Troubleshooting
WSHP-SVX11E-EN
33
Insufficient capacity
X
X
Dirty filter
Replace/clean
X
X
Blower RPM too low
Correct
X
X
Loss of conditioned air due to leaks in
ductwork
Repair leaks
X
Introduction of excessively hot return-air
Correct
X
Introduction of excessively cold return-air
Correct
X
X
Low on refrigerant charge
Locate leak, repair and recharge by
weight (not by superheat)
X
X
Restricted thermal expansion valve
Replace
X
X
Defective reversing valve
See WSHP-IOM-# for touch test chart
X
X
Thermostat improperly located
Relocate
X
X
Unit undersized
Recalculate heat gains/losses
X
X
Inadequate water flow
Increase GPM
X
X
Scaling in heat exchanger
Clean or replace
X
Water too hot
Decrease temperature
X
Water too cold
Increase temperature
X
X
Filter drier blocked
Replace
X
X
Defective reversing valve
Check or replace
High pressure switch open
X
Inadequate GPM
Increase water flow to unit
X
Water too hot
Decrease temperature
X
Inadequate air flow
Check, clean blower and coil
X
Dirty filter
Clean/replace
X
X
Overcharged with refrigerant
Decrease charge
X
X
Defective pressure switch
Check or replace
High head pressure
X
Trash in heat exchanger
Backflush
X
Low water flow
Increase GPM
X
X
Overcharge of refrigerant
Decrease charge
X
X
Non-condensable in system
Evacuate and recharge by weight
X
X
Water too hot
Decrease temperature
X
Dirty filter
Clean / replace
X
Inadequate air flow
Check, clean blower and coil
Low suction pressure
X
X
Undercharged
Locate leak, repair and recharge
X
X
Restricted thermal expansion valve
Repair / replace
X
Inadequate air flow
Check, clean blower and coil
X
Dirty filter
Clean/replace
X
Inadequate GPM
Increase GPM
Low pressure switch open
X
Inadequate GPM
Increase GPM
X
Water too cold
Increase temperature
X
Inadequate air flow
Increase CFM
X
Dirty filter
Clean/replace
X
X
Undercharged with refrigerant
Increase charge
X
X
Defective pressure switch
Replace
X
X
Heat transfer fluid too cold
Raise water temperature
Table 11. Troubleshooting table (continued)
Problem
Heating Cooling
Cause
Correction
Summary of Contents for Axiom GECE 006
Page 34: ...34 WSHP SVX11E EN Wiring Diagrams Figure 15 Deluxe 24V controls...
Page 35: ...Figure 16 Tracer ZN524 Wiring Diagrams WSHP SVX11E EN 35...
Page 36: ...Figure 17 Tracer UC400 B 208V 60 Hz 1pH Wiring Diagrams 36 WSHP SVX11E EN...
Page 37: ...Figure 18 Tracer UC400 B 208V 60 Hz 1pH with hot gas reheat Wiring Diagrams WSHP SVX11E EN 37...
Page 39: ......