background image

© 2010 American Standard Heating & Air Conditioning

Installer’s Guide

6. When the air handler with supplementary heater is

to be installed in the downflow position on combus-
tible flooring an accessory sub-base (TAYBASE100
for 4TEE3F39-64) must be used. See Figure 1.

7. If supplementary heat is to be added, power supply

must be sufficient to carry the load. In addition,
minimum air flow settings, unit and duct clearances
to combustible material must be maintained as
stated on the air handler rating nameplate.

CAUTION

!

For air handlers not equipped with a factory installed
electric heater, a field installed heater is available from
American Standard Inc. Only heaters built by American
Standard Inc. are approved for use in the air handler.
These heaters have been designed and tested in accor-
dance with UL standards to provide safe and reliable
operation. A list of approved heaters is provided on the
air handler rating nameplate. Heaters that are not fac-
tory approved could cause damage and are not cov-
ered under equipment warranty.

NOTE: If air handler is used WITHOUT a supplementary
electric heater, a sheetmetal plate is required to cover
the open hole in the airflow system (See Figure 2)

.

 In

addition, ensure that the cabinet is sealed air tight
where the field wires enter the unit.

These air handlers are suitable for installation in a
closet, alcove or utility room with free, non-ducted, air
return, using the area space as a return air plenum.
With ducted supply air, if the minimum clearances to
combustible materials and service access are observed,
the above installations are suitable.
This area may also be used for other purposes, includ-
ing an electric hot water heater - 

but in no case shall

a fossil fuel device be installed and/or operated in
the same closet, alcove or utility room.

In addition, these air handlers are suitable for installa-
tion in an attic, garage or crawl space with ducted sup-
ply and return air.
This equipment has been evaluated in accordance with
the Code of Federal Regulations, Chapter XX, Part 3280
or the equivalent. “SUITABLE FOR MOBILE HOME
USE”
For proper installation the following items must be con-
sidered:

1. If adequate power is available and correct according

to nameplate specifications.

2. Insulate all ducts, particularly if unit is located out-

side of the conditioned space.

3. Pursuant to Florida Building Code 13-610.2.A.2.1,

this unit meets the criteria for a factory sealed
air handler.

4. To ensure maximum efficiency and system perfor-

mance, the existing supply and return duct system
static pressures must not exceed the total available
static pressure of the air handler.  Reference ACCA
Manual D, Manual S and Manual RS along with the
air handler Product Data and Service Facts for addi-
tional information.

5. It is recommended that the outline drawing be stud-

ied and dimensions properly noted and checked
against selected installation site. By noting in ad-
vance which knockouts are to be used, proper clear-
ance allowances can be made for installation and
possible future service.

From Dwg. 21B140413

4"

6"

17"

1"

3/8"

1/4" HOLES (4)

ACCESSORY BAY99X123

IF AIRHANDLER IS USED 

WITHOUT

 A FACTORY FURNISHED

SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER
THE OPEN HOLE IN THE AIR FLOW SYSTEM

Figure 2

B

A

JOIST

JOIST

JOISTS

HEADER

JOISTS

HEADER

NAILS

REAR

FLANGE

FRONT OF

UNIT

HEADER

1"

NAILS

HEADER

MIN. SPACING TO
ANY COMBUSTIBLE
MATERIAL.

1"

APPROX. 3/4" FLANGES ON FIELD
FABRICATED DUCT OR PLENUM

ONE INCH DUCT SPACERS

FLOOR

SUBBASE

UNIT

FLOOR OPENING - SIZE

 MODEL NO.

A

B

 TAYBASE100

23-3/4

14-13/16

 TAYBASE101

21-3/4

14-13/16

 TAYBASE102

26-3/4

14-13/16

Figure 1

AIR HANDLER SUB-BASE

Summary of Contents for 4TEE3F39A1000A

Page 1: ...for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made against the transportation company immediately Check to be sure all major com Co...

Page 2: ...fuel device be installed and or operated in the same closet alcove or utility room In addition these air handlers are suitable for installa tion in an attic garage or crawl space with ducted sup ply a...

