Page 10
INSTALLER'S GUIDE
STEP 9
-
Connect low voltage wiring.
STEP 10 -
Place Wiring Diagram.
1. Attach the wiring diagram, included in the documentation
packet, to the back of the heater compartment panel.
Close up with other wires not shown
STEP
11
-
Replace Heater compartment panel on air
handler.
Resistor
Assembly
Low
Voltage
Harness
Electric
Heat Control
Harness
Heater
Resistance
Harness
1. Connect the 4-pin low voltage harness to Electric Heat
Control as shown.
2. If installing in TAMX Air Handler models, connect the 2-pin
resistor ID assembly (tie wrapped to Electric Heat Controls
harness) into the 2-pin heater ID harness as shown.
3. All other Air Handler models, the 2-pin resistor ID assembly
is not used and should be left disconnected.