYRLAY006A wire harness attached to 

the relays to the logic module as shown in Figure 3 on 

page 4.

5.

  

 Connect the BAYRLAY006A to the economizer Logic 

Module and make the field connections as shown in 

Figure 7 on page 7.

Summary of Contents for BAYECON203AA

Page 1: ...lock out all unit disconnects prior to ac cessory installation or unit maintenance to prevent injury or death from electrical shock or contact with moving parts SAFETY HAZARD Do not remove end covers...

Page 2: ...cure all wires with wire ties so that there is no interference with any moving parts in the unit 11 In the Control Box complete the wiring connections per the appropriate wiring diagram on pages 6 and...

Page 3: ...7 8 15 11 16 11 11 16 15 BAYECON204AA AB AC 26 22 21 32 19 17 11 16 14 11 16 21 3 8 Economizer Logic Module Logic Module not shown located inside economizer Mixed Air Sensor Duct Rain Hood Mist Elimi...

Page 4: ...ting Location of Mixed Air Sensor 1 From economizer assembly pass wire harness through coil Grommet See View A 2 Continue routing behind compressor compartment and into Blower Compartment Coil Grommet...

Page 5: ...5 INSTALLER S GUIDE Figure 5 Mount BAYRLAY006A ICMC Board Relays DFC...

Page 6: ...Figure 6 YCZ Economizer Connection Diagram IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a Ho...

Page 7: ...gure 7 WCZ DCZ Economizer Connection Diagram IMPORTANT Retain this wiring diagram please return this document to service information pack upon completion of work Wiring Diagram for Economizer Using a...

Page 8: ...A A ACCESSORY MODELS BAYECON10 3AA AB AC BAYECON10 4AA AB AC BAYECON20 3AA AB AC BAYECON20 4AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon c...

Page 9: ...A A ACCESSORY MODELS BAYECON103AA AB AC BAYECON104AA AB AC BAYECON203AA AB AC BAYECON204AA AB AC IMPORTANT Retain this wiring diagram please return this document to service information pack upon compl...

Page 10: ...representative MODEL DRIVE MOTOR OPEN DRIVE MOTOR CLOSED SPRING RETURN M7415 Power to TR and TR1 jumper T and T1 Disconnect jumper at T or T1 and disconnect P or P1 if connected Disconnect power at TR...

Page 11: ...a DC multimeter between terminal So of the W7459A and terminal S of the enthalpy sensor See Fig 11 positive meter lead to terminal S of the enthalpy sensor Multimeter indication is between 3 and 25 m...

Page 12: ...47 3 507 57 2 14 5 000 3 420 59 0 15 4 767 3 373 60 8 16 4 545 3 328 62 6 17 4 335 3 283 64 4 18 4 136 3 239 66 2 19 3 948 3 180 68 0 20 3 769 3 157 69 8 21 3 599 3 118 71 6 22 3 437 3 080 73 4 23 3 2...

Page 13: ...Fan contacts are open Disconnect devices at P and P1 Jumper P to P1 defaults to on board MIN POS potentiometer Place 5 6K ohm resistor across T and T1 Blue sleeve provides input to economizer that the...

Page 14: ...t 45 degrees open Adjust DCV MAX towards CW Motor will move to position set by DCV MAX pot Adjust DCV MAX to fully CCW Motor will drive closed Reconnect jumper to N terminal Adjust DCV MAX and MIN POS...

Page 15: ...plications For more information please visit www trane com or www americanstandardair com The manufacturer has a policy of continuous data improvement and it reserves the right to change design and sp...

Reviews: