Drive and Cabinet

AFDG-SVU01L-EN

17 

Lifting the Drive

WARNING

Heavy Objects!

Failure to properly lift unit could result in death or 
serious injury. Do not use cables (chains or slings) 
except as shown. Each of the cables (chains or slings) 
used to lift the unit must be capable of supporting the 
entire weight of the unit. Lifting cables (chains or 
slings) may not be of the same length. Adjust as 
necessary for even unit lift. Other lifting arrangements 
may cause equipment or property-only damage.

WARNING

Improper Unit Lift!

Failure to properly lift unit could result in death or 
serious injury or possible equipment or property-only 
damage. Test lift unit approximately 24 inches (61 cm) 
to verify proper center of gravity lift point. To avoid 
dropping of unit, reposition lifting point if unit is not 
level.

Important:

AFDG (remote-mounted) and AFDU (unit-
mounted) have differing lift point locations 
and lifting procedures. For AFDG, refer to 

Figure 6, p. 17

 and 

Table 2, p. 17

; for AFDU, 

refer to 

Figure 7, p. 18

, associated text, and 

Table 3, p. 18

.

Figure 6.

Lift point locations for AFDG (remote-
mounted)

Table 2.

Drive weights for AFDG (remote-mounted)

Voltage

Drive Panel SRRL 

Amp Rating

Frame

Weight (lb)

460/480

169

D3

989

213

1019

268

D4

1121

321

1144

394

1187

480

E2

1504

524

1533

603

1531

649

1634

693

F3

2885

791

2885

933

2885

1031

2885

1227

F4

3419

1360

3419

575/600

138

D3

989

171

1019

215

D4

1121

258

1145

306

1187

356

1217

400

E2

1504

444

1539

507

1595

560

1681

649

F3

2885

756

2885

840

2885

942

F4

3419

1120

3419

Summary of Contents for AFDG

Page 1: ...all and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly...

Page 2: ...ent that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Page 3: ...t damage System contains oil and refrigerant and may be under positive pressure Recover refrigerant to relieve pressure before opening the system See unit nameplate for refrigerant type Do not use non...

Page 4: ...binet Wire Routing 19 Wire Routing 19 Wire Sizing 20 Grounding the Cabinet 20 UC800 AFD Operation 25 Adaptive Frequency Drive Control 25 Introduction 25 Chiller and AFD Sequence of Operation 25 Compre...

Page 5: ...mote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency driv...

Page 6: ...ment could result in death or serious injury Safety Precautions 1 This equipment should be adjusted and serviced by qualified electrical maintenance personnel familiar with the construction and operat...

Page 7: ...tors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury Disconnect all electric power including remote disconnects and discharge all motor st...

Page 8: ...ransistors that turn on and off in response to the gate driver A combination of two distinct operating modes make up the AFDG AFDU control within the chiller s UC800 control First by controlling the i...

Page 9: ...quirement on SSRLs of 730 780 850 890 945 and 1050 F0 Drive Bus Bars on SSRLs of 730 780 850 890 945 and 1050 G0 D Drive Module on SRRLs of 190 240 302 361 and 443 at 460V and 155 192 242 290 344 and...

Page 10: ...nce AA Original Design of Tracer AdaptiView Chiller Control with TR200 Drive Digit 12 Starter Type A Unit Mounted Digit 13 Agency Listing 0 UL and CUL Listed Standard on All Units Digit 14 Special Opt...

Page 11: ...sure is installed away from oil coolants or other airborne contaminants Do not install the drive above 3300 feet 1000 meters without derating output power For every 3300 feet 1000 meters above 3300 fe...

Page 12: ...RONT VIEW 1 400 18 660 RECOMMENDED MOUNTING HOLES 2 580 3 28 17 30 1 400 23 74 18 700 2 580 3 760 3 760 23 82 VIEW A A 23 42 MAX DOOR OPENING 23 42 MAX DOOR OPENING 109 MAX DOOR SWING 109 MAX DOOR SWI...

Page 13: ...D 13 92 12 28 6 50 4 84 5X MAGNETIC CORE CHOKES A BOTTOM VIEW 17 30 25 04 3 35 1 400 2 580 1 400 2 580 3 760 3 760 23 82 6 50 14 05 3 740 3 23 25 04 63 24 31 62 31 62 1 280 1 280 2 470 2 470 3 740 1 4...

Page 14: ...8 43 T1 10 10 GND 16 90 MIN 22 50 MAX L1 L2 L3 2X1 TERMINAL STRIP 11 73 TOP VIEW 1 85 3 90 9 10 12 80 2 80 7 90 1 88 7 90 2 80 15 60 120VAC CONTROL LOW VOLTAGE WIRING 126 22 2 50 18 74 2 50 18 86 6 54...

Page 15: ...N 22 50 MAX L1 L2 L3 11 73 2 91 2X1 TERMINAL STRIP 10 10 GND 18 43 T1 16 56 T2 14 69 T3 Adaptive Frequency Drive for Chillers 69 50 5 83 2X1 TERMINAL STRIP SERVICE ACCESS DOOR CIRCUIT BREAKER 1 13 30...

Page 16: ...osed and safely be contained within the starter enclosure However the components may sustain damage 1 57 3X 10 00 19 37 17 86 14 09 6 39 7 72 47 41 44 26 1 57 30 00 2 50 1 29 63 41 INDICATES CONDUCTOR...

Page 17: ...approximately 24 inches 61 cm to verify proper center of gravity lift point To avoid dropping of unit reposition lifting point if unit is not level Important AFDG remote mounted and AFDU unit mounted...

Page 18: ...eye Use of two chain hoists one for each lift eye or use of a single hoist with a spreader bar are permissible methods for lifting the drive Table 3 Drive weights for AFDU unit mounted Voltage Drive P...

Page 19: ...iring should be copper and should be sized according to applicable codes to handle the drive s continuous rated input current Refer to submittals for power lug sizes and location along with control wi...

Page 20: ...en the ground connections to 375 in lb 42 4 N m Note The AFDU unit mounted ships grounded to the chiller WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death...

Page 21: ...20 for drive component list Motor Leads CTs From 575V Line Local Control Panel LCP To Motor Input Power and Control Wiring AFDG SVU01L EN 21 Note Wiring from the drive to the motor is required to be r...

Page 22: ...n mode choke Figure 10 AFDG remote mounted open assembly no doors F4 Units F3 Units are similar but have only two inverters Input Power and Control Wiring 22 AFDG SVU01L EN Units with Ceramic bearings...

Page 23: ...Figure 11 AFDU unit mounted component layout Motor Leads Circuit Breaker Control Power Transformer Panel Cooling Fan Input Power and Control Wiring AFDG SVU01L EN 23...

Page 24: ...r Module AFD Starter Fault Speed Signal Drive Module Common Mode Choke CTs cal ntrol nel CP Units with ceramic bearings will not get common mode chokes Units with ceramic bearings will not get common...

Page 25: ...timal operating condition is found the algorithm can avoid the surge in the future When surge is detected a surge recovery routine makes adjustments to move out of surge reestablish stabile operating...

Page 26: ...he UC800 Startup The starting speed for AFD under UC800 control will vary depending upon the pressure ratio acrossthe compressor The UC800 predicts the condensing pressure during startup and sets the...

Page 27: ...ol algorithm will periodically readjust this boundary This re optimization will occur when any of three different criteria are met 1 After startup stabilization the control will re optimize unless the...

Page 28: ...the new surge boundary Surge Detection Surge detection control logic monitors changes in compressor motor current A surge occurrence leaves a characteristic motor current signature as shown in Figure...

Page 29: ...C800 to provide a speed reference to the drive The UC800 also provides both Fault and Up to Speed transition complete contact closure inputs for variable frequency drive starters At start of the compr...

Page 30: ...ommunication Potential Transformers Line Side of Starter Circuit Breaker Starter Module to Variable Speed Drive Interface HFC Stop Relay 2K11 2K1 2K1 Start Relay Starter Module 3 Phase Current Transfo...

Page 31: ...ion Potential Transformers Line Side of Starter Circuit Breaker Starter Module to Variable Speed Drive Interface HPC Stop Relay 2K11 2K1 2K1 Start Relay Starter Module 3 Phase Current Transformers Loa...

Page 32: ...o 60 active or historic alarms A technician can interact with an individual device or a group of devices for advanced troubleshooting For more information on Tracer TU visit your local Trane Service c...

Page 33: ...S Current Unbalance Trip Point 15 100 30 Percent Current Unbalance Grace Period 10 255 90 Seconds Maximum Acceleration Time 6 64 6 Seconds Set to 30 Acceleration Shutdown Action Shutdown Transition Sh...

Page 34: ...the power cannot be inadvertently energized For variable frequency drives or other energy storing components provided by Trane or others refer to the appropriate manufacturer s literature for allowab...

Page 35: ...Use the up down arrow keys to access the parameter number and then press the OK key 5 Use the up down arrow keys to change the parameter and then press the OK key to change the setting Table 10 Job sp...

Page 36: ...small Heat sink temp 1634 0 23 Display line 2 large Power Kw 1610 0 24 Display line 3 large Freq Hz 1613 0 40 Hand on key Disabled 0 0 41 Off key Disabled 0 0 60 Main Menu password 999 0 61 Access to...

Page 37: ...Data CT Meter Scale 0 RLA Stop Delay 3 KW Motor NP RLA Volts Hz Voltage Transformer Ratio 20 Prestart Checks Date Checked Current Unbalance Trip Point 30 Drive Grounded Acceleration Time 30 Motor Rot...

Page 38: ...terminal connections inside the drive enclosure Ensure all are clean and tight and not rubbing against each other anywhere WARNING Live Electrical Components Failure to follow all electrical safety pr...

Page 39: ...power including remote disconnects and discharge all motor start run capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For varia...

Page 40: ...40 AFDG SVU01L EN Wiring Schematics For reference an as built schematic wiring diagram and a field wiring connection diagram are located inside the main control panel door of the chiller...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...