background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT —

This Document is 

customer property

 and is to remain with this unit.  Please return to service information

pack upon completion of work.

Installer’s Guide

18-AC55D1-4

Condensing Units

4TTX6

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation.  All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. 

 Should further information be

desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

The following instructions cover 4TTX6 Condensing Units.

See special wiring and sequence of operation on page 5.

NOTICE:
These outdoor units may be used with indoor units
equipped with Thermostatic Expansion Valve only.

WARNING

!

These units use R-410A refrigerant which operates at 50%
to 70% higher pressures than R-22. Use only R-410A
approved service equipment. Refrigerant cylinders are
painted a “Rose” color to indicate the type of refrigerant
and may contain a “dip” tube to allow for charging of liquid
refrigerant into the system. All R-410A systems use a POE
oil that readily absorbs moisture from the atmosphere. To
limit this “hygroscopic” action, the system should remain
sealed whenever possible. Never break a vacuum with air
and always change the driers when opening the system for
component replacement.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit.  The electrical power
available must agree with that listed on the nameplate.

B. LOCATION & PREPARATION OF THE UNIT

1. When removing unit from the pallet, notice the tabs on

the basepan. Remove tabs by cutting with a sharp tool as
shown in Figure 2 (see page 2).

2. The unit should be set on a level support pad at least as

large as the unit base pan, such as a concrete slab. If this
is not the application used please refer to application
bulletin “XL16i-APG**-EN” (* latest revision number).

3. The support pad must NOT be in direct contact with any

structure.  Unit must be positioned a minimum of 12"

1

CAUTION

!

UNIT CONTAINS R-410A REFRIGERANT!

R-410A OPERATING PRESSURE EXCEEDS THE 
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS 
REQUIRED. FAILURE TO USE PROPER SERVICE 
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR 
PERSONAL INJURY.

SERVICE

USE ONLY R-410A REFRIGERANT AND

APPROVED POE COMPRESSOR OIL.

from any wall or surrounding shrubbery to insure
adequate airflow.  Clearance must be provided in front of
control box (access panels) & any other side requiring
service access to meet National Electrical Code.  Also,
the unit location must be far enough away from any

5 FT. ABOVE UNIT-UNRESTRICTED

Summary of Contents for 4TTX6

Page 1: ...is hygroscopic action the system should remain sealed whenever possible Never break a vacuum with air and always change the driers when opening the system for component replacement Check for transport...

Page 2: ...o rebend once it has been shaped 3 Determine the best starting point for routing the refrigerant tubing INSIDE OR OUTSIDE THE STRUCTURE 4 Provide a pull thru hole of sufficient size to allow both liqu...

Page 3: ...acuum pump and observe the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns i...

Page 4: ...installed in the air han dling device according to the instructions accompanying the air handler and the heaters I START CONTROL Some models have quick start components which are factory installed Fo...

Page 5: ...to Field Hook up Diagrams above 4TTX6 units require 80 airflow with Y1 first stage 100 airflow with Y2 second stage Note A The installer must jumper at the LVTB R to O Note B Cut remove the factory in...

Page 6: ...2 5 8 756 29 3 4 5 8 5 16 143 5 5 8 92 3 5 8 210 8 1 4 79 3 1 8 692 27 1 4 4TTX6036B 4 1064 41 7 8 946 37 1 4 870 34 1 4 3 4 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 730 28 3 4 4TTX6048B 4 1267 49 7 8 94...

Page 7: ...18 AC55D1 4 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Page 8: ...X X X 6 Inform owner on how to operate system and what to expect of it At the same time deliver Owner s Use and Care Booklet CHECKOUT PROCEDURE After installation has been completed it is recommended...

Reviews: