26
UHM-DHM-SF-1H
Service Facts
*UHM AIRFLOW - COOLING
NOTE:
CONTINUOUS fan mode during COOL-
ING operation may not be appropriate in
humid climates. If the indoor air ex-
ceeds 60% relative humidity or simply
feels uncomfortably humid, it is recom-
mended that the fan only be used in the
AUTO mode.
0.1
0.3
0.5
0.7
0.9
CFM
714
734
739
733
722
Watts
79
118
157
194
231
CFM
765
784
789
782
770
Watts
88
128
168
206
244
CFM
816
834
838
831
819
Watts
96
138
179
220
258
CFM
868
884
887
880
867
Watts
103
149
192
234
273
CFM
919
934
936
929
916
Watts
117
161
205
249
290
CFM
995
1009
1009
1002
989
Watts
135
181
227
274
316
CFM
1072
1084
1083
1075
1061
Watts
156
204
253
302
346
CFM
1123
1134
1132
1124
1110
Watts
171
220
271
322
368
CFM
862
879
882
875
863
Watts
105
148
190
232
272
CFM
924
939
941
934
921
Watts
118
162
207
250
291
CFM
985
999
1000
992
979
Watts
133
178
224
270
313
CFM
1046
1059
1059
1051
1037
Watts
149
196
244
292
336
CFM
1108
1119
1117
1109
1095
Watts
167
215
265
316
362
CFM
1200
1209
1206
1197
1183
Watts
197
248
301
355
404
CFM
1292
1299
1294
1285
1270
Watts
232
286
343
400
453
CFM
1353
1359
1353
1344
1328
Watts
258
314
373
432
488
CFM
1011
1024
1024
1017
1003
Watts
139
185
232
279
322
CFM
1082
1094
1093
1085
1071
Watts
159
207
256
306
351
CFM
1154
1164
1162
1153
1139
Watts
181
231
283
335
382
CFM
1225
1234
1230
1222
1207
Watts
206
258
312
367
417
CFM
1297
1304
1299
1290
1275
Watts
234
288
345
402
455
CFM
1404
1409
1402
1393
1377
Watts
281
340
400
462
520
CFM
1512
1514
1505
1495
1478
Watts
336
399
464
530
595
CFM
1583
1584
1574
1564
1546
Watts
377
444
512
580
650
CFM
1159
1169
1167
1158
1144
Watts
183
233
285
337
385
CFM
1241
1249
1245
1236
1221
Watts
212
264
319
374
425
CFM
1323
1329
1324
1315
1299
Watts
244
300
358
416
470
CFM
1404
1409
1402
1393
1377
Watts
281
340
400
462
520
CFM
1486
1489
1481
1471
1454
Watts
322
384
448
513
576
CFM
1609
1609
1599
1588
1571
Watts
393
461
530
599
671
CFM
1732
1730
1716
1705
1687
Watts
475
550
624
698
781
CFM
1813
1810
1795
1783
1765
Watts
536
617
694
772
864
Notes:
1. * First letter may be "A" or "T".
2. ^ Letter may be "A" through "Z"
3. ** Factory setting.
4. Continuous Fan Setting: Heating or cooling airflow is approximately 50% of selected
cooling value.
5. LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID
CLIMATE setting; NORMAL is 400 cfm/ton; HIGH 450 cfm/ton is for DRY CLIMATE setting.
*UHMC100ACV4VA^
Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static
Pressure With Filter
Airflow
Setting
External Static Pressure
2.5
290 CFM/ton
Unit
Outdoor
310 CFM/ton
330 CFM/ton
400 CFM/ton
430 CFM/ton
350 CFM/ton
370 CFM/ton
450 CFM/ton
3
290 CFM/ton
310 CFM/ton
330 CFM/ton
430 CFM/ton
450 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton
370 CFM/ton
400 CFM/ton
430 CFM/ton
3.5
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
450 CFM/ton
Cooling
430 CFM/ton
450 CFM/ton
4
290 CFM/ton
310 CFM/ton
330 CFM/ton
350 CFM/ton
370 CFM/ton
400 CFM/ton