Page 3: ...placed on a plenum TAYPLNM100 Connecting return duct directly to the side front or rear of the cabinet is not ap proved 12 Route refrigerant condensate drain lines away from air handler so they do not...

Page 4: ...es so NOT to puncture the coil tubing c Position unit on Pedestal or other suitable foun dation If Pedestal is not used a frame strong enough to support the total weight must be pro vided Provide a mi...

Page 5: ...twork connections are made seal air tight and per Local codes DOWNFLOW BAFFLE KIT X X 7 8 GASKET SCREWS TO REMOVE COIL SCREWS TO REMOVE COIL DISCARD DRIP TRAY 1 2 GASKET INSIDE SURFACE OF BAFFLE 7 8 G...

Page 6: ...PAN TO CLEAR TABS ON COIL CHANNEL SUPPORTS FOR DOWNFLOW OR HORIZONTAL LEFT APPLICATIONS DRAINPAN SHOWN IN PLACE TAB AS MOUNTED ON COIL CHANNEL SUPPORT Figure 10 TO REMOVE BLOWER ASSEMBLY WHEN COIL IN...

Page 7: ...as well as the middle to prevent sagging The service access must remain unobstructed If the unit is sup ported along the length of the front and back with rails the air handler only needs to be sus p...

Page 8: ...urn opening shown in the outline drawings i Openings where field wiring enters the cabi net must be completely sealed Location of power entry is shown on the outline drawing Use 2 5 clear stickers pro...

Page 9: ...o secondary drain connections are provided for the different orientations See Figure 17 The lower of the two should be connected as a backup to prevent conden sate overflow by a blocked primary drain...

Page 10: ...the drain line to a closed drain sys tem 9 Use Teflon tape on the air handler drain line con nections Do Not Use pipe joint compound or PVC CPVC cement It is always recommended that an auxiliary drain...

Page 11: ...Options Switches 7 8 Auxiliary Heat DIP SWITCHES AS SHIPPED COOLING HEATING AIRFLOW FAN OFF DELAY AUXILIARY HEAT SPEEDS Figure 21 K CHECKOUT PROCEDURE 1 Check the Air Handler installation in accordanc...

Page 12: ...ERS WITH SINGLE STAGE COOLING 2 STAGE HEAT From Dwg No B801074 COMFORT CONTROL VARIABLE SPEED AIR HANDLER HEAT PUMP O D SECTION SINGLE SPEED NOTES 1 LOW VOLTAGE WIRING TO BE NO 18 A W G MINIMUM CONDUC...

Page 13: ...w during the defrost cycle 5 Connect only if used with applicable indoor thermostat 6 When heaters are used discard power leads with polarized plug PM A and connect 1 PF to mating plug in the heater c...

Page 14: ...ER CONTROL BOX AS SHOWN 4TEE3F48 AIR HANDLERS WITH 2 STAGE HEAT PUMP COMFORT CONTROL VARIABLE SPEED AIR HANDLER HEAT PUMP O D SECTION 2 STAGE NOTES 1 LOW VOLTAGE WIRING TO BE NO 18 A W G MINIMUM CONDU...

Page 15: ...18 GE12D1 8 15 Installer s Guide OUTLINE DRAWING FOR 4TEE3F39 48 64 From Dwg D802101 Rev 9...

Page 16: ...12D1 8 Installer s Guide 4TEE3F39 48 64 AIR HANDLERS DIMENSIONAL DATA Model No H W 4TEE3F39A1000A 57 90 23 50 4TEE3F48A1000A 4TEE3F48B1000A 4TEE3F64A1000A 4TEE3F39A 48A 48B 60A Are two piece cabinets...

Page 17: ...18 GE12D1 8 17 Installer s Guide...

Page 18: ...r size per nameplate specifications 4 Check control box panel in place and secured NOTE OPERATION OF HEATERS MUST BE CHECKED DURING THE OPERATION CHECK OF THE TOTAL SYSTEM 1 Make sure power is OFF at...

Reviews: