14

Indoor Blower Performance

Indoor Fan Performance 4WCY4048

Down Airflow

Horizontal Airflow

4WCY4048-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

187 

232 

264 

291 

318 

347 

379 

413 

446 

472 

CFM 

1355 

1387 

1396 

1392 

1382 

1370 

1360 

1351 

1341 

1326 

400 CFM/TON* 

OFF 

OFF 

OFF  OFF 

Watts 

315 

324 

352 

389 

428 

464 

498 

529 

563 

606 

CFM 

1603 

1581 

1577 

1580 

1583 

1583 

1577 

1567 

1558 

1556 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

301 

431 

507 

552 

584 

615 

651 

694 

739 

779 

CFM 

1752 

1794 

1812 

1816 

1812 

1806 

1800 

1797 

1793 

1785 

4WCY4048-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

208 

254 

284 

312 

343 

379 

414 

437 

460 

490 

CFM 

1337 

1393 

1398 

1388 

1383 

1390 

1399 

1384 

1380 

1370 

400 CFM/TON* 

OFF 

OFF 

OFF  OFF 

Watts 

302 

349 

386 

423 

465 

509 

552 

583 

599 

628 

CFM 

1574 

1580 

1585 

1589 

1594 

1598 

1601 

1597 

1584 

1556 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

501 

523 

555 

592 

631 

672 

714 

760 

800 

845 

CFM 

1847 

1823 

1817 

1818 

1820 

1819 

1817 

1820 

1815 

1810 

Indoor Fan Performance 4WCY4060

Down Airflow

4WCY4060-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

394 

427 

464 

504 

548 

591 

633 

668 

CFM 

1673 

1772 

1799 

1793 

1779 

1771 

1767 

1756 

400 CFM/TON* 

OFF 

OFF 

OFF  OFF 

Watts 

695 

642 

660 

710 

764 

811 

849 

893 

966 

CFM 

2054 

2036 

2031 

2032 

2033 

2031 

2023 

2012 

2002 

4WCY4060-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

443 

461 

493 

532 

571 

607 

642 

680 

CFM 

1796 

1741 

1726 

1725 

1722 

1712 

1698 

1692 

400 CFM/TON* 

OFF 

OFF 

OFF  OFF 

Watts 

740 

697 

715 

763 

819 

866 

892 

894 

872 

CFM 

2012 

1987 

1979 

1977 

1976 

1969 

1950 

1913 

1852 

Horizontal Airflow

*Factory Default Setting

Summary of Contents for 4WCY4024

Page 1: ...2013 Trane Pub No 22 1789 19 Product Data 4WCY4024 through 4WCY4060 Single Packaged Convertible Heat Pump 14 SEER 2 5 Ton R 410A 22 1789 19...

Page 2: ...are easy and versatile to install Because cooling and heating functions are all contained in a single cabinet a Trane packaged heat pump system is easy to install and service It can be flush mounted b...

Page 3: ...Contents Optional Equipment Listing 4 General Data 5 Heater Data 8 SPEK Data 9 Performance Data Indoor Blower 12 Typical Wiring 16 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 2...

Page 4: ...BAYADAP053A Adapter Curb 4WCY4042 060 to BAYCURB034 BAYADAP054A 12 Duct Shroud Covers Horizontal 4WCY4024 0607 BAYCOVR112A 18 Duct Shroud Covers Horizontal 4WCY4024 060 7 BAYCOVR118A Extreme Condition...

Page 5: ...Net lbs 4WCY4030A1000B 208 230 1 60 30000 875 2 15 12 0 14 25 71 27600 2 15 15200 1 81 8 0 208 230 1 60 19 2 30 30 RECIPROCATING 200 230 1 60 11 1 63 SPINE FIN 2 24 13 32 3 8 EXPANSION VALVE PLATE FIN...

Page 6: ...3 468 372 4WCY4048B1000B 208 230 1 60 47500 1400 3 96 12 0 14 0 73 45000 3 77 28400 3 44 8 0 208 230 1 60 33 9 50 50 SCROLL 208 230 1 60 20 5 109 SPINE FIN 2 24 18 01 3 8 EXPANSION VALVE PLATE FIN 3 1...

Page 7: ...61 75 607 479 4WCY4060A3000C 208 230 3 60 58000 1780 4 95 11 5 14 0 76 55000 4 60 37600 4 29 8 0 208 230 3 60 28 6 45 45 SCROLL 208 230 3 60 16 0 110 SPINE FIN 2 24 23 57 3 8 EXPANSION VALVE PLATE FIN...

Page 8: ...048 060 4 W TC 3060 4 WCZ6048 060 4 7 5 10 0 40 45 40 45 208 240 3 42 48 15 0 20 0 51200 68300 2 7 5 10 0 45 60 208 240 1 54 63 11 27 15 0 38500 51200 2 7 5 10 0 1 36 42 7 5 10 0 25600 34100 W TC 3036...

Page 9: ...9 Single Power Entry Kit Data Table 2 BAYSPEK060F Ampacity and Max Fusing Circuit Breakers...

Page 10: ...10 Table 3 BAYSPEK061 Ampacity and Max Fusing Circuit Breakers Single Power Entry Kit Data...

Page 11: ...11 Single Power Entry Kit Data Table 4 BAYSPEK062F 63F 64E 65E Ampacity and Max Fusing Circuit Breakers...

Page 12: ...10 816 813 803 794 800 846 450 CFM TON OFF OFF ON OFF Watts 86 102 127 156 185 213 242 275 319 CFM 884 870 882 899 909 907 895 886 898 Indoor Fan Performance 4WCY4030 4WCY4030 HOR DIPSWITCH SETTINGS E...

Page 13: ...390 424 455 483 516 571 CFM 1391 1377 1377 1375 1366 1352 1344 1360 Indoor Fan Performance 4WCY4042 4WCY4042 HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0...

Page 14: ...0 400 CFM TON OFF OFF OFF OFF Watts 302 349 386 423 465 509 552 583 599 628 CFM 1574 1580 1585 1589 1594 1598 1601 1597 1584 1556 450 CFM TON OFF OFF ON OFF Watts 501 523 555 592 631 672 714 760 800 8...

Page 15: ...speed to provide improved comfort quietness and potential energy savings The Graph below shows the ramping process COOLING FAN DELAY OPTIONS SWITCH SETTINGS DELAY NOMINAL AIRFLOW OFF OFF 50 80 100 if...

Page 16: ...16 Typical Wiring...

Page 17: ...17 Typical Wiring...

Page 18: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Page 19: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Page 20: ...s to construct build or modify the items depicted in the drawings The manufacturer is not respon sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resu...

Page 21: ...ovide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manu facturer is not responsible for th...

Page 22: ...ot responsible for the unauthorized use of these drawings and expressly disclaims any liability for dam ages resulting from such unauthorized use D C B A E Manual Fresh Air Model Unit Application Mode...

Page 23: ...23 Dimensional Data and Weights 4WCY4024 through 4WCY4036 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 24: ...24 Dimensional Data and Weights 4WCY4024 through 4WCY4036 2 of 3...

Page 25: ...25 Dimensional Data and Weights 4WCY4024 through 4WCY4036 3 of 3...

Page 26: ...26 Dimensional Data and Weights 4WCY4042 through 4WCY4060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 27: ...27 Dimensional Data and Weights 4WCY4042 through 4WCY4060 2 of 3...

Page 28: ...28 Dimensional Data and Weights 4WCY4042 through 4WCY4060 3 of 3...

Page 29: ...tac tors Accessories Roof Curb The roof curb shall be de signed to mate with the unit and provide support and complete weathertight instal lation when properly installed Adhesive back polyurethane sea...

Page 30: ...The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 90...

Reviews: