Indoor Blower Performance

Indoor Fan Performance 4WCY4024

Down Airflow

Horizontal Airflow

4WCY4024A-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

52 

66 

89 

115 

140 

164 

186 

206 

229 

259 

CFM 

706 

716 

727 

733 

731 

719 

700 

679 

662 

659 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

72 

94 

120 

148 

177 

207 

233 

254 

267 

290 

CFM 

786 

793 

805 

813 

813 

806 

793 

780 

778 

799 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

80 

99 

125 

153 

182 

211 

243 

284 

342 

CFM 

860 

862 

877 

892 

903 

904 

897 

884 

869 

4WCY4024-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

35 

70 

90 

108 

131 

160 

188 

204 

225 

250 

CFM 

695 

729 

734 

728 

721 

715 

705 

679 

680 

685 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

79 

87 

105 

129 

155 

180 

206 

232 

264 

306 

CFM 

846 

807 

802 

810 

816 

813 

803 

794 

800 

846 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

86 

102 

127 

156 

185 

213 

242 

275 

319 

CFM 

884 

870 

882 

899 

909 

907 

895 

886 

898 

Indoor Fan Performance 4WCY4030

4WCY4030-HOR 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

110 

148 

176 

203 

232 

264 

293 

311 

CFM 

870 

898 

908 

911 

914 

916 

906 

868 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

147 

190 

217 

241 

270 

305 

337 

353 

CFM 

980 

1013 

1013 

1006 

1005 

1008 

1002 

957 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

205 

247 

276 

305 

339 

375 

403 

CFM 

1121 

1141 

1139 

1135 

1138 

1140 

1122 

4WCY4030-DOWN 

DIPSWITCH SETTINGS 

External Static Pressure (in. wg) 

AIRFLOW SETTING 

 

0.0 

0.1 

0.2 

0.3 

0.4 

0.5 

0.6 

0.7 

0.8 

0.9 

1.0 

350 CFM/TON 

OFF 

OFF 

OFF 

ON 

Watts 

109 

140 

166 

191 

220 

250 

280 

302 

CFM 

850 

871 

873 

867 

858 

850 

840 

822 

400 CFM/TON* 

OFF 

OFF 

OFF 

OFF 

Watts 

145 

179 

207 

233 

261 

291 

319 

341 

CFM 

962 

977 

978 

970 

959 

950 

946 

951 

450 CFM/TON 

OFF 

OFF 

ON 

OFF 

Watts 

199 

230 

268 

302 

328 

352 

388 

CFM 

1088 

1096 

1105 

1107 

1100 

1089 

1081 

*Factory Default Setting

Down Airflow

Horizontal Airflow

Summary of Contents for 4WCY4024

Page 1: ...2013 Trane Pub No 22 1789 19 Product Data 4WCY4024 through 4WCY4060 Single Packaged Convertible Heat Pump 14 SEER 2 5 Ton R 410A 22 1789 19...

Page 2: ...are easy and versatile to install Because cooling and heating functions are all contained in a single cabinet a Trane packaged heat pump system is easy to install and service It can be flush mounted b...

Page 3: ...Contents Optional Equipment Listing 4 General Data 5 Heater Data 8 SPEK Data 9 Performance Data Indoor Blower 12 Typical Wiring 16 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 2...

Page 4: ...BAYADAP053A Adapter Curb 4WCY4042 060 to BAYCURB034 BAYADAP054A 12 Duct Shroud Covers Horizontal 4WCY4024 0607 BAYCOVR112A 18 Duct Shroud Covers Horizontal 4WCY4024 060 7 BAYCOVR118A Extreme Condition...

Page 5: ...Net lbs 4WCY4030A1000B 208 230 1 60 30000 875 2 15 12 0 14 25 71 27600 2 15 15200 1 81 8 0 208 230 1 60 19 2 30 30 RECIPROCATING 200 230 1 60 11 1 63 SPINE FIN 2 24 13 32 3 8 EXPANSION VALVE PLATE FIN...

Page 6: ...3 468 372 4WCY4048B1000B 208 230 1 60 47500 1400 3 96 12 0 14 0 73 45000 3 77 28400 3 44 8 0 208 230 1 60 33 9 50 50 SCROLL 208 230 1 60 20 5 109 SPINE FIN 2 24 18 01 3 8 EXPANSION VALVE PLATE FIN 3 1...

Page 7: ...61 75 607 479 4WCY4060A3000C 208 230 3 60 58000 1780 4 95 11 5 14 0 76 55000 4 60 37600 4 29 8 0 208 230 3 60 28 6 45 45 SCROLL 208 230 3 60 16 0 110 SPINE FIN 2 24 23 57 3 8 EXPANSION VALVE PLATE FIN...

Page 8: ...048 060 4 W TC 3060 4 WCZ6048 060 4 7 5 10 0 40 45 40 45 208 240 3 42 48 15 0 20 0 51200 68300 2 7 5 10 0 45 60 208 240 1 54 63 11 27 15 0 38500 51200 2 7 5 10 0 1 36 42 7 5 10 0 25600 34100 W TC 3036...

Page 9: ...9 Single Power Entry Kit Data Table 2 BAYSPEK060F Ampacity and Max Fusing Circuit Breakers...

Page 10: ...10 Table 3 BAYSPEK061 Ampacity and Max Fusing Circuit Breakers Single Power Entry Kit Data...

Page 11: ...11 Single Power Entry Kit Data Table 4 BAYSPEK062F 63F 64E 65E Ampacity and Max Fusing Circuit Breakers...

Page 12: ...10 816 813 803 794 800 846 450 CFM TON OFF OFF ON OFF Watts 86 102 127 156 185 213 242 275 319 CFM 884 870 882 899 909 907 895 886 898 Indoor Fan Performance 4WCY4030 4WCY4030 HOR DIPSWITCH SETTINGS E...

Page 13: ...390 424 455 483 516 571 CFM 1391 1377 1377 1375 1366 1352 1344 1360 Indoor Fan Performance 4WCY4042 4WCY4042 HOR DIPSWITCH SETTINGS External Static Pressure in wg AIRFLOW SETTING 1 2 3 4 0 0 0 1 0 2 0...

Page 14: ...0 400 CFM TON OFF OFF OFF OFF Watts 302 349 386 423 465 509 552 583 599 628 CFM 1574 1580 1585 1589 1594 1598 1601 1597 1584 1556 450 CFM TON OFF OFF ON OFF Watts 501 523 555 592 631 672 714 760 800 8...

Page 15: ...speed to provide improved comfort quietness and potential energy savings The Graph below shows the ramping process COOLING FAN DELAY OPTIONS SWITCH SETTINGS DELAY NOMINAL AIRFLOW OFF OFF 50 80 100 if...

Page 16: ...16 Typical Wiring...

Page 17: ...17 Typical Wiring...

Page 18: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Page 19: ...page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the...

Page 20: ...s to construct build or modify the items depicted in the drawings The manufacturer is not respon sible for the unauthorized use of these drawings and expressly disclaims any liability for damages resu...

Page 21: ...ovide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manu facturer is not responsible for th...

Page 22: ...ot responsible for the unauthorized use of these drawings and expressly disclaims any liability for dam ages resulting from such unauthorized use D C B A E Manual Fresh Air Model Unit Application Mode...

Page 23: ...23 Dimensional Data and Weights 4WCY4024 through 4WCY4036 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 24: ...24 Dimensional Data and Weights 4WCY4024 through 4WCY4036 2 of 3...

Page 25: ...25 Dimensional Data and Weights 4WCY4024 through 4WCY4036 3 of 3...

Page 26: ...26 Dimensional Data and Weights 4WCY4042 through 4WCY4060 1 of 3 NOTE The view labeled Bottom Side represents the Base as viewed looking up from underneath the unit...

Page 27: ...27 Dimensional Data and Weights 4WCY4042 through 4WCY4060 2 of 3...

Page 28: ...28 Dimensional Data and Weights 4WCY4042 through 4WCY4060 3 of 3...

Page 29: ...tac tors Accessories Roof Curb The roof curb shall be de signed to mate with the unit and provide support and complete weathertight instal lation when properly installed Adhesive back polyurethane sea...

Page 30: ...The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 90...

Reviews: