48
BAS-SVX40K-EN
WCS-SO, -SCO
2
, -SB/R Display Sequence
Note:
WCS-SO/SCO
2
sensors do not have set point, timed override, fan mode or system mode. If you
need these features you will have to add a WCS-SD display sensor.
Use the NEXT and Address (ADDR) buttons to move forward or back through the sensor display
sequence. Use the UP and DOWN arrows to toggle between units and increase or decrease values in
their given increments.
Pressing the NEXT button repeatedly displays the following conditions in this order:
1. Blank Screen or Errors
2. CO
2
(optional)
3. Temperature
4. Temperature offset
5. Humidity (optional)
6. Humidity Offset (optional)
7. Motion Test (optional)
8. Back to top
Note:
Pressing the ADDR button will act like a BACK button, so you can go through the options in
reverse.
Blank Screen or Errors
This screen is blank if there are no errors present. If an error is present, it will be displayed until the error
condition is resolved, then the screen will be blank.
CO
2
Displays the CO
2
level in parts per million (ppm).
Note:
It takes eight (8) days for a newly installed CO
2
sensor to acclimate to the environment and
complete a calibration cycle.