RT-SVX060A-GB

39

11

UNT-PRC002-GB

Sound power levels

Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

55

50

42

37

37

31

30

46

FWD 08

2

57

54

47

40

30

38

40

50

3

58

57

50

42

32

40

43

53

1

57

51

45

42

34

33

28

48

FWD 10

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

57

51

45

42

34

33

28

48

FWD 12

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

56

62

50

48

39

38

36

56

FWD 14

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

1

57

63

51

49

40

39

37

57

FWD 20

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

56

55

55

53

46

45

42

57

FWD 08

2

63

62

60

60

53

53

53

64

3

66

65

63

62

56

55

57

67

1

62

58

55

58

51

48

44

61

FWD 10

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

62

58

55

58

51

48

44

61

FWD 12

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

66

65

65

65

57

50

46

68

FWD 14

2

73

72

69

71

64

59

57

74

3

78

76

73

75

69

64

63

78

1

68

72

64

64

56

52

50

69

FWD 20

2

76

76

68

71

65

61

61

75

3

78

79

71

74

69

66

66

78

Zone temperature source

The zone temperature source are summarized in the 
table below by hierarchy order.

Source

Condition

1. BAS

BAS command enabled 

Value in validity range [-10°C; +50°C]

2. Zone Temp Sensor

Ad-hoc Config enabled

 

Value in validity range [-10°C; +50°C]

3. Zone Temp THS04

THS04 installed 

Ad-hoc Config enabled

 

Value in validity range [-10°C; +50°C]

4. Conventional Thermostat

Ad-hoc config enabled

4. Return Air Temp

Value in validity range [-10°C; +50°C]

CO2 sensor

CO2 sensor can be either in air return duct or wall 

mounted. It maintains a CO2 concentration below a 

preset value to ensure acceptable comfort.
Controls the opening of the fresh air damper of the 
economizer. The outside air damper will modulate in 
order to maintain the CO2 concentration below the 

setpoint.
To open damper it should combine the amount of 
desired fresh air and the free cooling mode to modulate 
from 0 to 100% maximum opening of the dampers. 
It is possible to preset a minimum opening during 
commissioning.
The CO2 sensor is set for 0-10V analog outputs and 

provide sensing of carbone dioxide over a range of 
0-2000 ppm. The sensor requires a 24 VDC power 
supply. Consult wiring diagram supplied with the unit 
for details.
The resolution of analog outputs reaches 10 ppm CO2. 

The information is then sent to the controller CH536 to 
control the opening position of the fresh air damper.
Avoid locating the duct sensor on surfaces with an 
uncooled, unheated area behind them or in “dead” 
spot behind doors or in corners. The CO2 wall mounted 

sensor should be placed on a flat surface, 1.4 m from 
the floor in an area of the room where there is free air 
circulation. 

CO2 sensor maintenance

This CO2 sensor has excellent stability and requires no 

maintenance. In most environments the recommended 
calibration interval is five years. A trained service 
technician can use a portable CO2 meter to certify 

sensor calibration. If, when checking the sensor, the 
reading differs too much from the reference value, the 
sensor can be recalibrated in the field. A calibration kit, 
software, and calibration gases are required. If certified 
accuracy is required, the sensor must be calibrated 
against accurate and traceable calibration gases in a 
laboratory. Consult Trane BAS for further details.

Fire thermostat

U12 is the dedicated I/O. Optional fire thermostat should 
be configured if present according to wiring diagram.

Clogged filter detector

This device is mounted in the filter section. The sensor 
measures the difference in pressure before and after 
the filter section. The information is sent to the optional 
service terminal or the BMS.

Smoke Detector

Installation:

 This device is used to detect smoke in the 

air stream. Detector is delivered by trane and must 
be installed by the customer to comply with local 
regulation. The detector must be connected to the 
central panel according the wiring diagram.

Operation:

 When smoke is detected, it shuts off the unit, 

and an alarm is activated in the controller to inform the 
user through the local or remote control. 

Other accessories available

-  DTS : duct mounted wired temperature sensor
The duct mounted sensor - mainly for unit with auxliary 
heat - must be installed away of any duct singularities 
and generally at 2 m of any duct elbow or duct inside 
element both upstream and downstream.
-  TZS01 : wall mounted wired temperature sensor
-  THS04 : wall mounted thermostat
Refer to separate documentation for more information.

Alarm  and Warnings

Alarms stop the unit or reduce the heating/cooling 
capacity. Alarm can be either manual reset (requires 
human intervention to re-start the unit) or automatic 
reset.
Warning run the unit in fall-back mode.
Example : if outdoor air humidity sensor is not working, 
the economizer runs in dry-bulb mode.
Events are accessible through optional local service 
terminal which display the current events and 
display history of past events (up to 99 alarms 
and 99 warnings). 

Controls

Summary of Contents for Airfinity XL IC

Page 1: ...RT SVX060A GB Installation Operation Maintenance Original instructions Airfinity XL Models IH IC Large Packaged Rooftop Units 140 to 220 kW...

Page 2: ...460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 2...

Page 3: ...57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 6...

Page 4: ...in accordance with factory standard before shipment Warnings and Cautions Warnings and Cautions appear at appropriate sections throughout this manual Your personal safety and the proper operation of...

Page 5: ...izes the possibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and...

Page 6: ...is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water tempera...

Page 7: ...62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20...

Page 8: ...bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IC140 IC150 IC170 IC190 IC220 Cooling Mode Net Cooling Capacity 1 kW 140...

Page 9: ...t with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x300 Disconnect swich unit with other...

Page 10: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Page 11: ...s Extra Lenght Extra weight 4 Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner H...

Page 12: ...ies Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars IH140 IH150 IH170 IH190 IH220 Cooling Mode Net Cooling Capacity 1 kW 139 8 153 6 162 7 187 1 201...

Page 13: ...95 95 95 150 150 Disconnect swich unit with electrical heater option Sirco 500A Sirco 500A Sirco 500A Sirco 630A Sirco 630A Cross section max unit with electrical heater option mm 240 240 240 2x300 2x...

Page 14: ...ing limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bar...

Page 15: ...s Extra Lenght Extra weight Hot Water Coil kg 60 60 60 60 60 Electric Heater kg 26 26 26 26 26 Gas Burner low Heat kg 382 382 382 382 382 Gas Burner Standard Heat kg 434 434 434 434 434 Gas Burner Hig...

Page 16: ...ilable for FWD30 and FWD45 Sound level L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit d...

Page 17: ...ion The installation must conform to all local standards and regulations Reception of Units Unit Handling The unit is supplied on wooden blocks It is recommended to check the machine s condition upon...

Page 18: ...min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installation Instructions for the roofcurb assembly and installation In order to insure watertighness of the roofcurb assembly it is i...

Page 19: ...63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installatio...

Page 20: ...tering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the...

Page 21: ...64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Installation Filter installation Access to the filter cells is done via the filter access door Filter sup...

Page 22: ...on The airflow measurement option when selected is associated with an air differential pressure sensor which measures the pressure difference before the inlet nozzle and inside the inlet nozzle Unit a...

Page 23: ...212 General Electrical Recommendations Electrical Parts When reviewing this manual keep in mind All field installed wiring must be in accordance with local regulations CE directives and guidelines Be...

Page 24: ...outing inside control panel should be made case by case by installer WARNING Ground Wire All field installed wiring must be completed by qualified personnel All field installed wiring must comply with...

Page 25: ...51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69...

Page 26: ...51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 64...

Page 27: ...D 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit...

Page 28: ...47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shi...

Page 29: ...57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequen...

Page 30: ...t dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008...

Page 31: ...46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 100...

Page 32: ...L M H speed Sound pressure level 5 dB A 36 40 43 38 41 44 46 50 53 47 52 57 47 52 58 Sound power level 5 dB A 46 50 53 48 51 54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 10...

Page 33: ...speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65...

Page 34: ...ture 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat excha...

Page 35: ...inimize the overpressure in the building caused by the introduction of fresh air This option is typically used when the fresh air intake needed is between 40 to 50 of the nominal air flow or when the...

Page 36: ...he measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coi...

Page 37: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Electric Heater Electric heater are fitted on the supply fan discharge Heaters have two heatin...

Page 38: ...galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving te...

Page 39: ...diagram supplied with the unit for details The resolution of analog outputs reaches 10 ppm CO2 The information is then sent to the controller CH536 to control the opening position of the fresh air da...

Page 40: ...eaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air f...

Page 41: ...gn occupancy of the zone Occupied standby setpoint 0 6L s per m2 ASHRAE62 1 x Surface Occupied setpoint 4 72L s per person ASHRAE62 1 x DesignOccupants Occupied standby setpoint 2 Occupancy based vent...

Page 42: ...ring diagrams and options shipped with the unit Unit is level with sufficient clearance all round Duct network is correctly sized according to the unit configuration insulated and water tight Condensa...

Page 43: ...s required to Check the gas category Check the gas intake pressure on the gas valve Perform the combustion analysis to verify that the level of flue gases corresponds to the data contained in general...

Page 44: ...ess panels to service the unit Failure to disconnect power before attempting any servicing can result in severe injury or death Air filters It is very important for the central duct system air filters...

Page 45: ...1 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 5...

Page 46: ...ment pre commission Configure unit control module Calibrate controls Check operational set points and performance Check operation of all safety devices Megger the motor compressor windings Check unit...

Page 47: ...76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Oil analysis Trane Oil Analysis is a predictive tool used to detect minor issues before they b...

Page 48: ...e comfortable and energy efficient environments Trane offers a broad portfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com...

Reviews: