![Trane Air-Fi WCS-SB Installation, Operation And Maintenance Manual Download Page 45](http://html1.mh-extra.com/html/trane/air-fi-wcs-sb/air-fi-wcs-sb_installation-operation-and-maintenance-manual_1148928045.webp)
BAS-SVX40K-EN
45
Figure 34.
Mounting the sensor backplate into sheetrock or plaster
Note:
WCS-SO shown. WCS-SCO
2
and -SB/R similar.
Important:
To comply with FCC and IC regulations, do not mount this sensor within 20cm of any other
radio device including other WCS sensors.
Wiring an External Sensor Probe to WCS-SB/R
An external temperature probe can be used by wiring it into the two position connector at the bottom of
the sensor.
Recommended External Sensor:
Installer supplied. Any sensor or probe that has a 10K Type 2
thermistor.
Note:
This sensor also has an internal space temperature sensor which it will use in the absence of an
external sensor. This allows you to use the wireless sensor as a base model space temperature
sensor. To be clear, you can only use the internal temperature sensor or hook up an external
temperature probe. You cannot use both at the same time.
Wire Size recommendation:
For best results use solid or stranded 22 AWG. However, solid and
stranded 18 to 24 AWG will also work.
Note:
18 AWG will be difficult to remove from the connector.
1. Strip insulation back 5/16 in. (8 to 9 mm). The stripped back section of wire should be straight
without any kinks for best results when inserting into the connector.