RT-SVX060A-GB

4

4

UNT-PRC002-GB

Technical Data

FWD

08

12

20

30

45

Power supply

(V/Ph/Hz)

230/1/50

Capacities
Cooling capacity on water (1)

(kW)

5,2

8,3

15

18,8

30,1

Heating capacity on water (2)

(kW)

6,3

11,9

18,9

20,9

38,2

Fan motor

(type)

2 x direct drive centrifugal

Fan power input (3)

(kW)

0,23

0,46

0,65

1,04

1,51

Current amps (3)

(A)

1,1

2,2

3,1

4,7

5,5

Start-up amps

(A)

3,2

5,5

9,3

14,1

16,5

Air flow
minimum

(m

3

/h)

490

980

1400

1800

2700

nominal

(m

3

/h)

820

1650

2300

3000

4500

maximum

(m

3

/h)

980

1970

2600

3600

5400

Main coil
Water entering/leaving connections

(type)

ISO R7 rotating female

(Dia)

3/4"

3/4"

1 1/2"

1 1/2"

1 1/2"

Electric heater (accessory for blower only)
Electric power supply

(V/Ph/Hz)

230/1/50

230/1/50 or 400/3/50

400/3/50

400/3/50

400/3/50

Heating capacity

(kW)

2/4

8

10

12

12

Hot water coil (accessory for blower only)
Heating capacity (4)

(kW)

6,3

12

17,4

22,4

34,5

G2 filter (filter box accessory)
Quantity

2

2

2

2

2

Dimensions ( LxWxth)

(mm)

386x221x8

486x271x8

586x321x8

586*421*8

586*621*8

G4 filter (filter box accessory)
Quantity

-

2

2

2

2

Dimensions ( LxWxth)

(mm)

-

486x264x48

586x314x48

586*414*48

586*614*48

Condensate pump (accessory)

(type)

Centrifugal

Water flow - lift height

(l/h - mm)

24 - 500

Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)

(dB(A))

36/40/43

38/41/44

46/50/53

47/52/57

47/52/58

Sound power level (5)

(dB(A))

46/50/53

48/51/54

56/60/63

57/62/67

57/62/68

Unit dimensions
Width x Depth

(mm)

890 x 600

1090 x 710

1290 x 820

1290 x 970

1290 x 1090

Height

(mm)

250

300

350

450

650

Shipped unit dimensions
Width x Depth

(mm)

933 x 644

1133 x 754

1333 x 864

1333 x 1008

1333*1133

Height

(mm)

260

310

360

460

660

Weight

(kg)

32

46

61

76

118

Colour

galvanised steel

Recommended fuse size
Unit alone (aM/gI)

(A)

8/16

8/16

8/16

8/25

8/25

Unit with electric heater (gI)

(A)

16 (2kW),25 (4kW)

40 (230V),3*16 (400V)

3*20

3*25

3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

General information

Foreword

These instructions are given as a guide to good practice 
in the installation, start-up, operation, and maintenance 
by the user, of Trane Airfinity rooftop units. They do 
not contain full service procedures necessary for the 
continued successful operation of this equipment. The 
services of a qualified technician should be employed 
through the medium of a maintenance contract with 
a reputable service company. Read this manual 
thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated, 
charged and tested in accordance with factory standard 
before shipment.

Warnings and Cautions

Warnings and Cautions appear at appropriate sections 
throughout this manual. Your personal safety and the 
proper operation of this machine require that you follow 
them carefully. The constructor assumes no liability 
for installations or servicing performed by unqualified 
personnel.

WARNING!

 Indicates a potentially hazardous situation 

which, if not avoided, could result in death or serious 
injury.

CAUTION!

 Indicates a potentially hazardous situation 

which, if not avoided, may result in minor or moderate 
injury. It may also be used to alert against unsafe 
practices or for equipment or property-damage-only 
accidents.

Safety Recommendations

To avoid death, injury, equipment or property damage, 
the following recommendations should be observed 
during maintenance and service visits:
1. The maximum allowable pressures for system leak 
testing on low and high pressure side are given in the 
chapter “Installation”. Insure to do note exceed test 
pressure by using appropriate device.
2. Disconnect the main power supply before any 
servicing on the unit.
3. Service work on the refrigeration system and the 
electrical system should be carried out only by qualified 
and experienced personnel.
4. To avoid any risk, it is recommended to place the unit 
on an area with restricted access.

Reception

On arrival, inspect the unit before signing the delivery 
note. Specify any visible damage on the delivery note, 
and send a registered letter of protest to the last carrier 
of the goods within 7 days of delivery.
Notify the local TRANE sales office at the same time. The 
delivery note must be clearly signed and countersigned 
by the driver.
Any concealed damage shall be notified by a registered 
letter of protest to the last carrier of the goods within 
7 days of delivery. Notify the local TRANE sales office at 
the same time.
Important notice: No shipping claims will be accepted 
by TRANE if the above mentioned procedure is not 
respected. For more information, refer to the general 
sales conditions of your local TRANE sales office.
Note: Unit inspection in France. Delay to send registered 
letter in case of visible and concealed damage is only 
72 hours.

Loose Parts Inventory

Check all the accessories and loose parts that are 
shipped with the unit against the shipping list. Included 
in these items will be the all kind of sensors, thermostat 
and electrical diagrams, service literature, which are 
placed inside the control panel and/or indoor section for 
shipment.

Warranty

Warranty is based on the general terms and conditions 
of the manufacturer. The warranty is void if the 
equipment is repaired or modified without the written 
approval of the manufacturer, if the operating limits are 
exceeded or if the control system or the electrical wiring 
is modified. Damage due to misuse, lack of maintenance 
or failure to comply with the manufacturer’s instructions 
or recommendations is not covered by the warranty 
obligation. If the user does not conform to the rules of 
this manual, it may entail cancellation of warranty and 
liabilities by the manufacturer.

Refrigerant

Consult the addendum to Manuals for units with 
refrigerant, for conformity to the Pressure Equipment 
Directive (PED) 97/23/EC and Machinery Directive 
2006/42/EC.

Summary of Contents for Airfinity XL IC

Page 1: ...RT SVX060A GB Installation Operation Maintenance Original instructions Airfinity XL Models IH IC Large Packaged Rooftop Units 140 to 220 kW...

Page 2: ...460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 2...

Page 3: ...57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 6...

Page 4: ...in accordance with factory standard before shipment Warnings and Cautions Warnings and Cautions appear at appropriate sections throughout this manual Your personal safety and the proper operation of...

Page 5: ...izes the possibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and...

Page 6: ...is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water tempera...

Page 7: ...62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20...

Page 8: ...bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IC140 IC150 IC170 IC190 IC220 Cooling Mode Net Cooling Capacity 1 kW 140...

Page 9: ...t with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x300 Disconnect swich unit with other...

Page 10: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Page 11: ...s Extra Lenght Extra weight 4 Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner H...

Page 12: ...ies Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IH140 IH150 IH170 IH190 IH220 Cooling Mode Net Cooling Capacity 1 kW 139 8 153 6 162 7 187 1 201...

Page 13: ...95 95 95 150 150 Disconnect swich unit with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x...

Page 14: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Page 15: ...s Extra Lenght Extra weight Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner Hig...

Page 16: ...ilable for FWD30 and FWD45 Sound level L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit d...

Page 17: ...ion The installation must conform to all local standards and regulations Reception of Units Unit Handling The unit is supplied on wooden blocks It is recommended to check the machine s condition upon...

Page 18: ...min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installation Instructions for the roofcurb assembly and installation In order to insure watertighness of the roofcurb assembly it is i...

Page 19: ...63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installatio...

Page 20: ...tering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the...

Page 21: ...64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installation Filter installation Access to the filter cells is done via the filter access door Filter sup...

Page 22: ...on The airflow measurement option when selected is associated with an air differential pressure sensor which measures the pressure difference before the inlet nozzle and inside the inlet nozzle Unit a...

Page 23: ...212 General Electrical Recommendations Electrical Parts When reviewing this manual keep in mind All field installed wiring must be in accordance with local regulations CE directives and guidelines Be...

Page 24: ...outing inside control panel should be made case by case by installer WARNING Ground Wire All field installed wiring must be completed by qualified personnel All field installed wiring must comply with...

Page 25: ...51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69...

Page 26: ...51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 64...

Page 27: ...D 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit...

Page 28: ...47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shi...

Page 29: ...57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequen...

Page 30: ...t dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008...

Page 31: ...46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 100...

Page 32: ...L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 10...

Page 33: ...speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65...

Page 34: ...ture 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat excha...

Page 35: ...inimize the overpressure in the building caused by the introduction of fresh air This option is typically used when the fresh air intake needed is between 40 to 50 of the nominal air flow or when the...

Page 36: ...he measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coi...

Page 37: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Electric Heater Electric heater are fitted on the supply fan discharge Heaters have two heatin...

Page 38: ...galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving te...

Page 39: ...diagram supplied with the unit for details The resolution of analog outputs reaches 10 ppm CO2 The information is then sent to the controller CH536 to control the opening position of the fresh air da...

Page 40: ...eaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air f...

Page 41: ...gn occupancy of the zone Occupied standby setpoint 0 6L s per m2 ASHRAE62 1 x Surface Occupied setpoint 4 72L s per person ASHRAE62 1 x DesignOccupants Occupied standby setpoint 2 Occupancy based vent...

Page 42: ...ring diagrams and options shipped with the unit Unit is level with sufficient clearance all round Duct network is correctly sized according to the unit configuration insulated and water tight Condensa...

Page 43: ...s required to Check the gas category Check the gas intake pressure on the gas valve Perform the combustion analysis to verify that the level of flue gases corresponds to the data contained in general...

Page 44: ...ess panels to service the unit Failure to disconnect power before attempting any servicing can result in severe injury or death Air filters It is very important for the central duct system air filters...

Page 45: ...1 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 5...

Page 46: ...ment pre commission Configure unit control module Calibrate controls Check operational set points and performance Check operation of all safety devices Megger the motor compressor windings Check unit...

Page 47: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Oil analysis Trane Oil Analysis is a predictive tool used to detect minor issues before they b...

Page 48: ...e comfortable and energy efficient environments Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com...

Reviews: