Electrical Data
24
WSHP-SVX11E-EN
GEC015 220-240/50/1
8.6
7.9
28.0
1
11.1
0.70
1/12
1
10.6
15
0.0
0.0
GEC015 220-240/50/1 13.2
7.9
28.0
1
11.1
0.70
1/6
1
16.5
20
3.0
12.5
GEC015 220-240/50/1 17.4
7.9
28.0
1
11.1
0.70
1/6
1
21.7
25
4.0
16.67
GEC015
265/60/1
7.1
6.4
30.0
1
9.0
0.70
1/6
1
8.7
15
0.0
0.0
GEC015
265/60/1
11
6.4
30.0
1
9.0
0.70
1/12
1
13.8
15
2.74
10.34
GEC015
265/60/1
14.7
6.4
30.0
1
9.0
0.70
1/12
1
18.3
20
3.7
13.96
GEC018
208/60/1
10.0
9.0
30.0
1
12.6
1.00
1/6
1
12.3
20
0.0
0.0
GEC018
208/60/1
11.8
9.0
30.0
1
12.6
1.00
1/6
1
14.8
20
2.25
10.82
GEC018
208/60/1
15.4
9.0
30.0
1
12.6
1.00
1/6
1
19.3
20
3.0
14.42
GEC018
230/60/1
9.9
9.0
30.0
1
12.6
0.90
1/6
1
12.2
20
0.0
0.0
GEC018
230/60/1
12.9
9.0
30.0
1
12.6
0.90
1/6
1
16.1
20
2.76
12.0
GEC018
230/60/1
17
9.0
30.0
1
12.6
0.90
1/6
1
21.2
25
3.7
16.09
GEC018
265/60/1
8.5
7.8
30.0
1
10.9
0.70
1/6
1
10.5
15
0.0
0.0
GEC018
265/60/1
11
7.8
30.0
1
10.9
0.70
1/6
1
13.8
15
2.74
10.34
GEC018
265/60/1
14.7
7.8
30.0
1
10.9
0.70
1/6
1
18.3
20
3.7
13.96
Table 3.
Console VA
Designator
Controls
Deluxe with
Reheat (75 VA)
Deluxe with
Electric Heat
(75 VA)
UC400-B
(75 VA)
ZN524
(75 VA)
x = ON
(a)
Controller
6.0
6.0
12.5
19.5
1K1
Compressor Contactor
5.5
5.5
5.5
5.5
X
1K2
Fan Relay
9.5
9.5
9.5
9.5
2L1
Reversing Valve
5.0
5.0
5.0
5.0
X
2L2
Reheat Valve
5.0
—
—
—
5B3
Damper Actuator
—
—
—
—
1K10
Electric Heat Contactor
—
5.5
Optional
(b)
Optional
(b)
(b) Electric heat is optional with ZN524 and UC400-B controller. If electric heat is selected, add 5.5 VA.
X
IU3
Boilerless Control Board
—
3.0
N/A
N/A
X
Field Supplied Solenoid
7.0
7.0
7.0
7.0
X
1K6, 1K7
Reheat Relays(2)
12.5
—
Optional
(c)
Optional
(c)
(c) HGR is optional with the ZN524 and UC400-B controller. If HGR is selected, add 12.5 VA.
X
1K8
Reheat Low Speed Relay
—
—
N/A
N/A
X
1U1
Thermostat-Unit Mounted
6.0
6.0
N/A
N/A
X
Timer Delay Relay
N/A
N/A
N/A
N/A
X
Total VA
56.5
47.5
39.5
46.5
61.40
Extra VA
18.5
27.5
32.5
32.5
13.60
Note:
Listed VA values are for reference only. Actual values may vary with operating conditions.
Table 2.
Electrical data (0.5 to 1.5 tons) (continued)
Model
Volts
Total
Unit
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motors
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
(a) Consider unit options and concurrent loads.
Summary of Contents for Axiom GECE 006
Page 34: ...34 WSHP SVX11E EN Wiring Diagrams Figure 15 Deluxe 24V controls...
Page 35: ...Figure 16 Tracer ZN524 Wiring Diagrams WSHP SVX11E EN 35...
Page 36: ...Figure 17 Tracer UC400 B 208V 60 Hz 1pH Wiring Diagrams 36 WSHP SVX11E EN...
Page 37: ...Figure 18 Tracer UC400 B 208V 60 Hz 1pH with hot gas reheat Wiring Diagrams WSHP SVX11E EN 37...
Page 39: ......