12
SSP-PRC001-EN
Table 3.
Gross Cooling Capacities (MBh) 7½ Tons TWA090A Heat Pump with 7½ TWE090A Air Handler
CFM Air
flow
Ent
DB °F
Ambient Temperature
85
95
105
Entering WB
61
67
73
61
67
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
2700
75
84.1
67.2
92.8
56.3 102.1 37.7
81.2
65.7
89.5
55.0
98.5
36.4
78.0
64.2
86.1
53.6
94.8
35.2
80
84.6
78.6
93.0
64.5 102.1 49.6
81.8
77.2
89.8
63.2
98.5
48.3
78.8
75.7 86.3. 61.7
94.8
46.9
85
86.9
86.9
93.1
75.8 102.2 61.3
84.4
84.4
89.9
74.4
98.7
60.0
81.7
81.7
86.4
72.9
95.0
58.6
90
91.2
91.2
93.7
87.3 102.3 72.9
88.7
88.7
90.6
85.9
98.7
71.5
86.0
86.0
87.3
84.5
95.1
70.0
3000
75
87.5
70.3
94.4
54.8 103.7 38.4
82.7
68.8
91.1
53.4 100.0 37.1
79.4
67.2
87.5
51.9
96.1
35.7
80
86.5
82.9
94.6
67.5 103.7 51.2
83.6
81.4
91.1
65.9 100.0 499
80.5
79.9
87.6
64.4
96.2
48.5
85
89.6
89.6
94.7
79.7 103.8 64.0
87.1
87.1
91.4
78.3 100.2 62.6
84.3
84.3
87.9
76.7
96.4
61.3
90
94.1
94.1
95.7
92.4
92.4 103.9 76.4
91.5
92.5
91.0 100.3 75.0
88.6
88.6
88.7
88.7
96.5
73.6
3300
75
87.0
73.3
95.7
56.6 104.9 39.0
83.9
71.7
92.3
55.2 101.2 37.6
80.6
70.1
88.6
53.7
97.3
36.2
80
88.1
87.0
95.8
70.1 105.0 52.8
84.7
84.7
92.4
68.6 101.2 51.4
81.9
81.9
88.8
67.0
97.4
50.0
85
92.0
92.0
96.1
83.4 105.1 66.5
89.3
89.3
92.8
82.0 101.4 65.2
86.4
86.4
89.2
80.4
97.6
63.8
90
96.6
96.6
97.5
97.2 105.2 79.9
93.9
93.9
93.9
93.9 101.5 78.5
90.9
90.9
91.0
91.9
97.7
77.0
3600
75
88.2
76.1
96.8
58.3 106.0 39.5
85.0
74.6
93.3
56.9 102.2 38.1
81.6
73.0
89.6
55.4
98.2
36.7
80
89.3
89.3
96.9
72.7 106.1 54.2
86.6
86.6
93.4
71.2 102.3 52.9
83.7
83.7
89.8
69.6
98.3
51.5
85
94.1
94.1
97.4
87.0 106.2 69.0
91.3
91.3
94.0
85.6 102.5 67.6
88.3
88.3
90.4
84.0
98.4
66.1
90
98.9
98.9
98.9
98.9 106.4 83.2
96.0
96.0
96.1
96.1 102.6 81.8
92.9
92.9
93.0
93.0
98.7
80.3
CFM Air
flow
Ent
DB °F
Ambient Temperature
115
Enter WB
61
67
73
MBH SHC MBH SHC MBH SHC
2700
75
74.7
62.5
82.4
52.1
90.9
33.8
80
75.6
74.1
82.6
60.0
91.0
45.5
85
78.9
78.9
82.9
71.3
91.1
57.2
90
83.1
83.1
84.0
83.0
91.3
68.5
3000
75
75.9
65.6
83.7
50.4
92.2
34.3
80
77.0
77.0
83.9
62.8
92.3
47.1
85
81.3
81.3
84.3
75.2
92.5
59.9
90
85.6
85.6
85.7
85.7
92.6
72.1
3300
75
77.1
68.5
84.8
52.2
93.3
34.8
80
78.9
78.9
85.0
65.4
93.4
48.6
85
83.3
83.3
85.6
78.9
93.6
62.4
90
87.8
87.8
87.9
87.9
93.7
75.5
3600
75
78.1
71.3
85.7
53.9
94.1
35.3
80
80.6
80.6
85.9
68.0
94.3
50.1
85
85.1
85.1
86.7
82.5
94.4
64.6
90
89.7
89.7
89.8
89.8
94.8
78.8
Notes:
1.
Dry coil condition. Total gross capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2.
All temperatures are in °F.
3.
All capacities shown are gross and have not considered indoor fan heat.
4.
To obtain net cooling capacities, subtract indoor fan heat.
5.
MBH = Total Gross Cooling Capacity
6.
SHC = Sensible Heat Capacity
Performance Data