36
BAS-SVX40K-EN
Figure 23.
Removing the sensor cover
2. Press and hold the Address button located on the back of the sensor until two numbers appear at
the top of the display, with the left number flashing. At the bottom of the display, the letters
g n
appear.
Figure 24.
Pressing the address button
The
g
corresponds to the Tracer SC group (GRP) and the
n
corresponds to the network (NET).
Notes:
•
Use the up/down arrow buttons to change the value of the number that is flashing.
•
Use the left/right arrow buttons to scroll to the other address settings.
•
If no button is pressed, the display will return to the normal screen after several seconds.
3. Press the up/down arrow buttons on the front of the sensor to set the left number to match the
corresponding group (GRP).
4. Press the right arrow button to make the right number flash.