WSHP-SVX01Y-EN
77
Table
48.
Electrical
data
standard
static
motors
(0.5
to
25
tons),
single
speed
blower
motor
(6
to
25
tons)
(continued)
Model
No.
Volts
Total
Unit
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No.
of
Comp.
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motor
Num
Mini-
mum
Circuit
Ampaci-
ty
Maxi-
mum
Overcur-
rent
Protec-
tive
Device
Electric
Heat
kW
(a)
Electric
Heat
Amps
(a)
GEVE300
460/60/3
46.9
18.6
125
2
9.70
7
1/2
1
51.55
70
—
—
GEVE300
575/60/3
37.4
14.7
100
2
8.00
7
1/2
1
41.08
50
—
—
GEVE300
208/60/3
122.2
48.1
245
2
26.00
10
1
134.23
175
—
—
GEVE300
230/60/3
121.2
48.1
245
2
25.00
10
1
133.23
175
—
—
GEVE300
460/60/3
49.7
18.6
125
2
12.50
10
1
54.35
70
—
—
GEVE300
575/60/3
39.4
14.7
100
2
10.00
10
1
43.08
50
—
—
GEVE300
208/60/3
133.2
48.1
245
2
37.00
15
1
145.23
175
—
—
GEVE300
230/60/3
132.2
48.1
245
2
36.00
15
1
144.23
175
—
—
GEVE300
460/60/3
55.2
18.6
125
2
18.00
15
1
59.85
70
—
—
GEVE300
575/60/3
43.5
14.7
100
2
14.10
15
1
47.18
60
—
—