5.5 Reuse Existing Refrigerant Lines
For retrofit applications, where the existing
indoor evaporator coil and/or refrigerant lines
will be used, the following precautions should
be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
CAUTION
!
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important:
Take precautions to prevent noise
within the building structure due to vibration
transmission from the refrigerant lines.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
• Minimize the number of 90º turns.
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
Isolation From Joist/Rafter
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appro-
priate method every 8 ft.
Joist/Rafter
Isolator
Line Set
8 Feet Maximum
5.4 Refrigerant Line Insulation
Important:
The Vapor Line must always be
insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal)
contact.
Vapor Line
Liquid Line
Insulation
Summary of Contents for 4TTR6018J
Page 23: ...18 AC98D1 7D EN 23 Section 17 Wiring Diagrams 024N 036N Models...
Page 24: ...24 18 AC98D1 7D EN 024N 036N Models...
Page 25: ...18 AC98D1 7D EN 25 048N Models...
Page 26: ...26 18 AC98D1 7D EN 048N Models...
Page 27: ...18 AC98D1 7D EN 27 060N Models...
Page 28: ...28 18 AC98D1 7D EN 060N Models...
Page 29: ...18 AC98D1 7D EN 29 018J 030J 036J 048J Models...
Page 30: ...30 18 AC98D1 7D EN 018J 030J 036J 048J Models...
Page 31: ...18 AC98D1 7D EN 31 035J Models PRINTED FROM D157362P05 REVB...
Page 32: ...32 18 AC98D1 7D EN PRINTED FROM D157362P05 REVB 035J Models...
Page 33: ...18 AC98D1 7D EN 33 049J 061C Models...
Page 34: ...34 18 AC98D1 7D EN 049J 061C Models...
Page 35: ...18 AC98D1 7D EN 35 060J 060K Models...
Page 36: ...36 18 AC98D1 7D EN 060J 060K Models...
Page 43: ...18 AC98D1 7D EN 43 Notes...