Installing the Indoor Unit
Prepare the Indoor Unit
1. Determine the mounting location on the ceiling or wall by using the installation template. Mark
the bolt locations and remove the installation template.
2. Remove the return air grille, side panels and the hanger bracket from the indoor unit. Open the
air inlet grille and the screw cover and remove the screws.
3. Loosen the side panel fixing screw and remove the side panels.
4. Loosen the two hanger bracket setting bolts (M8) on each side by about 0.4 inches (10mm).
5. Remove the two hangber bracket fixing bolts (M6) on the rear side. Detach the hanger bracket
by pulling it backward.
6. Release the claws in the 3 places indicated.
7. Release the center hook and remove the front panel.
8. Release the claws in the places indicated on the electric box cover and remove the box.
Installing the Unit
1. Once the mounting location has been marked using the installation template, drill the mounting
holes. The unit must be level to ensure proper condensate drainage.
2. Insert the anchor bolts into the drilled holes, and drive the pins completely into the anchor bolts
with a hammer.
3. Fix the hanger bracket to the anchor bolts.
4. Put the hanger bolt into the clasp of the indoor unit and tighten the screws on the hanger to
prevent the indoor unit from moving.
5. Reinstall and tighten the right and left side panels.
Floor Installation
12
Floor and Ceiling Unit