Trane 4TTX6 Installer'S Manual Download Page 4

4

18-AC55D1-4

Installer’s Guide

adjust system refrigerant charge upon completion of
installation. See unit Service Facts.

E. ELECTRICAL CONNECTIONS

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility of
electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended

to simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum

 total

 length of low voltage

wiring from outdoor unit, to indoor unit, and to thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat.  Wire per appropriate
hook-up diagram (included in these instructions).

F. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by
closing the system main disconnect switch.  This will activate
the compressor sump heat (where used).  Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

G. OPERATIONAL AND CHECKOUT

PROCEDURES

Final phases of this installation are the unit Operational and
Checkout Procedures which are found in this instruction (see
page 8). To obtain proper performance, all units must be
operated and charge adjustments made in accordance with
procedures found in the Service Facts.

H. ELECTRIC HEATERS

Electric heaters, if used, are to be installed in the air han-
dling device according to the instructions accompanying the
air handler and the heaters.

I. START CONTROL

Some models have quick start components which are factory
installed. For models that do not have factory installed start
components, provisions are made for a field installed start kit
accessory. When adding an accessory, follow the instructions
provided with the kit.

J. OUTDOOR THERMOSTAT

An outdoor thermostat TAYSTAT250A may be field installed.
For data, see wiring diagram attached to unit and instruction
sheet packaged with outdoor thermostat.

K. XL SEACOAST SHIELD

All units are shipped with a black Seacoast Shield. Removal
of the shield will potentially shorten the life of the joints in
the outdoor coil.

REFRIGERANT CIRCUIT

Liquid Pressure Too High

Liquid Pressure Too Low

Suction Pressure Too High

Suction Pressure Too Low

Liquid Refrig. Floodback TXV System

Liquid Refrig. Floodback Capillary Tube System

I.D. Coil Frosting

Compressor Runs Inadequate or No Cooling

ELECTRICAL

Compressor & O.D. Fan Do Not Start

Compressor Will Not Start But O.D. Fan Runs

O.D. Fan Won’t Start

Compressor Hums But Won’t Start

Compressor Cycles on IOL

I.D. Blower Won’t Start

SYSTEM FAULTS

P - Primary Causes      S - Secondary Causes

P

P

P

S

S

P

S

S

S

S

S

S

S

P

S

S

S

S

P

P

P

P

S

S

S

S

S

S

S

P

P

P

P

S

P

P

S

S

S

P

P

P

P

P

P

P

P

P

P

S

S

S

P

P

P

P

P

S

P

S

P

S

S

S

S

S

S

S

P

P

P

P

P

S

P

P

POWER SUPPLY

HIGH VOLTAGE WIRING

COMPR. IOL

RUN CAPACITOR

START CAPACITOR

START RELAY

CONTACTOR CONTACTS

LOW VOLTAGE WIRING

CONTROL TRANSFORMER

CONTACTOR COIL

LOW VOLTAGE FUSE

STUCK COMPRESSOR

INEFFICIENT COMPRESSOR

REFRIGERANT UNDERCHARGE

REFRIGERANT OVERCHARGE

EXCESSIVE EVAP. LOAD

NONCONDENSABLES

RESTRICTED O.D. AIRFLOW

O.D. AIR RECIRCULATION

TXV STUCK OPEN

SUPERHEAT

RESTRICTED I.D. AIRFLOW

REF. CIRCUIT RESTRICTIONS

O.D. FAN SPEED SWITCH

TROUBLESHOOTING CHART — WHAT TO CHECK

L. TROUBLESHOOTING

Summary of Contents for 4TTX6

Page 1: ...is hygroscopic action the system should remain sealed whenever possible Never break a vacuum with air and always change the driers when opening the system for component replacement Check for transport...

Page 2: ...o rebend once it has been shaped 3 Determine the best starting point for routing the refrigerant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liqu...

Page 3: ...acuum pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns i...

Page 4: ...installed in the air han dling device according to the instructions accompanying the air handler and the heaters I START CONTROL Some models have quick start components which are factory installed Fo...

Page 5: ...to Field Hook up Diagrams above 4TTX6 units require 80 airflow with Y1 first stage 100 airflow with Y2 second stage Note A The installer must jumper at the LVTB R to O Note B Cut remove the factory in...

Page 6: ...2 5 8 756 29 3 4 5 8 5 16 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 692 27 1 4 4TTX6036B 4 1064 41 7 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 730 28 3 4 4TTX6048B 4 1267 49 7 8 94...

Page 7: ...18 AC55D1 4 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Page 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Reviews: