Performance Data
SSP-PRC001-EN
13
Table 4.
Gross Cooling Capacities (MBh) 10 Ton TWA120A Heat Pump with 10 Ton TWE120A Air Handler
CFM Air
flow
Ent
DB °F
Ambient Temperature
85
95
105
Entering WB
61
67
73
61
67
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
3600
75
114.6 90.1 126.2 76.3 138.8 51.1 110.6 88.1 121.8 74.5 134.0 49.4 106.2 85.9 117.1 72.6 128.9 47.7
80
115.0 104.8 126.4 85.8 138.8 66.4 111.1 102.8 122.0 83.9 134.0 64.6 106.9 100.7 117.3 81.9 128.9 62.6
85
117.1 117.1 126.5 100.7 138.8 81.2 113.7 113.7 122.0 98.6 134.0 79.3 110.1 110.1 117.4 96.5 129.0 77.4
90
122.7 122.7 126.9 115.2 138.9 95.9 119.2 119.2 122.7 113.2 134.2 94.0 115.5 115.5 118.2 111.1 129.1 92.1
4000
75
116.7 94.0 128.5 73.3 114.1 52.1 112.5 91.9 123.9 71.4 136.1 50.4 108.1 86.7 119.1 69.3 130.8 48.5
80
117.5 110.2 128.6 89.5 141.1 68.5 113.4 108.1 124.0 87.6 136.1 66.6 109.2 106.0 119.2 85.5 130.8 64.6
85
120.7 120.7 128.6 105.4 141.1 84.5 117.1 117.1 124.1 103.4 136.2 82.6 113.4 113.4 119.3 101.2 131.0 80.7
90
126.6 126.6 129.5 121.4 141.2 100.5 122.9 122.9 125.2 119.4 136.3 98.6 119.1 119.1 120.7 117.3 131.1 96.6
4400
75
118.5 97.7 130.3 75.5 142.9 53.0 114.2 95.6 125.6 73.6 137.8 51.1 109.6 93.4 120.7 71.6 132.4 49.2
80
119.7 115.3 130.4 93.0 142.9 70.4 115.6 113.2 125.8 91.0 137.8 68.5
11.3 111.1 120.8 89.0 132.5 66.5
85
123.9 123.9 130.5 110.0 143.0 87.7 120.2 120.2 125.9 107.9 138.0 85.8 116.3 116.3 121.1 105.8 132.6 83.8
90
129.9 129.9 131.9 127.4 143.1 104.8 126.1 126.1 127.5 125.4 138.1 102.9 122.2 122.2 122.0 122.0 132.7 100.9
4800
75
120.0 101.3 131.9 77.7 144.5 53.6 115.6 99.1 127.1 75.7 139.4 51.7 111.1 96.9 122.1 73.7 133.8 49.8
80
121.7 120.2 132.0 96.3 144.5 72.2 116.7 116.7 127.2 94.4 139.3 70.3 112.8 112.8 122.2 92.3 133.9 68.3
85
126.7 126.7 132.2 114.4 144.6 90.7 122.9 122.9 127.6 112.4 139.5 88.8 118.8 118.8 122.7 110.3 134.0 86.8
90
132.9 132.9 134.1 133.2 144.7 109.0 129.0 129.0 128.9 128.9 138.5 106.9 124.9 124.9 124.8 124.8 134.1 104.8
CFM Air
flow
Ent
DB °F
Ambient Temperature
115
Enter WB
61
67
73
MBH SHC MBH SHC MBH SHC
3600
75
101.7 83.6 112.2 70.6 123.4 45.8
80
102.6 98.5 112.4 79.8 123.5 60.6
85
106.3 106.3 112.5 94.3 123.6 75.3
90
111.7 111.7 113.5 109.0 123.7 90.0
4000
75
103.5 87.5 114.0 67.2 125.2 46.5
80
104.9 103.8 114.2 83.4 125.3 62.6
85
109.5 109.5 114.4 99.0 125.4 78.6
90
115.0 115.0 115.9 115.2 125.5 94.5
4400
75
105.0 91.1 115.5 69.4 126.7 47.1
80
106.5 106.5 115.7 86.8 126.8 64.5
85
112.2 112.2 116.1 103.6 126.9 81.7
90
117.9 117.9 117.8 117.8 126.9 98.5
4800
75
106.3 94.7 116.7 71.5 128.0 47.7
80
108.7 108.7 116.9 89.8 128.0 66.2
85
114.6 114.6 117.6 108.0 128.2 84.7
90
120.5 120.5 120.4 120.4 128.2 102.6
Notes:
1.
Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2.
All temperatures are in °F.
3.
All capacities shown are gross and have not considered indoor fan heat.
4.
To obtain net cooling capacities, subtract indoor fan heat.
5.
MBH = Total Gross Cooling Capacity
6.
SHC = Sensible Heat Capacity
10 Tons Gross Cooling Capacities