Installer’s Setup Continued
Installer’s Guide
Airflow Settings
Setting
Range
Description
Blower On Delay Cooling
Disabled, [Enhanced],
30 Second Delay,
1 Minute At 50%,
4 Minutes At 80%,
7.5 Minutes at 80%,
1 Minute At 50% 4 Minutes At 80%
(Variable Speed indoor blower only) Select the cooling blower on
delay. Enhanced setting is 1 minute at 50% blower speed then 7.5
minutes at 80% blower speed and finally 100% blower speed.
Blower On Delay Cooling
[0] - 30 seconds
(Non-Variable Speed blower only) Select the cooling blower on delay
Blower Off Delay Cooling
Disabled, 30 Seconds At 35%,
3 Minutes At 50%,
[1.5 Minutes At 50%],
30 Seconds At 50%,
45 Seconds At 100%,
1.5 Minutes At 100%
(Variable Speed indoor blower only) Select the cooling blower off
delay
Blower Off Delay Cooling
[0] - 90 Seconds
(Non-Variable Speed blower only) Select the cooling blower off delay
Blower On Delay Heating
Disabled, [Enhanced],
30 Second Delay,
1 Minute At 50%,
4 Minutes At 80%,
7.5 Minutes at 80%,
1 Minute At 50% 4 Minutes At 80%
(Variable Speed indoor blower only) Select the compressor heating
blower on delay. Enhanced setting is 1 minute at 50% blower speed
then 7.5 minutes at 80% blower speed and finally 100% blower
speed.
Blower On Delay Heating
[0] - 30 Seconds
(Non-Variable Speed blower only) Select the compressor heating
blower on delay
Blower On Delay Heating
[0] - 60 Seconds
Select the hydronic heating blower on delay
Blower Off Delay Heating
Disabled,
30 Seconds At 35%,
3 Minutes At 50%,
[1.5 Minutes At 50%],
30 Seconds At 50%,
45 Seconds At 100%,
1.5 Minutes At 100%
(Variable Speed indoor blower only) Select the compressor heating
blower off delay
Blower Off Delay Heating
[0] - 90 Seconds
(Non-Variable Speed blower only) Select the compressor heating
blower off delay
Blower Off Delay Heating
[0] - 90 Seconds
Select the hydronic heating blower off delay
1st Stage Airflow Cool
35% - 60%, [50%]
(2 compressor 2 stage only) Select 1st stage cooling airflow
2nd Stage Airflow Cool
55% - 80%, [65%]
(1 compressor 2 stage only) Select 1st stage cooling airflow
1st Stage Airflow Heat
35% - 60%, [50%]
(2 compressor 2 stage only) Select 1st stage heating airflow
2nd Stage Airflow Heat
55% - 80%, [65%]
(1 compressor 2 stage only) Select 1st stage heating airflow
Once all selections have been made, press the Done button to exit and return to Menu. Press Next to navigate to the next setting.
Installer Settings allow the user to configure the equipment settings and customize how the control operates. To
access Installer Settings press the Menu button, then press Next until “Service” is displayed. Now press Select and
hold for 5 seconds until “Installer Settings” is displayed. Press Select again to enter Installer Settings menu. The
default setting will be shown in brackets. After each selection press Done to save changes.