RT-SVX060A-GB
19
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Installation
Unit overall view
Figure 4 - Outdoor section
Figure 5 - Indoor section
OD Fans:
Diameter : 800 mm
Standard : AC Fans
Low ambient : EC Fans (Optional)
Electronic Expansion Valve
(EEXV)
Option Plastic louver
OD Coils
Fins and Tubes coil
High corrosion resistance Epoxy coating fins (Optional)
High efficiency scroll
compressors in tandem
Delivers high performance in
part load thanks to capacity
modulation. Eco Design
compliant.
Dual refrigeration circuit
On top of improving capacity
modulation and increasing part
load efficiency, having two
circuits also maximizes reliability
by providing system redundancy.
Centralized control panel
for easy access and service.
Remote service terminal
provided as an option.
High Quality Air Filtration
Two rails for wide range of
filtration up to F9.
EC Plug Fan
Rail system for easy
access and maintenance
Double Skin panel
Double wall and thick 50 mm glass wool
insulation provided as standard with all
units, for higher indoor air quality.
Fresh air hood
Factory installed
Slopped and removable
drain pan for easy cleaning
Optional Auxiliary heat
electrical heater or hot
water coil
Unit nameplate
Economizer with intelligent
control Standard with every
Airfinity XL™ unit.