AFDG-SVU01L-EN
37
Startup Test Log
Water-Cooled CenTraVac™ Chiller with Tracer® AdaptiView™ Control and
Adjustable Frequency Drive™ (AFD) Starter
Job Name
AFD Serial Number
Job Location
AFD Model Number
Sales Order Number
Ship Date
Chiller Serial Number
Start Date
Chiller Model Number
Starter Date:
Tracer® TU: Service Setpoints View: AFD
Default
Setting
Manufacturer
AFD Control
Auto
Type
Re-Optimization Sensitivity
20%
Vender ID
Model Number
UC800 Starter Type: Remote Mount Non-
Communicating AFD
Tracer® TU: Configuration View: Starter
Trane
Default
Setting
Volts & Hz
Amps
Motor Data:
Restart Inhibit Stop to Start Time
30
Manufacturer
Surge Protection
enable
Type & Frame
Surge Sensitivity
20
Drawing #
Power Loss Reset Time
60
Serial Number
Unit Line Voltage
*
Nameplate Data:
CT Meter Scale
0
RLA
Stop Delay
3
KW
Motor NP RLA
*
Volts & Hz
Voltage Transformer Ratio
20
Prestart Checks
Date Checked
Current Unbalance Trip Point
30
Drive Grounded
Acceleration Time
30
Motor Rotation
Acceleration Shutdown Action
Shutdown
Drive Chassis Grounded
Overload Type
Linear
Control Wiring Tight
Phase Reversal
Enable
Drive Connections are Tight
Contactor Integrity
Disable
Verified Settings
Phase Reversal Grace Period
700
Surge Protection
Enable
Comments:
Momentary Power Loss
2000
Restart Inhibit Stop to Start
30
Surge Sensitivity
20
Power Loss Reset
15
RTD Type
75
*Must be set per sales order variable.
Test Log Date:
Log 1
Log 2
AFD Output Power (KW)
Speed
Frequency
Tracer® TU Field Startup View: AFD
Maximum Frequency
60
Minimum Frequency
38
AFD Surge Capacity Increase
1
Tracer® TU Status View: Motor
Average Line Current
Starter Average Phase Voltage
Starter Load Power Factor
Motor Winding #1 temp
Motor Winding #2 temp
Motor Winding #3 temp