Trane 4TEE3D01B1000A Installer'S Manual Download Page 12

12

18-GE15D1-2

Installer’s Guide

Table 1 — Control Wiring

* The maximum total cable length for the entire Comfort

Control communicating system is 500 ft. 18 AWG.

* * Maximum

 total

 length of low voltage wiring from outdoor

unit, to indoor unit, and to Comfort Control.

S

T

L

O

V

4

2

-

g

n

i

r

i

W

I

I

s

s

a

l

C

C

E

N

E

Z

I

S

E

R

I

W

*

*

H

T

G

N

E

L

E

R

I

W

.

X

A

M

G

W

A

8

1

T

F

0

5

1

G

W

A

6

1

.

T

F

5

2

2

G

W

A

4

1

.

T

F

0

0

3

NOTE: If Air Handler is used with or without a heater,
the electrical entry hole as well as any other cabinet
penetrations  must be sealed air tight.

IMPORTANT: When supplementary heaters are in-
stalled, inspect to insure that all packaging material
has been removed.

I.

CONTROL WIRING

1. Connect wiring between indoor unit, outdoor unit

and Comfort Control. The use of color-coded low-
voltage wires is recommended.

2. A low voltage terminal board is provided for control

wiring, and is located on the left side of the cross
brace in the center of the unit.

3. Field wiring diagrams on pages 18-20 show the low

voltage wiring hookup for all applicable systems.
Plug-in type electrical connectors are provided for
use with supplementary heaters.

Communicating Control Wiring

WIRE SIZE

MAX. WIRE LENGTH*

18 AWG

250 FT

7.

Provide means for drainage to prevent winter
freeze-up of condensate line

.

8. Do not connect the drain line to a closed drain sys-

tem.

It is always recommended that an auxiliary drain pan
be installed under a horizontally installed Air Handler.
Connect the auxiliary drain line to a separate drain line
(no trap is needed in this line) and terminate according
to local codes.

NOTE: Do NOT use a torch or flame near the plastic
drain pan coupling.

NOTE: Do NOT tighten the drain pipe excessively. Sup-
port the condensate piping and traps outside the unit
to prevent strain on the drain coupling.

H. ELECTRICAL - POWER WIRING

1. These Air Handlers are shipped from the factory

wired for 230 Volts. The units may be wired for 208
Volts. Follow instructions on unit wiring diagram
located on inside blower panel housing and in the
Service Facts document included with the unit.

2. The selection of wire and fuse sizes should be made

according to the Minimum Branch Circuit Ampacity
and the Maximum Overcurrent Device listed on the
unit nameplate.

IMPORTANT: The BAYHTR** electric heat accessory,
designed for use with this air handler, may include up to a
combination of three 30 and / or 60 amp circuit breakers to
provide an electrical disconnect for service personnel that
is intended to help protect internal electrical components in
the event of a short circuit or ground fault. As designed, the
circuit breakers supplied in the BAYHTR** accessory do not
provide over-current protection of the branch circuit.
Therefore, the branch circuit(s) shall be sized and protected
according to the unit nameplate.

3. Field wiring diagrams for electric heaters and unit

accessories are shipped with the accessory.

4. Wiring must conform to National and Local codes.

Ground unit per Local codes following recognized
safety procedures.

If an electric heater is not installed, the installer MUST
seal opening with a sheet metal plate made per Figure
1 and the Knockout Plate provided in the Accessory Kit
MUST be installed on the air handler and the conduit
terminated to it. The electrical connections are made
using the two power leads and ground wire connections
which are located near the discharge of the blower.

Openings where field wiring enters the cabinet
must be completely sealed.

 Location of power entry

is shown on the outline drawing.  Use 2.5" clear stick-
ers to seal all unused electrical knockouts.  See Figure
13.

Summary of Contents for 4TEE3D01B1000A

Page 1: ...from the factory in the upflow or horizontal right configuration Variable Speed Communicating Air Handlers with Integrated Whole House Air Cleaner 4TEE3D01B1000A 4TEE3D02B1000A 4TEE3D03B1000A NOTE Rep...

Page 2: ...plate Heaters that are not factory approved could cause damage and are not covered under equipment warranty INSTALLATION LIMITATIONS RECOMMENDATIONS The general location of the Air Handler is normally...

Page 3: ...allation instruc tions These should only be installed on the supply air side of the system 23 Unit installation must include either a return air duct or grille that prevents accidental access to pins...

Page 4: ...8 LOCATED ON LEFT SIDE 1 2 3 4 Figure 4 Two Piece Wrapper Spear Closeup NOTE Make certain that the unit has been installed in a level position to ensure proper draining UPFLOW 1 Before installing unit...

Page 5: ...baffle See Figure 12 a Remove the factory installed baffle assembly from the apex of the coil by using a 5 16 nutdriver to remove the screws b Replace this baffle with the factory supplied nar row coi...

Page 6: ...ckets Remove and Discard Replace with Narrow Baffle For Maximum Efficiency on Upflow Figure 12 Baffle Replacement Figure 13 Electrical Knockouts Electrical Knockout Sticker Sheet 12 After ductwork con...

Page 7: ...Actuator Tab Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL FIELD CHARGER COLLECTION CELL HORIZONTAL RIGHT Actuator Tab Electrical Contacts Electrical Contacts Figure 14 COLLECT...

Page 8: ...cal Contacts on Bottom side FIELD CHARGER COLLECTION CELL DOWNFLOW Actuator Tab Electrical Contacts Electrical Contacts FIELD CHARGER COLLECTION CELL Downflow and Horizontal Left orientations availabl...

Page 9: ...ation isolators field supplied must be placed under the unit 4 It is always recommended that an auxiliary drain pan be installed under a horizontal Air Handler See Condensate Drain Piping to prevent p...

Page 10: ...utline drawing on page 21 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE If the convertible duct flanges are not used they must be...

Page 11: ...of air handler condensate drain connection Close as possible Figure 22 Field Fabricated Traps 2 MINIMUM 2 MINIMUM EZT 105 Figure 21 Manufactured Traps Figure 20 Drain Connections 3 4 NPT Primary drai...

Page 12: ...Sup port the condensate piping and traps outside the unit to prevent strain on the drain coupling H ELECTRICAL POWER WIRING 1 These Air Handlers are shipped from the factory wired for 230 Volts The u...

Page 13: ...ge 1 2 3 heat humidifier and EAC relays User Interface displays UNIT TEST EXIT Displayed for three seconds NOTE Airflow is default or programmed selections J AIRFLOW ADJUSTMENT Blower speed changes ar...

Page 14: ...14 18 GE15D1 2 Installer s Guide USERINTERFACEMENU COMMUNICATINGMODE Figure 24 User Interface Menu Communicating Mode...

Page 15: ...18 GE15D1 2 15 Installer s Guide USER INTERFACE MENU 24 VAC MODE Figure 25 User Interface Menu 24V Mode...

Page 16: ...arge Air Sensor Open Error 6 Flash N A RAS RNG ERR N A 117 Return Air Temperature Fault Return Air Temperature Range Error RAS SHORT Return Air Sensor Short Error RAS OPEN Return Air Sensor Open Error...

Page 17: ...ller s Guide M FIELD WIRING REFERENCE ONLY COMMUNICATING INDOOR UNIT WITH COMMUNICATING COMFORT CONTROL COMMUNICATING OUTDOOR UNIT COMMUNICATING INDOOR UNIT WITH COMMUNICATING COMFORT CONTROL 24 VAC S...

Page 18: ...8 18 GE15D1 2 Installer s Guide COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC SINGLE STAGE COOLING COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC 2 STAGE OR 2 STEP COOLING...

Page 19: ...GE15D1 2 19 Installer s Guide COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC SINGLE STAGE HEAT PUMP COMMUNICATING INDOOR UNIT WITH 24 VAC COMFORT CONTROL 24 VAC 2 STAGE OR 2 STEP HEAT PU...

Page 20: ...20 18 GE15D1 2 Installer s Guide N OUTLINE DRAWING FOR 4TEE3D01 10 Printed from D802612REV03...

Page 21: ...000A 43 00 21 50 4TEE3D02A1000A 45 00 23 50 4TEE3D03A1000A 57 90 23 50 4TEE3D04A1000A 57 90 23 50 4TEE3D05A1000A 51 75 26 00 4TEE3D06A1000A 57 90 23 50 4TEE3D07A1000A 57 90 26 00 4TEE3D08A1000A 57 90...

Page 22: ...CLEANING THE COLLECTION CELL 1 Turn the air conditioning system off at the Comfort Control 2 Loosen thumbscrews to remove the filter panel Remove the COLLECTION CELL by pulling for ward See Figure 5 p...

Page 23: ...IATE GLOVES WHEN HANDLING THE FIELD CHARGER 4 Wipe down the face plate of the FIELD CHARGER with a dry shop towel or use a vacuum cleaner NOTE Do NOT disassemble the FIELD CHARGER 5 Push a block of fo...

Page 24: ...the variable speed motor d Turn the system power ON e Turn the Comfort Control to Fan only setting f Check for LED illumination on the power supply to the air cleaner LED illumination indicates High V...

Reviews: