background image

© 2009 Trane

18-AC55D1-4

Installer’s Guide

structure to prevent excess roof run-off water from
pouring directly on the unit. Do not locate unit(s) close
to bedroom(s).

4. The top discharge area must be unrestricted for at least

five (5) feet above the unit.

5. When the outdoor unit is mounted on a roof, be sure the

roof will support the unit’s weight.  Properly selected
isolation is recommended to prevent sound or vibration
transmission to the building structure.

6. The maximum length of refrigerant lines from outdoor to

indoor unit should NOT exceed eighty (80) feet.

7. If outdoor unit is mounted above the air handler, maxi-

mum lift should not exceed twenty-five (25) feet (suction
line).  If air handler is mounted above condensing unit,
maximum lift should not exceed twenty-five (25) feet
(liquid line).

NOTE:
Refer to “Refrigerant Piping Software” Pub. No. 32-3312-0*,
and “Refrigerant Piping Manual” Pub. No. 32-3009-0* (the
position of the * denotes latest revision number).

8. Locate and install indoor coil or air handler in accor-

dance with instruction included with that unit.

C. INSTALLING REFRIGERANT LINES

CAUTION

!

If using existing refrigerant lines make certain that all joints
are brazed, not soldered.

Condensing units have provisions for braze connections.

Pressure taps are provided on the service valves of outdoor
unit for compressor suction and liquid pressures.

The indoor end of the recommended refrigerant line sets may
be straight or with a 90 degree bend, depending upon situa-
tion requirements.  This should be thoroughly checked out
before ordering refrigerant line sets.

The gas line must always be insulated.

CAUTION

!

In scroll compressor applications, dome temperatures may
be hot. Do not touch top of compressor, may cause minor
to severe burning.

The units are factory charged with the system charge
required when using fifteen (15) feet of connecting line. Unit
nameplate charge is the same.

Final refrigerant charge adjustment is necessary. 

Use

the Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.

3. Determine the best starting point for routing the

refrigerant tubing — INSIDE OR OUTSIDE THE
STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both

liquid and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly

secure the tubing before making connections.

8. To prevent a noise within the building structure due to

vibration transmission from the refrigerant lines, the
following precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation
type hangers.

b. Isolation hangers should also be used when refriger-

ant lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill,

they should be insulated and isolated.

d. Isolate the lines from all ductwork.

D. SERVICE VALVE OPERATION

BRASS LIQUID LINE SERVICE VALVE

The Brass Liquid Line Service Valve is factory shipped in the
seated position to hold factory charge.  The pressure tap
service port (when depressed) opens only to the field brazing
side of the valve when the valve is in the seated position.
The liquid line valve is 

not 

a back seating valve (see

WARNING 

below).

WARNING

!

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclock-
wise only until the stem contacts the rolled edge. (See
Figure 3) No torque is required.

BRASS GAS LINE SERVICE VALVE

The Brass Gas Line Service Valve is shipped in the closed
position to hold the factory refrigerant charge.  The pressure
tap service port (when depressed) opens only to the field
brazing side when the valve is in the closed position. The Gas
Line Service Valve is full open with a 1/4 turn.  See Figure 4.

BRAZING REFRIGERANT LINES

1. Remove lower access cover to access service valves.

2. Before brazing, remove plugs from external copper stub

tubes.  Clean internal and external surfaces of stub
tubes prior to brazing.

3. Cut and fit tubing, minimizing the use of sharp

90° bends.

4. Insulate the entire gas line and its fittings.

5. Do 

NOT

 allow uninsulated liquid line to come in direct

contact with bare gas line.

6. Precautions should be taken to avoid heat damage

to the pressure tap valve core during brazing.  It is

BASEPAN TAB REMOVAL

2

Summary of Contents for 4TTX6

Page 1: ...is hygroscopic action the system should remain sealed whenever possible Never break a vacuum with air and always change the driers when opening the system for component replacement Check for transport...

Page 2: ...o rebend once it has been shaped 3 Determine the best starting point for routing the refrigerant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liqu...

Page 3: ...acuum pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns i...

Page 4: ...installed in the air han dling device according to the instructions accompanying the air handler and the heaters I START CONTROL Some models have quick start components which are factory installed Fo...

Page 5: ...to Field Hook up Diagrams above 4TTX6 units require 80 airflow with Y1 first stage 100 airflow with Y2 second stage Note A The installer must jumper at the LVTB R to O Note B Cut remove the factory in...

Page 6: ...2 5 8 756 29 3 4 5 8 5 16 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 692 27 1 4 4TTX6036B 4 1064 41 7 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 730 28 3 4 4TTX6048B 4 1267 49 7 8 94...

Page 7: ...18 AC55D1 4 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Page 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Reviews: